Page 96
1.3.6 Fixed temp.c...
04. 07. 2015
10:37
Control 1
Variant 1
T fixed 1
step-wise
70.0°C
1.3.10 Post Heatin...
04. 07. 2015
10:37
Activation
Boiler type
Hysteresis
Min. temp.
Solid fuel boiler
10.0K
40.0°C
1.3.10 Post Heatin...
04. 07. 2015
10:37
Max. temp.
Sensor boiler
Time block 1
Time block 2
Time block 3
55.0°C
TS4
PROFESSIONAL MODE
If control algorithms have been
defined as ›Fixed T‹ under
›1.3.7 Output parameter‹, the
appropriate outputs can be configured here.
In case of the fixed temperature control, the
collector is controlled to the preset tempera-
ture via a variable pump delivery rate.
Continue with ›Post Heating Requ.‹.
Use ›Boiler sensor‹ to assign the temperature
sensor which supplies the temperature value
of the boiler.
Up to six time blocks can
be activated for reheating.
Here, reheating can be activated.
The boiler is defined as
›Solid-fuel boiler‹ or ›Gas/oil‹.
In case of solid-fuel boilers reheating is made
via the charge pump of the drinking water
tank and is only activated if the temperature
of the tank is within the values ›Min. temp.‹
and ›Max. temp.‹.