background image

42929-2-0721

Page 2

Empire Comfort Systems Inc. • Belleville, IL

CAUTION

Due to sharp edges and the weight of the assembly, 

please use proper eye protection and gloves to reduce 

the potential for injuries.

TOOLS/SUPPLIES NEEDED FOR HMFA:

•  Phillips Screwdriver

•  Electric Drill

•  Flathead Screwdriver

•  5/16", 3/8" Nut Drivers

•  Metal Snips

•  Utility Knife

•  Flex Vent Kit 

SDGDFA25 

Other miscellaneous tools commonly used for framing & wiring.

HMFA INTRODUCTION

The Forced Air Heat Management system (HMFA) is 

designed to be installed in conjunction with specific Empire 

Comfort Systems Fireplaces, to reduce the amount of heat 

produced  during  operation  of  the  fireplace.  This  system 

includes a variable speed controlled blower that will deliver 

a desired percentage of the heat produced by the fireplace 

to the exterior of the building.

CONTENTS OF HMFA:

1.  Blower w/Base Assembly (1 ea.)

2.  Outer Termination Assembly (1 ea.)

3.  6" Diameter Collar w/Flange (2 ea.)

4.  6" X 6" X 6" “Y” Duct Connector (1 ea.)

5.  6" Diameter Adapter (“Y” to Flex Connection) (1 ea.)

6.  Band Clamp (4 ea.)

7.  Rheostat (Variable Speed Control) w/Knob (1 ea.)

8.  Junction Box w/Cover (1 ea.)

9.  Hardware Pack (1 ea.)

NOTE:

 Flex venting is not included with HMFA kit. Please 

order the SD6DFA25 Flex Vent Kit which includes 25' of Flex 

Vent and (2) Band clamps to complete the system installation.

MAKE-UP AIR REQUIREMENT FOR HMFA

When in operation, the HMFA Forced Air Heat Management 

System will deliver a percentage of heated air from the 

fireplace  to  the  exterior  of  the  building.  Because  a  certain 

amount of air will be removed from the building, it must be 

replaced with fresh make-up air, to prevent negative pressure 

from building up inside the structure.
Some central furnaces include make-up air dampers. If 

a make-up air damper is included with the furnace, check 

the damper for proper function and operation. There are 

variations in central furnace make-up dampers, therefore,  

you must check to see if the existing system is compatible. 

Some systems are designed to operate if a negative pressure 

is detected inside the building. 

Other systems are designed to operate only while the central 

furnace blower is operating, and would therefore require an 

additional make-up air damper system be installed. 
Make-up Air Dampers are available at local HVAC supply 

stores or contractors. The Make-up Air Damper shall be sized 

based on the potential amount of cubic air to be expelled. 

The HMFA system has the potential of expelling 150 CFM.
If installing a Make-up Air Damper, it is recommended that it 

be installed at the opposite end of the building. In addition, 

installation of the damper at a high level of a vaulted ceiling 

will help dilute the incoming cold air with the warmer air 

normally found near the ceiling. 

WARNING

HMFA Blower MUST be mounted on an exterior wall. 

DO NOT transfer heat to an interior space.

HMFA FORCED AIR HEAT MANAGEMENT SYSTEM

Summary of Contents for VFLB36FP30N

Page 1: ...operty damage Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not tou...

Page 2: ...HMFA When in operation the HMFA Forced Air Heat Management System will deliver a percentage of heated air from the fireplace to the exterior of the building Because a certain amount of air will be rem...

Page 3: ...p to the fireplace Placement of the HMFA blower system in relationship to the fireplace is indicated with minimum framed opening dimensions and vent length requirements as shown in Figures 1 and 2 ALL...

Page 4: ...t to control the HMFA should be made Refer to electrical connections on page 21 3 The framed opening for installation of the HMFA is 14 1 2 X 14 1 2 in all applications See Figures 3 and 4 CAUTION Due...

Page 5: ...enting connection to the blower 14 1 2 OFFSET FLANGE TO BE FLUSH WITH INSIDE WALL AND SECURED BACK EDGE OF BLOWER BASE BRACKET TO BE MOUNTED FLUSH TO THE INSIDE WALL VENT CONNECTION RIGHT SIDE Figure...

Page 6: ...the back edge of the side brackets with the back edge of the framed opening See Figures 4 and 9 Secure the Blower Base assembly with the 9 1 long drywall screws provided as shown in Figure 8 14 1 2 1...

Page 7: ...System to reduce the amount of heat produced during operation of the fireplace CONTENTS OF HMFA 36 48 60 72 P 1 Duct Inlet Assembly 1 ea 2 6 Dovetail Connector 1 ea 3 Gusset 4 ea 4 Top Framing Bracke...

Page 8: ...e 12 below Install the framing brackets according to the chosen finishing option 7 Move the top pair of side framing brackets from the fireplace to the sides of the Heat Transfer Kit as shown in Figur...

Page 9: ...ection and gloves to reduce the potential for injuries ALUMINUM TAPE ON SEAMS DUCT CONNECTOR JOINT DRILL 1 8 HOLES ON VFLB OUTER TOP AT THESE LOCATIONS IF HOLES ARE NOT ALREADY PRESENT Figure 11 Seali...

Page 10: ...72 P Heat Transfer Kit installed will use the same rough framing dimensions as are found in the VFLB Installation Manual However if the rough opening depth is less than 13 1 2 an opening must be incor...

Page 11: ...cut to work with the HMFA 36 48 60 72 P Heat Transfer Kit 11 Consult the wall finishing options in the VFLB installation manual and see Figures 14 and 15 below 12 Cut the non combustible board accord...

Page 12: ...42929 2 0721 Page 12 Empire Comfort Systems Inc Belleville IL Figure 15 Non Combustible Board Finishing Option 2 NOTE Proceed to page 20 if HMFATV Television Kit is not being used...

Page 13: ...t Switch 1 ea 10 Wire Harness Fan Control 1 ea 11 Junction Box 1 ea 12 Wire Bushing 5 8 2 ea 13 Clip Wire 2 ea 14 Romex Connector 3 8 1 ea 15 Zip Tie 4 ea WARNING HMFA Blower MUST be mounted on an ext...

Page 14: ...Figure 17 Connecting Limit Switch And Plate Assembly Figure 18 Limit Switch And Plate Assembly Hanging From Wire Harness NOTE When finishing interior wall leave the Limit Switch connected to the Wire...

Page 15: ...tch Wire Harness to the fireplace control system as shown in either Figure 19 or Figure 20 Neatly coil excess Limit Switch Wire length and secure with zip tie in left front corner of fireplace Figure...

Page 16: ...ew included Make sure that the face of the fan switch is fastened firmly against the surface of the Firebox Top For VFLB60 72 drill out the two holes shown in Figure 21 with a 3 16th drill bit Attach...

Page 17: ...Belleville IL ATTACH WIRE CLIP ATTACH WIRE CLIPS Figure 23 Wire Clip Location VFLB60 and VFLB72 Figure 22 Wire Clip Location VFLB36 and VFLB48 20 Attach either one VFLB36 48 or two VFLB60 72 wire cli...

Page 18: ...one end Attach the end of the Wire Harness with two female connectors to the Fan Switch and route the Wire Harness through the wire clips as shown in Figure 24 or 25 exiting through the hole in the ri...

Page 19: ...fort Systems Inc Belleville IL 22 Attach Junction Box to right side Access Plate and connect Fan Switch Wire Harness as shown in Figures 26 and 27 Figure 26 Attach Junction Box To Access Plate Figure...

Page 20: ...Flex Vent Kit See Figures 28 and 29 6 DIA 3 WAY Y CONNECTOR SELF DRILLING SCREWS 3 PLACES BAND CLAMP COLLAR FLANGE COLLAR PARTS FROM HMFA FORCED AIR KIT NOT USED FLEX VENT KIT SD6DFA25 NOT INCLUDED IN...

Page 21: ...tions Figure 30 27 The electrician is responsible for performing all wiring from the blower to the wall mounted rheostat or junction box on right side of fireplace The rheostat must be mounted in a st...

Page 22: ...igure 34 Figure 34 32 Install the cut end of the Air Duct over the Blower outlet See Figure 35 33 Check to see if the flanges of the Air Duct are flush with the bottom inside flange of the Outer Termi...

Page 23: ...lled around the outer edges of the termination This provides for J channel or other siding materials to be installed up to the termination face It is the installer s responsibility to caulk or seal ar...

Page 24: ...1 9 R10856 Spacer Vibration 4 10 42715 Base Blower 1 N S R13145 Wire Harness 2 Feet 1 N S R13221 Diverter Connector 6 X 6 X 6 Y Branch 1 N S R13222 Adapter 6 Inch Flex 1 N S R13223 Clamp 7 Inch Diame...

Page 25: ...42929 2 0721 Page 25 Empire Comfort Systems Inc Belleville IL Figure 39 HMFA 1 Exploded View 5 4 4 3 6 7 8 9 10 2 1...

Page 26: ...x Number Part Number Description Quantity 1 42783 Top Standoff 2 36 48 4 60 72 2 42788 Gusset 4 3 R13208 Connector 6 Dovetail 1 4 N A Duct Assembly 1 N S N A Drywall Screw No 8 X 1 8 N S N A Screw No...

Page 27: ...Nut 4 40 2 1 R1148 Zip Tie 4 2 R1569 Wire Clip 2 3 42862 Limit Switch Plate 1 4 R11243 Cover Plate Plain 1 5 R1536 Wire Bushing 5 8 2 6 R13268 Limit Switch 150 Degree 1 7 R6176 Switch Fan Control 1 8...

Page 28: ...ww empirecomfort com Empire Comfort Systems Inc Belleville IL If you have a general question about our products please e mail us at info empirecomfort com If you have a service or repair question plea...

Reviews: