Wiring

The appliance, when installed, must be electrically grounded in 

accordance with local codes or, in the absence of local codes with 

the 

National Electrical Code, ANSI/NFPA70 or Canadian Electrical 

Code CSA C22.1

, if an external electrical source is utilized. 

This 

appliance is equipped with a three-prong (grounding) plug for 

your protection against shock hazard and should be plugged 

directly into a properly grounded three-prong receptacle. Do 

not cut or remove the grounding prong from this plug.

 For an 

ungrounded receptacle, an adapter, which has two prongs and a 

wire for grounding, can be purchased, plugged into the unground-

ed receptacle and its wire connected to the receptacle mounting 

screw. With this wire completing the ground, the appliance cord 

plug can be plugged into the adapter and be electrically grounded. 

A 7/8” (22mm) hole is provided in the junction box for use with a 

conduit connector if local codes require this type of protection.

Optional Thermostat Installation

The thermostat should be installed in the same room as the fur-

nace 4’ (1.2m) to 5’ (1.5m) above the floor and away from another 

heat source (cooking stove, hot water heater, etc.) including walls 

and doorways with a heat source in an adjoining room. 

Do Not 

Install Thermostat on Outside Wall.

To Conserve Gas: Turn off pilot when heater is not in use.

Insulated Vent Enclosure

Vented wall furnaces installed in buildings with flat roofs can have 

poor venting. The cold vent pipe will have a delay in proper vent-

ing and cause the wall furnace to shut “OFF” by the vent safety 

switch. To prevent delayed venting as well as condensation of flue 

products an insulated vent enclosure is recommended.
Use type B vent pipe and maintain at least one inch (25mm) clear-

ance to combustibles.
Use metal thimble to protect vent pipe as it passes through com-

bustibles.

10’(3m) OR

LESS

3’ (.9m) MIN

2’ (.6m) MIN

Figure 8

Proper Pilot Flame

The correct pilot flame (Figure 6) will be blue, extending past the 

thermocouple. The flame will surround the thermocouple just be

-

low the tip.

Natural gas pilots require adjusting when the inlet gas pressure 

is above 5” w.c. (1.245kPa). Remove the pilot cover screw on the 

control valve (Figure 5), and turn the adjustment screw clockwise 

to reduce flame. Replace pilot cover screw to eliminate gas leak

-

age.

LP gas (propane) will not require adjustment.
After use, cleaning may be required for the proper flame.

PROPER FLAME ADJUSTMENT

DO MAKE A PERIODIC VISUAL
CHECK OF PILOT & BURNERS

Figure 6

Proper Main Burner Flame

The  correct  flame  will  be  a  short  blue  inner  flame  with  a  much 

larger light blue outer flame. The main burner (Figure 7) shows 

the approximate height of each part of the flame for each gas. The 

burner does not have a primary air adjustment. The flame will be 

correct  if  the  factory-set  pressure  and  orifice  opening  are  used. 

After the furnace has been operating, the burner ports may be 

blocked by foreign matter carried in by combustion air. Therefore, 

cleaning of the burner may be needed for proper flame.

To clean burner port disconnect the gas supply to the valve, and 

remove the eight screws fastening the burner door. After remov-

ing the burner door from the combustion chamber, remove rear 

burner, pilot burner and front burner. With front and rear burners 

removed from furnace, force water into the ribbon ports and dry 

with air pressure.

4” (102mm)

6” (152mm)

NAT

AND

LP

1 1/2” (38mm)

1/4” (6mm)

NAT

LP

Figure 7

Replacing Fan and Oiling the Motor

The fan motor should be cleaned and oiled once each heating 

season. To reach the motor, withdraw the metal shroud surround-

ing the fan blade by removing the screws on each side. Oil holes 

are located on the top at each end of the motor. Use a few drops 

of #10 motor oil. To clean the motor, blow air through its ventilation 

openings with a vacuum cleaner or low pressure air source.

If fan motor is replaced, the silicone rubber gaskets, see Page 10, 

Index No. 5, Part 712059, should also be replaced. The gaskets 

must be stretched to fit the motor bolts into the gasket holes and 

then the motor and gaskets installed on the motor mounting bars.

Summary of Contents for FAW-55-1SPP

Page 1: ...these instructions are not followed exactly a fire or explosion may result causing property damage personal injury or loss of life Do not store or use gasoline or other flammable vapors and liquids in...

Page 2: ...burner ignition devices are located not less than 18 457mm above the floor Such equipment shall be located or protected so it is not subject to physical damage by a moving vehicle Specifications Model...

Page 3: ...gas can adsorb or absorb onto or into walls masonry and other materials and fabrics in a room That will take some of the odorant out of the gas reducing its odor intensity LP Gas may stratify in a clo...

Page 4: ...onnected to a chimney flue serving a separate solid fuel burning appliance 3 Uninsulated Single Wall Metal Pipe shall not be used outdoors in cold climates for venting gas utilization equipment 4 Atte...

Page 5: ...connec tion Also refer to Figure 2 for positioning the furnace on wall and for locating gas line connection Locating Gas Supply The gas line can enter the furnace either though the floor or wall The...

Page 6: ...air in the gas line it is suggested that a match be used The match will light the pilot faster than the piezo under this condition Attention The 7 8 22mm strain relief bushing is located within the s...

Page 7: ...will be blue extending past the thermocouple The flame will surround the thermocouple just be low the tip Natural gas pilots require adjusting when the inlet gas pressure is above 5 w c 1 245kPa Remov...

Page 8: ...Fan Motor The upper front panel the shroud sur rounding the fan blade and fan blade must be removed See oiling the Motor paragraph on page 7 Spark Igniter Does Not Light Pilot With air in the gas lin...

Page 9: ...knob clockwise to OFF 6 Wait ten 10 minutes to clear out any gas Then smell for gas including near the floor If you smell gas STOP Follow B in the safety information above If you don t smell gas go to...

Page 10: ...808 PILOT TUBING 25 DV562 LOWER FRONT PANEL 26 DV824 FRONT BURNER 27 P8842 MAIN BURNER ORIFICE NATURAL GAS TWO REQUIRED 27 P8853 MAIN BURNER ORIFICE LP GAS TWO REQUIRED 28 DV687 MANIFOLD AND PLATE ASS...

Page 11: ...32192 1 0314 Page 11...

Page 12: ...oval elbows 3 Single story type B 1 gas vents require a baseplate and one pair of ceiling plate spacers 4 Multi story type B 1 gas vents require a baseplate one pair of ceiling plate spacers at the fi...

Page 13: ...ranty parts All parts listed in the Parts List have a Part Number When ordering parts first obtain the Model Number and Serial Number from the name plate on your equipment Then determine the Part Numb...

Page 14: ...32192 1 0314 Page 14 APPLIANCE SERVICE HISTORY Date Dealer Name Service Technician Name Service Performed Notes...

Page 15: ...A bill of sale cancelled check or payment record should be kept to verify purchase date and establish warranty period Ready access to the appliance for service What Is Not Covered Damages that might r...

Page 16: ...s Empire Comfort Systems Inc 918 Freeburg Ave Belleville IL 62220 If you have a general question about our products please e mail us at info empirecomfort com If you have a service or repair question...

Page 17: ...tout autre appareil QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ Ne pas tenter d allumer d appareil Ne touchez a aucun interrupteur Ne pas vous servir des t l phones se trouvant dans le b ti ment o vous...

Page 18: ...syst me de com mande et les commandes de gaz qui ont t en contact avec l eau Ce radiateur ne doit pas tre branch une chemin e servant un autre appareil br lant un combustible solide A cause des hautes...

Page 19: ...que les pompiers vous assurent de la s ret de ces endroits avant d y aller Utiliser le t l phone de votre voisin et appeler les pompiers et une personne entra n e avec le propane Ne pas ouvrir les so...

Page 20: ...tall s dans un endroit o la facilit delaventilationpermetunecombustiondegazsatisfaisanteetun chappe ment convenable sous des conditions normales Dans les b timents de construction conventionnelle de b...

Page 21: ...tant est chang de place Un guide est fourni dans l emballage du radiateur pour vous aider localiser la connexion pour la ligne de gaz Aussi r f rer la Figure 2 pour positionner le radiateur sur le mur...

Page 22: ...de 3 914mm du compartiment des contr les au bas du radiateur 2 Enlever l entr e d fon able de 7 8 22mm du c t du panneau ap propri 3 Introduire le bouchon de nylon de l assemblage de la fiche de 3 914...

Page 23: ...que le radiateur ait fonctionn il se peut que les ouvertures du br leur soient bloqu es par des mati res trang res venant de l air de combustion Donc un nettoyage du br leur peut tre exig pour obteni...

Page 24: ...ation lequel doit tre install et entretenu correctement ou lorsque vous tripotez avec le syst me de fermeture de s ret de l vent peut causer un empoissonnement au monoxide de carbone CO et possiblemen...

Page 25: ...tion La veilleuse est suppos e rester allumer Si elle s teint recommencer les tapes 5 jusqu 10 Si le bouton ne revient pas sa position lorsque vous le rel chez arr ter et appeler imm diatement un tech...

Page 26: ...intervalles jusqu ce qu elle s allume Si l lectrode ne Produit Pas d tincelle 1 V rifier les connexions des fils lectriques 2 V rifier la distance du br leur de la veilleuse au bout de l lectrode Doi...

Page 27: ...s ret de l vent 16 8720130 Manchon 17 11765 Assemblage du compartiment d interrupteur 18 DV 832 Couvercle du compartiment d interrupteur 19 912073 Contr le de tol rance 20 R 1941 Contr le du ventilat...

Page 28: ...12428 7 0314 Page 12 Empire Comfort Systems Inc Nine Eighteen Freeburg Ave Belleville Illinois 62222 0529...

Page 29: ...de base et une paire d entretoises pour la plaque du plafond 4 Les vents gaz de type B 1 pour plus d un tage exige une plaque de base une paire d entretoises pour la plaque du pla fond au plafond du...

Page 30: ...mages pouvant r sulter de l emploi de l emploi abusif ou d une installation incorrecte de cet appareil Frais de d placement de diagnostic et de transport des pi ces sous garantie vers et depuis l usin...

Reviews: