background image

24117-0-0508

Page 3

The installation must conform with local codes or, in 

the absence of local codes, with the National Fuel Gas 

Code, ANSI Z223.1 (latest edition) and to the National 

electrical Code, ANSI/NFPA70 (latest edition).
NOTE: Installation and repair should be done by a quali-

fied service person. The appliance should be inspected 

before use and at least annually by a qualified service 

person. More frequent cleaning may be required due to 

excessive lint from carpeting, bedding material, etc. It 

is imperative that control compartment, burners and 

circulating air passageways of the appliance be kept 

clean.

Any safety screen or guard removed for servicing an 

appliance must be replaced prior to operating the ap-

pliance. Provide adequate combustion and ventilation 

air.
The flow of combustion and ventilation air MUST NOT 

be obstructed.
Provide adequate clearance around air openings into 

the  combustion  chamber  and  adequate  accessibility 

clearance for servicing and proper operation. NEVER 

obstruct the front opening of the appliance.

This  Empire  Comfort  Systems  Inc.  firebox  and  its 

components have been tested and will operate safely when 

installed in accordance with this installation manual. 

Read all instructions before starting installation, then 

follow these instructions carefully during installation 

to maximize firebox benefit and safety. Report to your 

dealer any parts damaged in shipment.
The  Empire  Comfort  Systems  Inc.  warranty  will  be 

voided by, and Empire Comfort Systems Inc. disclaims 

any responsibility for the following actions:

-  Installation of any damaged firebox.

-  Modification of the firebox or any of the components 

parts thereof.

-  Installation  other  than  as  instructed  by  Empire 

Comfort Systems Inc.

-  Installation and/or use of any component part or 

accessory not approved by Empire Comfort Systems 

Inc.  in  combination  or  assembly  with  a  Empire 

Comfort Systems Inc. firebox, not withstanding any 

independent testing laboratory or other third party 

approval of such component part or accessory.

Any such action may create a possible fire hazard.

Consult your local building codes.
Firebox Screen.

The firebox screen must be in place when the firebox is 

operating.

Instructions to Installer

1.  Installer  must  leave  instruction  manual  with  owner  after 

installation.

2.  Installer must have owner fill out and mail warranty card 

supplied with firebox.

3.  Installer should show owner how to start and operate log set 

that is installed into firebox.

Important

All  correspondence  should  refer  to  complete  Model  Number, 

Serial Number.
Notice: During initial firing of this firebox with a log set installed, its 

paint will bake out, and smoke will occur. To prevent triggering of 

smoke alarms, ventilate the room in which the unit is installed.

Qualified Installing Agency

Installation  and  replacement  of  gas  piping,  gas  utilization 

equipment or accessories and repair and servicing of equipment 

shall be performed only by a qualified agency. The term "qualified 

agency"  means  any  individual,  firm,  corporation  or  company 

which either in person or through a representative is engaged in 

and is responsible for (a) the installation or replacement of gas 

piping or (b) the connection, installation, repair or servicing of 

equipment, who is experienced in such work, familiar with all 

precautions required and has complied with all the requirements 

of the authority having jurisdiction.

State  of  Massachusetts:

  The  installation  must  be  made 

by  a  licensed  plumber  or  gas  fitter  in  the  Commonwealth 

of  Massachusetts.  The  state  of  Massachusetts  requires  that 

a  flexible  appliance  connector  cannot  exceed  three  feet  in 

length.
Sellers of unvented propane or natural gas-fired supplemental 

room heaters shall provide to each purchaser a copy of 527 

CMR 30 upon sale of the unit.
In the State of Massachusetts, unvented propane and natural 

gas-fired space heaters shall be prohibited in bedrooms and 

bathrooms.

The installation must conform with local codes or, in the absence 

of local codes, with the National Fuel Gas Code, ANSI Z223.1/

NFPA 54.*

*Available from the American National Standards Institute, Inc., 11 West 

42nd St., New York, N.Y. 10036.

IMPORTANT SAFETY INFORMATION

INTRODUCTION

Summary of Contents for VFP36PB2EF-1

Page 1: ...y or the gas supplier Carefully review the instructions supplied with the decora tive type unvented room heater for the minimum replace size requirement DO NOT INSTALL A VENT FREE LOG SET IN THIS FIRE...

Page 2: ...ection 9 Wiring Instructions for Installing a Dual Switch Receptacle 10 LK2 Accent Light Accessory 10 Optional Single Speed Blower Installation Instructions 11 13 Maintenance 13 Parts List 14 See Thro...

Page 3: ...val of such component part or accessory Any such action may create a possible re hazard Consult your local building codes Firebox Screen The rebox screen must be in place when the rebox is operating I...

Page 4: ...top standoff screws on the front edge of the top outer wrap See Figures 2a and 2b CLEARANCES FIREBOX STAND OFF COMBUSTIBLE FINISHED WALL OR MANTEL 2 X 4 HEADER TOP OUTER WRAP FINISH WITH TRIM KIT OR N...

Page 5: ...ALLOWED 22 8 20 6 18 5 16 3 14 2 24 0 FIREBOX FACE EXTENDED HOOD VB4H SERIES NOT AVAILABLE ON PENINSULA OPEN END 3 8 COMBUSTIBLE CLEARANCE REQUIRED FROM TOP EDGE OF FIREBOX CLEARANCES Ceiling Clearanc...

Page 6: ...dealer for assistance with this planning Planning Your Installation Accessory kits such as the FBB5 Blower kit Trim kits Mantles plus other Decorative Frame Hood and Door accessory kits may be install...

Page 7: ...D 25 1 2 25 1 2 25 1 2 25 1 2 E 36 36 36 36 F 34 1 4 35 1 4 34 1 4 35 1 4 G 29 1 8 29 1 8 29 1 8 29 1 8 H 41 1 8 41 1 8 41 1 8 41 1 8 I 1 1 4 1 1 4 1 1 4 1 1 4 J 6 1 8 6 1 8 6 1 8 6 1 8 K 8 1 2 8 1 2...

Page 8: ...rposes the hoods are located behind the upper louver s or inside the rebox on ush face units If brass stainless steel or hammered pewter hoods are desired they can be purchased as an option Attachment...

Page 9: ...w c This is in addition to the regulator tted to the log set WARNING CONNECTION DIRECTLY TO AN UNREGULATED L P TANK CAN CAUSE EXPLOSION Install only a ANSI Z21 11 2 vent free log set into this rebox...

Page 10: ...3 wire conductor with ground is recommended however 2 two wire conductors with grounds may be used in place of a 3 wire conductor with a ground if the black wires from the Accent Light and blower acc...

Page 11: ...If installed turn OFF gas supply to rebox gas log 2 If applicable turn OFF electric supply to rebox CAUTION ALL WIRING SHOULD BE DONE BY A QUALIFIED ELECTRICIAN AND SHALL BE IN COMPLIANCE WITH ALL LO...

Page 12: ...mbly and retain wires together near the blower motor using the plastic purse clip provided 11 To complete the installation plug the power cord into the junction box receptacle previously installed in...

Page 13: ...ROL SWITCH 1 2 A B 110 VOLT AC JUNCTION BOX WHITE FAN SWITCH BLACK FAN MOTOR ASSEMBLY Figure 18 Figure 19 Keep the control compartment logs and burner area surrounding the logs clean by vacuuming or b...

Page 14: ...8807 18807 18807 18807 LOUVER ASSEMBLY UPPER 13 18808 18808 18808 18808 LOUVER ASSEMBLY LOWER 14 24059 24059 UPPER LOUVER ASSEMBLY 15 24058 24058 LOWER LOUVER ASSEMBLY 16 19990 19990 19990 19990 BLOWE...

Page 15: ...24117 0 0508 Page 15 SEE THROUGH FIREBOX PARTS VIEW 1 2 3 4 5 8 7 8 9 11 12 13 16 17 18 19 20 22 7 24 23 27 23 12 13 9 11 24 20 19 18 27 17 3 4...

Page 16: ...24117 0 0508 Page 16 PENINSULA FIREBOX PARTS VIEW 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 25 26 23 24 27 12 23 24 13 9 11 3 4 20 19 18 17...

Page 17: ...ewter For use with See Through models VFP36SB2E L F ONLY Contact dealer for all available optional frame kits Bottom Trim Strip Available as optional kits in Black Brass Ham mered Pewter and Stainless...

Page 18: ...and nishes Contact dealer for all available mantel options Flush Panel Kits Flush panel kits may be used to replace louvered panels as desired for the See Through and Peninsula rebox models Available...

Page 19: ...8 29 1 8 29 1 8 29 1 8 H 41 1 8 41 1 8 41 1 8 41 1 8 I 1 1 4 1 1 4 1 1 4 1 1 4 J 6 1 8 6 1 8 6 1 8 6 1 8 K 8 1 2 8 1 2 8 1 2 8 1 2 L 6 6 6 6 M 27 5 8 27 5 8 27 5 8 27 5 8 N 36 7 8 36 7 8 36 7 8 36 7...

Page 20: ...D 3 8 COMBUSTIBLE CLEARANCE REQUIRED FROM TOP EDGE OF FIREBOX Combustible material clearance from front of rebox 36 minimum Sidewall Clearances The clearance from the inside of the rebox to perpendicu...

Page 21: ...Dimension when elevating rebox if installing on an elevated base Framing dimension A incudes a three inch clearance for standoffs on rebox Dimension C assumes use of 1 2 wall board ush to both front f...

Page 22: ...24117 0 0508 Page 22 SERVICE NOTES...

Page 23: ...24117 0 0508 Page 23 SERVICE NOTES...

Page 24: ...Page 24 EMPIRE EMPIRE Comfort Systems Empire Comfort Systems Inc 918 Freeburg Ave Belleville IL 62220 PH 618 233 7420 or 800 851 3153 FAX 618 233 7097 or 800 443 8648 info empirecomfort com www empir...

Reviews: