background image

30369-4-1013

Page 30

OpTIONAL BLOWER ACCESSORY INFORMATION

The appliance, when installed must be electrically con

-

nected and grounded in accordance with local codes or, 

in the absence of local codes, with the current CSA C22.1 

Canadian Electrical Code.
U.S.  Installations,  follow  local  codes  and  the  National 

Electrical Code, ANSI/NFPA No. 70.
Should this blower require servicing, the power supply 

must be disconnected. For rewiring of any replacement 

components, refer to Figures 43 and 44 and the parts list 

included with the blower assembly instructions.

BLOWER ACCESSORY

Operation

The  fireplace  is  equipped  to  receive  an  optional  FBB8  blower 

accessory that includes a fan control switch, plus a rheostat 

(speed control).

If you choose to install the optional blower, you can expect it to 

operate as follows:

From a cold start, the temperature activated fan control switch will 

normally take 5-10 minutes to heat up and energize the blower.

Once the blower is energized, adjust the blower speed  control as 

desired, then replace the surround kit assembly.

When the fireplace is shut off, it may take 30-40 minutes for  the 

heated unit to dissipate (cool down) enough for the blower to shut 

off automatically. 

NOTICE

: The blower shut off times will vary on 

blower speed and BTU input level setting control by adjustment of 

the HI/LO knob located on the gas valve.

Note: For installation of FBB8 blower accessory, refer to the 

instructions included with the blower kit.

Note:  The fan control switch is secured with two 8-32 Hex nuts to 

the bottom side of the firebox. Threaded studs are provided 

at the center of the fireplace, approximately 5” behind the 

front of the fireplace.

Figure 43

Figure 44

FAN CONTROL

SWITCH

FBB8 BLOWER ASSEMBLY

VALVE

PIEZO IGNITOR

REMOTE/OFF/ON SWITCH

FAN SPEED CONTROL

JUNCTION BOX

Summary of Contents for DVL25FP32N-2

Page 1: ...he information in these instruc tions are not followed exactly a fire or explo sion may result causing property damage personal injury or loss of life WARNING HOT GLASS DO NOT TOUCH NEVER WILL CAUSE B...

Page 2: ...tion 26 27 Alternate On Off Switch Installation 28 Surround Panel Installation 29 Optional Blower Accessory Information 30 Optional Decorative Glass Placement 31 Operating Instructions 32 Standing Pil...

Page 3: ...he glass front or any part removed for servicing the appliance must be replaced prior to operating the appliance Work should be done by a qualified service person Keep burner and control compartment c...

Page 4: ...erform service or make adjustments in an area where the conditions are such that you may not detect the odor if there has been a leak of LP Gas Odor fade due to oxidation by rust or adsorption on wall...

Page 5: ...2nd St New York N Y 10036 Any alteration of the original design installed other than as shown in these instructions or use with a type of gas not shown on the rating plate is the responsibility of the...

Page 6: ...ical vent kit DVVK 4FRE Horizontal flex vent kit round cap DVVK 4RE Horizontal round termination wall thick ness up to 11 7 16 DV822 Vinyl siding kit for DVVK 4RE DVVK 4F Horizontal flex vent kit DVVK...

Page 7: ...supply requirements for optional blower Properly framed opening size required for installation of the fireplace DV FIREPLACE DIMENSIONS MODEL A B C D E F G H I J K L M N O DVL25FP 37 1 2 26 14 1 4 10...

Page 8: ...EDGE OF DOOR FRAME 3 MIN 3 MIN 3 MIN TOP VIEW NON COMBUSTIBLE AREA TO SIDES AND BACK OF FIREPLACE Figure 3 3 MIN CLEARANCE ABOVE VENT SYSTEM 1 MIN CLEARANCE FROM FRAMING TO VENT SYSTEM 25 MIN DISTANC...

Page 9: ...ails in Venting Section When you install your Direct Vent Fireplace in D Room divider or E Flat on wall corner positions a minimum of 6 inches clearance must be maintained from the perpendicular wall...

Page 10: ...dures results in pressures in excess of 1 2 psig 14 w c 3 5 kPa on the fireplace gas valve it will result in a hazardous condition Checking Manifold Pressures Both Propane and Natural gas valves have...

Page 11: ...en a metal or wood panel is placed beneath the appliance 4 Install the side Framing brackets 1 per side using the pi lot holes provided behind the side flanges on the fireplace outer wrap Two setback...

Page 12: ...Clearance Note Maintain one inch 1 of clearance around vertical vent pipe See Figure 11 For horizontal vent maintain a minimum 1 clearance to the bottom and sides of the vent and 3 clearance to combus...

Page 13: ...16 C 14 1 16 15 5 16 D 53 1 2 60 3 8 Optional Blower Accessory The Loft fireplace may be equipped with an optional FBB8 blower accessory See page 38 The blower accessory may be installed at any time...

Page 14: ...cal Building Codes before beginning the installation WARNING THIS GAS FIREPLACE AND VENT ASSEMBLY MUST BE VENTED DIRECTLY TO THE OUTSIDEAND MUST NEVER BE ATTACHED TO A CHIMNEY SERVING A SEPARATE SOLID...

Page 15: ...ing out at joints or seams Condensate can cause corrosion of caps pipe and fittings It may be caused by having excessive lateral runs or having exterior portions of the system exposed to cold weather...

Page 16: ...does not apply if the 45 degree elbows are installed on the vertical part of the vent system Reduce 3 for every 90 elbow Example According to the chart the maximum horizontal vent length is 20 and if...

Page 17: ...evel a snorkel kit is recommended It allows installation depth down to 7 178 mm below grade level The 7 178 mm is measured from the center of the horizontal vent pipe as it penetrates through the wall...

Page 18: ...nued Positioning the Fireplace Determine the exact position of the appliance so the direct vent termination will be centered if possible between two 2 studs This will avoid any extra framing All vent...

Page 19: ...re 25 Figure 26 EXAMPLES TOP VENT RUN 24 MINIMUM CLEARANCE TO COMBUSTIBLES 24 H2 H1 V1 Example H2 2ft 2 90 90 6ft H 8ft V 15ft 3 ft 914 mm H3 1 ft 305mm 4 ft 122mm 6 ft 1 83M 21 ft 6 4M 10 ft 3M V 21f...

Page 20: ...lace in such a way that minimizes the number of offsets and horizontal vent length Since it is very important that the venting system maintain its balance between the combustion air intake and the flu...

Page 21: ...center line of the regulator I clearance to service regulator vent outlet 6 feet 1 89 m minimum J clearance to non mechanical air supply inlet to building or the combustion air inlet to any other appl...

Page 22: ...f each starting outer pipe line up rotate pipe section clockwise 90 approximately 3 inches The vent pipe is now locked together Continue adding components per the pre planned vent system configuration...

Page 23: ...ANCE TO COMBUSTIBLES FROM VERTICAL VENT 12 MIN 304 8mm CLEARANCE TO COMBUSTIBLES 3 MIN 76 2mm CLEARANCE TO COMBUSTIBLES Figure 30 Installing Firestops Firestops are required for safety whenever the ve...

Page 24: ...r any obstructions such as wiring or plumbing runs Reposition the appliance and vent system if necessary to accommodate ceiling joists and or obstructions Cut a 10 inch x 10 inch hole through the ceil...

Page 25: ...tside edge too so as to make a seal to the exterior wall NOTE Wood screws can and should be replaced with appropriate fasteners for use on stucco brick concrete or other types of siding CAUTION Ifexte...

Page 26: ...s holes These components should immediately be replaced 2 Remove the cap and shine a flashlight down the vent Remove any bird nests or other foreign material 3 Check for evidence of excessive condensa...

Page 27: ...daptoronfireplace Replace the horizontal and vertical pipe lengths elbows and horizontal or vertical termination kit All vent system components lock into place by sliding the concentric pipe section w...

Page 28: ...f switch located on the front of the control module tray 3 Run the low voltage alternate switch wires over to the right or left surround panel Then secure the wires with wire clips provided See Figure...

Page 29: ...TO SIDE FLANGES ON INSERT BACK SIDE NOTE INSTALL SURROUND ASSEMBLY SO THAT THE REAR FLANGE OF THE TOP PANEL SETS OVER THE TOP EDGE OF THE TOP SUPPORT BRACKET CENTER SURROUND LEFT TO RIGHT THEN SWING...

Page 30: ...ollows From a cold start the temperature activated fan control switch will normally take 5 10 minutes to heat up and energize the blower Once the blower is energized adjust the blower speed control as...

Page 31: ...only be performed after the DVL Fireplace has been fully installed secured and tested for leaks If operating the burner with a Remote Control make sure all batteries are installed and that the burner...

Page 32: ...our pilot flame to operate an additional one 1 to two 2 minutes before you turn the gas control knob from the PILOT position to the ON position This time period allows the millivolts electrical curren...

Page 33: ...ed setting THERMOCUPLE ELECTRODE THERMOPILE PILOT FOR YOUR SAFETY READ BEFORE LIGHTING Warning If you do not follow these instructions exactly a fire or explosion may result causing property damage pe...

Page 34: ...VE WILL BE DESTROYED WARNING LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROL WIRING ERRORS CAN CAUSE IM PROPER AND DANGEROUS OPERATION VERIFY PROPER OPERATION AFTER SERVICING For Standin...

Page 35: ...he pilot flame Be sure the wire connections from the thermopile at the gas valve terminals are tight and the thermopile is fully inserted into the pilot bracket Check the thermopile with a millivolt m...

Page 36: ...ded that the pilot remain in the CPI standing pilot mode to reduce cold start issues and or conserve battery backup power during a power outage 3 The gas valve has inlet and outlet pressure taps as sh...

Page 37: ...ION Do not operate the appliance with panel s removed cracked or broken Replacement of the panel s should be done by a licensed or qualified service person WARNING Improper installation adjustment alt...

Page 38: ...ormation Lighting Instructions FOR YOUR SAFETY READ BEFORE LIGHTING Warning If you do not follow these instructions exactly a fire or explosion may result causing property damage personal injury or lo...

Page 39: ...uctions on page 38 and Wiring Diagram on page 37 Troubleshooting Before proceeding with the procedures in the following trouble shooting table verify that the power supply AC DC adapter is present and...

Page 40: ...e wire harness 4 Replace the DFC board 1 Verify the electrical connections integrity and make sure they are in accordance with the relevant system wiring diagram If necessary replace the wire harness...

Page 41: ...ase and verify voltage at ignition between the EV1 terminal and the ground connection on the valve body 5 1 If the voltage is greater than 0 then Replace Valve 5 2 Or Replace DFC 6 Check the pressure...

Page 42: ...manufacturing processes fingerprints along with excess sealing materials may be present and should be removed When cleaning do not use abrasives on the porcelain liners or the glass door assembly Clea...

Page 43: ...el Number Float DF 25 33 S BL HP SS Black Hammered Pewter Stainless Steal Must also use 4 sided surround 4 Sided Surround DS 25 33 66BL Black Manhattan DF 25 33 N BL HP Black Hammered Pewter Must also...

Page 44: ...5 17155 17155 FLUE OUTLET ASSEMBLY 5 M163 M163 M163 M163 GASKET FLUE CONNECTOR 6 16223 27718 16223 27718 SPRING RETAINER ASSEMBLY 7 30577 30577 30577 30577 NAILING FLANGE 8 R10854 R10854 R10854 R10854...

Page 45: ...45mm P182 55 P208 1 45mm ORIFICE LP GAS 26 R7624 R7624 R7624 R7624 AIR SHUTTER 27 R10732 R10879 R10732 R10879 TUBE BURNER 28 11269 11269 11269 11269 GAS LINE BRACKET 29 28067 28067 28067 28067 BURNER...

Page 46: ...anty parts All parts listed in the Parts List have a Part Number When ordering parts first obtain the Model Number and Serial Number from the name plate on your equipment Then determine the Part Numbe...

Page 47: ...iance must be installed by a qualified installer and operated in accordance with the instructions furnished with the ap pliance A bill of sale cancelled check or payment record should be kept to verif...

Page 48: ...s Empire Comfort Systems Inc 918 Freeburg Ave Belleville IL 62220 If you have a general question about our products please e mail us at info empirecomfort com If you have a service or repair question...

Reviews: