background image

32192-1-0314

Page 6

Pressure Testing of the Gas Supply System

1.  To check the inlet pressure to the gas valve, a 1/8” (3mm) N.P.T. 

plugged tapping, accessible for test gauge connection, must 

be placed immediately upstream of the gas supply connection 

to the appliance.

2.  The appliance and is individual shutoff valve must be discon-

nected from the gas supply piping system during any pressure 

testing of that system at test pressures in excess of 1/2 psig 

(3.5 kPa).

3. The appliance must be isolated from the gas supply piping 

system by closing its individual manual shutoff valve during 

any pressure testing of the gas supply piping system at test 

pressures equal to or less than 1/2 psig (3.5 kPa).

Attention!

 If one of the above procedures results in pressures in 

excess of 1/2 psig (14” w.c.) (3.5 kPa) on the appliance gas valve, 

it will result in a hazardous condition.

Checking Manifold Pressure

Both  Propane  and  Natural  gas  valves  have  a  built-in  pressure 

regulator in the gas valve. Natural gas models will have a manifold 

pressure of approximately 4.0” w.c. (.996kPa) at the valve outlet with 

the inlet pressure to the valve from a minimum of 5.0” w.c. (1.24kPa). 

Propane gas models will have a manifold pressure approximately 

10.0” w.c. (2.49kPa) at the valve outlet with the inlet pressure to the 

valve from a minimum of 11.0” w.c. (2.739kPa) for the purpose of 

input adjustment to a maximum of 13.0” w.c. (3.237kPa).
A  1/8”  (3mm)  N.P.T.  plugged  tapping,  accessible  for  test  gauge 

connection, is located on the outlet side of the gas control.

The built-in regulator comes on at approximately 1/4th pressure 

and full on in 10 seconds.

TOP VIEW OF VALVE

PRESSURE REGULATOR

OUTLET PRESSURE TAP

GAS OUTLET

PILOT GAS OUTLET

PILOT ADJUSTMENT

SCREW BENEATH

COVER SCREW

MANUAL GAS COCK KNOB

RED RESET BUTTON

INLET PRESSURE TAP

GAS INLET

WRENCH BOSS

VENT

Figure 5

High Altitudes

For altitudes/elevations above 2,000 feet (610m), input ratings should 

be reduced at the rate of 4 percent for each 1,000 feet (305m) above 

sea level. Canadian High Altitudes for locations having an elevation 

above mean sea level between 2,000 feet (610m) and 4,500 feet 

(1370m), the manifold pressure is to be decreased from 4.0” w.c. 

(.996kPa) to 3.2” (.797kPa) w.c. for Natural Gas and from 10.0” w.c. 

(2.49kPa) to 8.0” w.c. (1.992kPa) for Propane Gas.

Piezo Pilot Ignitor Instructions

Depressing the red button completely causes a spark to occur at 

the pilot. This is a substitute for a match which requires opening 

the pilot hole cover.

To light the pilot, it is important that the electrode be 1/8” (3mm) 

from  the  thermocouple.  The  spark  must  occur  at  the  point  the 

burner flame hits the thermocouple. The end of the electrode will 

be red hot with the pilot on.
On a new installation with air in the gas line, it is suggested that a 

match be used. The match will light the pilot faster than the piezo 

under this condition.

Attention!

 The 7/8” (22mm) strain relief bushing is located within 

the same yellow envelope as the Installation Instructions and 

Owner’s Manual.

Attaching Furnace to Wall

When attaching furnace to the wall remove that portion of baseboard 

and molding on the wall which is behind the furnace. Attach furnace 

to wall, at the outer casing top, with (2) toggle bolts provided and 

to floor, at the outer casing bottom, with (2) #10 x 1 1/2” (38mm) 

screws provided.

Attention!

 The screw holes on the outer casing bottom are off-set 

above the floor approximately 3/8” (9.5mm). Do not over-tighten 

screws and distort the off-set on the outer casing bottom. Distortion 

of the outer casing bottom will not allow the lower front panel to be 

attached to the furnace.

Gas Supply

Check all local codes for requirements, especially for the size and 

type of gas supply line required. On Natural gas lines less than 15’ 

(4.5m) long, us (1/2” (13mm) pipe; on longer runs, use 3/4” (19mm) 

iron pipe or equal. On LP gas lines please consult LP gas supplier.

Installing a New Main Gas Cock

Each appliance should have its own manual gas cock.
A manual main gas cock should be located in the vicinity of the unit. 

Where none exists, or where its size or location is not adequate, 

contact your local authorized installer for installation or relocation.
Compounds used on threaded joints of gas piping shall be resistant 

to the action of liquefied petroleum gases. The gas lines must be 

checked for leaks by the installer. This should be done with a soap 

solution watching for bubbles on all exposed connections, and if 

unexposed, a pressure test should be made.

Never use an exposed flame to check for leaks. Appliance must 

be disconnected from piping at inlet of control valve and pipe 

capped or plugged for pressure test. Never pressure test with 

appliance connected; control valve will sustain damage!

A gas valve and ground joint union should be installed in the gas 

line upstream of the gas control to aid in servicing. It is required by 

the National Fuel Gas Code that a drip line be installed near the gas 

inlet. This should consist of a vertical length of pipe tee connected 

into the gas line that is capped on the bottom in which condensation 

and foreign particles may collect.

GAS SUPPLY PIPING

1/8(3mm)NPT PLUGGED HOLE

FOR TEST GAGE

GROUND JOINT UNION

3”(76mm)MINIMUM

MANUAL SHUT-OFF VALVE

GAS SUPPLY
INLET

1/8 (3mm) NPT PLUGGED HOLE

FOR TEST GAGE

GAS

VALVE

Figure 4

Method of Installing a Tee Fitting Sediment Trap

The use of the following gas connectors is recommended:

–ANS Z21.24 Appliance Connectors of Corrugate Metal Tubing 

and Fittings

–ANS Z21.45 Assembled Flexible Appliance Connectors of Other 

Than All-Metal Constructions

The above connectors may be used if acceptable by the authority 

having jurisdiction.

Summary of Contents for FAW-55-1SPP

Page 1: ...these instructions are not followed exactly a fire or explosion may result causing property damage personal injury or loss of life Do not store or use gasoline or other flammable vapors and liquids in...

Page 2: ...burner ignition devices are located not less than 18 457mm above the floor Such equipment shall be located or protected so it is not subject to physical damage by a moving vehicle Specifications Model...

Page 3: ...gas can adsorb or absorb onto or into walls masonry and other materials and fabrics in a room That will take some of the odorant out of the gas reducing its odor intensity LP Gas may stratify in a clo...

Page 4: ...onnected to a chimney flue serving a separate solid fuel burning appliance 3 Uninsulated Single Wall Metal Pipe shall not be used outdoors in cold climates for venting gas utilization equipment 4 Atte...

Page 5: ...connec tion Also refer to Figure 2 for positioning the furnace on wall and for locating gas line connection Locating Gas Supply The gas line can enter the furnace either though the floor or wall The...

Page 6: ...air in the gas line it is suggested that a match be used The match will light the pilot faster than the piezo under this condition Attention The 7 8 22mm strain relief bushing is located within the s...

Page 7: ...will be blue extending past the thermocouple The flame will surround the thermocouple just be low the tip Natural gas pilots require adjusting when the inlet gas pressure is above 5 w c 1 245kPa Remov...

Page 8: ...Fan Motor The upper front panel the shroud sur rounding the fan blade and fan blade must be removed See oiling the Motor paragraph on page 7 Spark Igniter Does Not Light Pilot With air in the gas lin...

Page 9: ...knob clockwise to OFF 6 Wait ten 10 minutes to clear out any gas Then smell for gas including near the floor If you smell gas STOP Follow B in the safety information above If you don t smell gas go to...

Page 10: ...808 PILOT TUBING 25 DV562 LOWER FRONT PANEL 26 DV824 FRONT BURNER 27 P8842 MAIN BURNER ORIFICE NATURAL GAS TWO REQUIRED 27 P8853 MAIN BURNER ORIFICE LP GAS TWO REQUIRED 28 DV687 MANIFOLD AND PLATE ASS...

Page 11: ...32192 1 0314 Page 11...

Page 12: ...oval elbows 3 Single story type B 1 gas vents require a baseplate and one pair of ceiling plate spacers 4 Multi story type B 1 gas vents require a baseplate one pair of ceiling plate spacers at the fi...

Page 13: ...ranty parts All parts listed in the Parts List have a Part Number When ordering parts first obtain the Model Number and Serial Number from the name plate on your equipment Then determine the Part Numb...

Page 14: ...32192 1 0314 Page 14 APPLIANCE SERVICE HISTORY Date Dealer Name Service Technician Name Service Performed Notes...

Page 15: ...A bill of sale cancelled check or payment record should be kept to verify purchase date and establish warranty period Ready access to the appliance for service What Is Not Covered Damages that might r...

Page 16: ...s Empire Comfort Systems Inc 918 Freeburg Ave Belleville IL 62220 If you have a general question about our products please e mail us at info empirecomfort com If you have a service or repair question...

Page 17: ...tout autre appareil QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ Ne pas tenter d allumer d appareil Ne touchez a aucun interrupteur Ne pas vous servir des t l phones se trouvant dans le b ti ment o vous...

Page 18: ...syst me de com mande et les commandes de gaz qui ont t en contact avec l eau Ce radiateur ne doit pas tre branch une chemin e servant un autre appareil br lant un combustible solide A cause des hautes...

Page 19: ...que les pompiers vous assurent de la s ret de ces endroits avant d y aller Utiliser le t l phone de votre voisin et appeler les pompiers et une personne entra n e avec le propane Ne pas ouvrir les so...

Page 20: ...tall s dans un endroit o la facilit delaventilationpermetunecombustiondegazsatisfaisanteetun chappe ment convenable sous des conditions normales Dans les b timents de construction conventionnelle de b...

Page 21: ...tant est chang de place Un guide est fourni dans l emballage du radiateur pour vous aider localiser la connexion pour la ligne de gaz Aussi r f rer la Figure 2 pour positionner le radiateur sur le mur...

Page 22: ...de 3 914mm du compartiment des contr les au bas du radiateur 2 Enlever l entr e d fon able de 7 8 22mm du c t du panneau ap propri 3 Introduire le bouchon de nylon de l assemblage de la fiche de 3 914...

Page 23: ...que le radiateur ait fonctionn il se peut que les ouvertures du br leur soient bloqu es par des mati res trang res venant de l air de combustion Donc un nettoyage du br leur peut tre exig pour obteni...

Page 24: ...ation lequel doit tre install et entretenu correctement ou lorsque vous tripotez avec le syst me de fermeture de s ret de l vent peut causer un empoissonnement au monoxide de carbone CO et possiblemen...

Page 25: ...tion La veilleuse est suppos e rester allumer Si elle s teint recommencer les tapes 5 jusqu 10 Si le bouton ne revient pas sa position lorsque vous le rel chez arr ter et appeler imm diatement un tech...

Page 26: ...intervalles jusqu ce qu elle s allume Si l lectrode ne Produit Pas d tincelle 1 V rifier les connexions des fils lectriques 2 V rifier la distance du br leur de la veilleuse au bout de l lectrode Doi...

Page 27: ...s ret de l vent 16 8720130 Manchon 17 11765 Assemblage du compartiment d interrupteur 18 DV 832 Couvercle du compartiment d interrupteur 19 912073 Contr le de tol rance 20 R 1941 Contr le du ventilat...

Page 28: ...12428 7 0314 Page 12 Empire Comfort Systems Inc Nine Eighteen Freeburg Ave Belleville Illinois 62222 0529...

Page 29: ...de base et une paire d entretoises pour la plaque du plafond 4 Les vents gaz de type B 1 pour plus d un tage exige une plaque de base une paire d entretoises pour la plaque du pla fond au plafond du...

Page 30: ...mages pouvant r sulter de l emploi de l emploi abusif ou d une installation incorrecte de cet appareil Frais de d placement de diagnostic et de transport des pi ces sous garantie vers et depuis l usin...

Reviews: