Page 102
1.5.3 Antifreeze pr.
04. 07. 2015
10:42
T ON
Glycol type
Tank
5.0°C
Water
Priority tank
1.5.4 Anti-legionellae
04. 07. 2015
10:43
Repetition
T legionellae
t-ON
t-monitor
Activation
1 day
60.0°C
01:00
60min
1.5.5 Cooling funct.
04. 07. 2015
10:43
Activation
Hyst.tank 1
Hyst.tank 2
t-ON
t OFF
2.0K
2.0K
00:00
07:00
PROFESSIONAL MODE
Here, the parameters for tank cooling are
defined.
›t-ON‹ and ›t-OFF‹ are used to define the
appropriate time slot in which the tank is to
be cooled via the collector, and ›Hyst.tank
1‹ and ›Hyst.tank 2‹ are used to define the
switch-ON hysteresis.
Continue to scroll.
These parameters must be set by the fitter
based on the applicable national regulations.
›Function‹ is used to define the period in
days (1day - 7days) during which legionella
reduction must have occurred at least once.
›t-ON‹ is used to define the time of a
possibly required reheating cycle.
›T legionellae‹ defines the disinfection
temperature. ›t monitor‹‹ is used to
define the minimum disinfection time.
Continue with ›Tank cooling‹.
In the case of plants with two tanks,
the source of the anti-freeze protection
heat must be selected by specifying
›Priority tank‹ or ›Secondary tank‹.
Continue with ›Anti-legionellae‹.