background image

30369-4-1013

Page 26

Locate and mark the center point of the vent pipe using a nail on 

the underside of the roof. Drive the nail through the center point. 

Mark the outline of the roof hole around this center point.

NOTE:

  Size of the roof hole dimensions depend on the pitch of 

the roof. There must be a 1 inch clearance (25 mm) to the 

vertical pipe sections. This clearance is to all combustible 

material. 

Cover the opening of the vent pipe and cut and frame the roof hole. 

Use framing lumber the same size as the roof rafters and install the 

frame securely. Flashing anchored to frame must withstand high 

winds. The storm collar is placed over this joint to make a water-tight 

seal. Non-hardening sealant should be used to completely seal this 

flashing installation.

Determining Minimum Vent Height Above the Roof.
WARNING: Major U.S. building codes specify minimum chimney 

and/or vent height above the roof top. These minimum heights 

are necessary in the interest of safety. These specifications are 

summarized in Figure 36

.

VENT CAP

GAS VENT

H

LOWEST

DISCHARGE

OPENING

H (Min.) - Minimum height from

roof to lowest discharge opening

ROOF PITCH IS X/12

ROOF PITCH

H (Min.)

Flat to 6/12

12" (305 mm)

6/12 to 7/12

15" (381 mm)

Over 7/12 to 8/12

18" (457 mm)

Over 8/12 to 16/12

24" (610 mm)

Over 16/12 to 21/12 36" (914 mm)

Figure 36

Note that for steep roof pitches, the vent height must be increased. 

In high wind conditions, nearby trees, adjoining roof lines, steep 

pitched roofs, and other similar factors can result in poor draft, or 

down-drafting. In these cases, increasing the vent height may solve 

this problem.

General Maintenance

Conduct an inspection of the venting system semi-annually. 

Recommended areas to inspect are as follows:

1.  Check areas of the venting system which are exposed to the 

elements for corrosion. These will appear as rust spots or 

streaks and, in extreme cases, holes. These components should 

immediately be replaced.

2.  Remove the cap and shine a flashlight down the vent. Remove 

any bird nests or other foreign material.

3.  Check for evidence of excessive condensate, such as water 

droplets forming in the inner liner and subsequently dripping 

out at joints. Condensate can cause corrosion of caps, pipe and 

fittings. It may be caused by having excessive lateral runs, too 

many elbows and exterior portions of the system being exposed 

to cold weather.

4.  Inspect joints to verify that no pipe sections or fittings have been 

disturbed and, consequently, loosened. Also, check mechanical 

supports, such as wall straps or plumbers’ tape for rigidity. 

Venting terminal shall not be recessed into a wall or siding.
A removable panel or other means must be provided in the enclosure 

for visual inspection of the flue connection.

NOTE: This also pertains to vertical vent systems installed on the 

outside of the building.
Slide the vertical vent cap over the ends of the vent pipe and secure. 

See Figure 37.

Installing the Vent System in a Chase

A chase is a vertical box-like structure built to enclose the gas 

appliance and/or it’s vent system. Vertical vent runs on the outside 

of a building may be, but are not required to be installed inside a 

chase.

Figure 37

CAUTION: Treatment of firestop spacers and construction of 

the chase may vary with the type of building. These instructions 

are  not  substitutes  for  the  requirements  of  local  building 

codes. Therefore, your local building codes must be checked 

to determine the requirements for these steps.

NOTE: 

When installing this vent system in a chase, it is always good 

building practice to insulate the chase as you would the outside 

walls of your home. This is especially important for cold climate 

installations. Upon completion of building your chase framing, 

install the vent system by following the instructions in this manual. 

Remember to build the chase large enough so that minimum 

clearance of combustible materials (including insulation) to the vent 

system are maintained.

vERTICAL TERMINATION

Summary of Contents for DVL25FP32N-2

Page 1: ...he information in these instruc tions are not followed exactly a fire or explo sion may result causing property damage personal injury or loss of life WARNING HOT GLASS DO NOT TOUCH NEVER WILL CAUSE B...

Page 2: ...tion 26 27 Alternate On Off Switch Installation 28 Surround Panel Installation 29 Optional Blower Accessory Information 30 Optional Decorative Glass Placement 31 Operating Instructions 32 Standing Pil...

Page 3: ...he glass front or any part removed for servicing the appliance must be replaced prior to operating the appliance Work should be done by a qualified service person Keep burner and control compartment c...

Page 4: ...erform service or make adjustments in an area where the conditions are such that you may not detect the odor if there has been a leak of LP Gas Odor fade due to oxidation by rust or adsorption on wall...

Page 5: ...2nd St New York N Y 10036 Any alteration of the original design installed other than as shown in these instructions or use with a type of gas not shown on the rating plate is the responsibility of the...

Page 6: ...ical vent kit DVVK 4FRE Horizontal flex vent kit round cap DVVK 4RE Horizontal round termination wall thick ness up to 11 7 16 DV822 Vinyl siding kit for DVVK 4RE DVVK 4F Horizontal flex vent kit DVVK...

Page 7: ...supply requirements for optional blower Properly framed opening size required for installation of the fireplace DV FIREPLACE DIMENSIONS MODEL A B C D E F G H I J K L M N O DVL25FP 37 1 2 26 14 1 4 10...

Page 8: ...EDGE OF DOOR FRAME 3 MIN 3 MIN 3 MIN TOP VIEW NON COMBUSTIBLE AREA TO SIDES AND BACK OF FIREPLACE Figure 3 3 MIN CLEARANCE ABOVE VENT SYSTEM 1 MIN CLEARANCE FROM FRAMING TO VENT SYSTEM 25 MIN DISTANC...

Page 9: ...ails in Venting Section When you install your Direct Vent Fireplace in D Room divider or E Flat on wall corner positions a minimum of 6 inches clearance must be maintained from the perpendicular wall...

Page 10: ...dures results in pressures in excess of 1 2 psig 14 w c 3 5 kPa on the fireplace gas valve it will result in a hazardous condition Checking Manifold Pressures Both Propane and Natural gas valves have...

Page 11: ...en a metal or wood panel is placed beneath the appliance 4 Install the side Framing brackets 1 per side using the pi lot holes provided behind the side flanges on the fireplace outer wrap Two setback...

Page 12: ...Clearance Note Maintain one inch 1 of clearance around vertical vent pipe See Figure 11 For horizontal vent maintain a minimum 1 clearance to the bottom and sides of the vent and 3 clearance to combus...

Page 13: ...16 C 14 1 16 15 5 16 D 53 1 2 60 3 8 Optional Blower Accessory The Loft fireplace may be equipped with an optional FBB8 blower accessory See page 38 The blower accessory may be installed at any time...

Page 14: ...cal Building Codes before beginning the installation WARNING THIS GAS FIREPLACE AND VENT ASSEMBLY MUST BE VENTED DIRECTLY TO THE OUTSIDEAND MUST NEVER BE ATTACHED TO A CHIMNEY SERVING A SEPARATE SOLID...

Page 15: ...ing out at joints or seams Condensate can cause corrosion of caps pipe and fittings It may be caused by having excessive lateral runs or having exterior portions of the system exposed to cold weather...

Page 16: ...does not apply if the 45 degree elbows are installed on the vertical part of the vent system Reduce 3 for every 90 elbow Example According to the chart the maximum horizontal vent length is 20 and if...

Page 17: ...evel a snorkel kit is recommended It allows installation depth down to 7 178 mm below grade level The 7 178 mm is measured from the center of the horizontal vent pipe as it penetrates through the wall...

Page 18: ...nued Positioning the Fireplace Determine the exact position of the appliance so the direct vent termination will be centered if possible between two 2 studs This will avoid any extra framing All vent...

Page 19: ...re 25 Figure 26 EXAMPLES TOP VENT RUN 24 MINIMUM CLEARANCE TO COMBUSTIBLES 24 H2 H1 V1 Example H2 2ft 2 90 90 6ft H 8ft V 15ft 3 ft 914 mm H3 1 ft 305mm 4 ft 122mm 6 ft 1 83M 21 ft 6 4M 10 ft 3M V 21f...

Page 20: ...lace in such a way that minimizes the number of offsets and horizontal vent length Since it is very important that the venting system maintain its balance between the combustion air intake and the flu...

Page 21: ...center line of the regulator I clearance to service regulator vent outlet 6 feet 1 89 m minimum J clearance to non mechanical air supply inlet to building or the combustion air inlet to any other appl...

Page 22: ...f each starting outer pipe line up rotate pipe section clockwise 90 approximately 3 inches The vent pipe is now locked together Continue adding components per the pre planned vent system configuration...

Page 23: ...ANCE TO COMBUSTIBLES FROM VERTICAL VENT 12 MIN 304 8mm CLEARANCE TO COMBUSTIBLES 3 MIN 76 2mm CLEARANCE TO COMBUSTIBLES Figure 30 Installing Firestops Firestops are required for safety whenever the ve...

Page 24: ...r any obstructions such as wiring or plumbing runs Reposition the appliance and vent system if necessary to accommodate ceiling joists and or obstructions Cut a 10 inch x 10 inch hole through the ceil...

Page 25: ...tside edge too so as to make a seal to the exterior wall NOTE Wood screws can and should be replaced with appropriate fasteners for use on stucco brick concrete or other types of siding CAUTION Ifexte...

Page 26: ...s holes These components should immediately be replaced 2 Remove the cap and shine a flashlight down the vent Remove any bird nests or other foreign material 3 Check for evidence of excessive condensa...

Page 27: ...daptoronfireplace Replace the horizontal and vertical pipe lengths elbows and horizontal or vertical termination kit All vent system components lock into place by sliding the concentric pipe section w...

Page 28: ...f switch located on the front of the control module tray 3 Run the low voltage alternate switch wires over to the right or left surround panel Then secure the wires with wire clips provided See Figure...

Page 29: ...TO SIDE FLANGES ON INSERT BACK SIDE NOTE INSTALL SURROUND ASSEMBLY SO THAT THE REAR FLANGE OF THE TOP PANEL SETS OVER THE TOP EDGE OF THE TOP SUPPORT BRACKET CENTER SURROUND LEFT TO RIGHT THEN SWING...

Page 30: ...ollows From a cold start the temperature activated fan control switch will normally take 5 10 minutes to heat up and energize the blower Once the blower is energized adjust the blower speed control as...

Page 31: ...only be performed after the DVL Fireplace has been fully installed secured and tested for leaks If operating the burner with a Remote Control make sure all batteries are installed and that the burner...

Page 32: ...our pilot flame to operate an additional one 1 to two 2 minutes before you turn the gas control knob from the PILOT position to the ON position This time period allows the millivolts electrical curren...

Page 33: ...ed setting THERMOCUPLE ELECTRODE THERMOPILE PILOT FOR YOUR SAFETY READ BEFORE LIGHTING Warning If you do not follow these instructions exactly a fire or explosion may result causing property damage pe...

Page 34: ...VE WILL BE DESTROYED WARNING LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROL WIRING ERRORS CAN CAUSE IM PROPER AND DANGEROUS OPERATION VERIFY PROPER OPERATION AFTER SERVICING For Standin...

Page 35: ...he pilot flame Be sure the wire connections from the thermopile at the gas valve terminals are tight and the thermopile is fully inserted into the pilot bracket Check the thermopile with a millivolt m...

Page 36: ...ded that the pilot remain in the CPI standing pilot mode to reduce cold start issues and or conserve battery backup power during a power outage 3 The gas valve has inlet and outlet pressure taps as sh...

Page 37: ...ION Do not operate the appliance with panel s removed cracked or broken Replacement of the panel s should be done by a licensed or qualified service person WARNING Improper installation adjustment alt...

Page 38: ...ormation Lighting Instructions FOR YOUR SAFETY READ BEFORE LIGHTING Warning If you do not follow these instructions exactly a fire or explosion may result causing property damage personal injury or lo...

Page 39: ...uctions on page 38 and Wiring Diagram on page 37 Troubleshooting Before proceeding with the procedures in the following trouble shooting table verify that the power supply AC DC adapter is present and...

Page 40: ...e wire harness 4 Replace the DFC board 1 Verify the electrical connections integrity and make sure they are in accordance with the relevant system wiring diagram If necessary replace the wire harness...

Page 41: ...ase and verify voltage at ignition between the EV1 terminal and the ground connection on the valve body 5 1 If the voltage is greater than 0 then Replace Valve 5 2 Or Replace DFC 6 Check the pressure...

Page 42: ...manufacturing processes fingerprints along with excess sealing materials may be present and should be removed When cleaning do not use abrasives on the porcelain liners or the glass door assembly Clea...

Page 43: ...el Number Float DF 25 33 S BL HP SS Black Hammered Pewter Stainless Steal Must also use 4 sided surround 4 Sided Surround DS 25 33 66BL Black Manhattan DF 25 33 N BL HP Black Hammered Pewter Must also...

Page 44: ...5 17155 17155 FLUE OUTLET ASSEMBLY 5 M163 M163 M163 M163 GASKET FLUE CONNECTOR 6 16223 27718 16223 27718 SPRING RETAINER ASSEMBLY 7 30577 30577 30577 30577 NAILING FLANGE 8 R10854 R10854 R10854 R10854...

Page 45: ...45mm P182 55 P208 1 45mm ORIFICE LP GAS 26 R7624 R7624 R7624 R7624 AIR SHUTTER 27 R10732 R10879 R10732 R10879 TUBE BURNER 28 11269 11269 11269 11269 GAS LINE BRACKET 29 28067 28067 28067 28067 BURNER...

Page 46: ...anty parts All parts listed in the Parts List have a Part Number When ordering parts first obtain the Model Number and Serial Number from the name plate on your equipment Then determine the Part Numbe...

Page 47: ...iance must be installed by a qualified installer and operated in accordance with the instructions furnished with the ap pliance A bill of sale cancelled check or payment record should be kept to verif...

Page 48: ...s Empire Comfort Systems Inc 918 Freeburg Ave Belleville IL 62220 If you have a general question about our products please e mail us at info empirecomfort com If you have a service or repair question...

Reviews: