Page 104 PROFESSIONAL MODE
1.6 Monitoring
04. 07. 2015
10:44
Message list
DiffTemp
Volume flow
Coll.Emerg.OFF
Sensor balancing
1.6.2 dT monitoring
04. 07. 2015
10:44
dT coll/stor
t max.coll/tank
Monitoring of
30.0K
10min
---
1.6.3 Phi monitoring
04. 07. 2015
10:44
flow rate RO1
The following items appear under ›1.6. Moni-
toring‹ next to the operation mode menus:
- ›DiffTemp‹
- ›Volume flow‹
- ›Coll.Emerg.OFF‹
- ›Sensor balancing‹
Call up the menu item ›DiffTemp‹.
›Phi monitoring‹ accesses any
flow menu for which volume flow
sensors have been configured.
Select appropriate submenu.
›dT monitoring‹ is used to define the
criteria which lead to fault detection.
›dT coll/stor‹ is used to define a differential
temperature between collector and tank, and
›t max.coll/tank‹ for the relevant period of
time.
If ›dT coll/stor‹ is exceeded within ›t max.
coll/tank‹, the controller detects a fault.
With ›Monitoring of‹, the monitoring of the
feed and return temperature
of the heat counter can be selected.
Continue with ›Volume flow‹.