background image

27525-2-0411

Page 9

3.  Add the BTU/Hr of all fuel burning appliances in the space.

 Vent-free heater    

 BTU/Hr

 Gas water heater  

 BTU/Hr

 Gas furnace 

 

 BTU/Hr

 Vented gas heater 

 BTU/Hr

 Gas fireplace logs 

 BTU/Hr

 Other gas appliances*  +   

 BTU/Hr

 Total 

 

 BTU/Hr

Example:  Vented gas heater  

20,000 

BTU/Hr

  

  Vent-free heater  

18,000 

BTU/Hr

  

  Total 

 

38,000 

BTU/Hr

*Do not include direct-vent gas appliances. Direct vent draws 

combustion air from the outdoors and vents to the outdoors.

4.  Compare the maximum BTU/Hr the space can support with the 

actual amount of BTU/Hr used.

 

 BTU/Hr (maximum the space can support)

 

 BTU/Hr (actual amount of BTU/Hr used)

  Example: 

    25,600 

BTU/Hr (maximum the space can support)

    38,000 

BTU/Hr (actual amount of BTU/Hr used)

 

WARNING

If the area in which the heater may be operated is smaller than that 

defined as an unconfined space or if the building is of unusually 

tight construction, provide adequate combustion and ventilation 

air by one of the methods described in the National Fuel Gas 

Code, ANSI Z223.1/NFPA 54, Air for Combustion and Ventilation, 

or applicable local codes.

The space in the above example is a confined space because the 

actual BTU/Hr used is more than the maximum BTU/HR the space 

can support. You must provide additional fresh air. Your options 

are as follows:

A.  Rework worksheet, adding the space of an adjoining room. If 

the extra space provides an unconfined space, remove door 

to adjoining room or add ventilation grills between rooms. See 

Ventilation Air From Inside Building.

 

B.  Vent room directly to the outdoors. See 

Ventilation Air From 

Outdoors.

C.  Install a lower BTU/Hr heater, if lower BTU/Hr size makes room 

unconfined.

If the actual BTU/Hr used is less than the maximum BTU/Hr the 

space can support, the space is an unconfined space. You will need 

no additional fresh air ventilation.

 

WARNING

You must provide additional ventilation air in a confined 

space.

This heater shall not be installed in a confined space or unusu

-

ally tight construction unless provisions are provided for adequate 

combustion and ventilation air.

A confined space is an area with volume less than 50 cubic feet per 

1,000 Btuh of the combined input rates of all appliances drawing 

combustion air from that space. Small areas such as equipment 

rooms are confined spaces. Furnaces installed in a confined space 

which supply heated air to areas outside the space must draw return 

air from outside the space through tightly sealed return air ducts. A 

confined space must have 2 openings into the space for combus

-

tion air. One opening must be within 12 inches of the ceiling and 

the other must be within 12 inches of the floor. The required sizing 

of these openings is determined by whether inside or outside air is 

used to support combustion, the method by which the air is brought 

to the space (vertical or horizontal duct) and by the total input rate 

of all appliances in the space.

Unusually Tight Construction

The air that leaks around doors and windows may provide enough 

fresh air for combustion and ventilation. However, in buildings of 

unusually tight construction, you must provide additional fresh air.

 

Unusually  tight  construction  is  defined  as  construction 

where:

a.  Walls and ceilings exposed to the outside atmosphere have 

a continuous water vapor retarder with a rating of one perm 

or less with openings gasketed or sealed, and

b.  Weatherstripping has been added on openable windows and 

doors, and

c.  Caulking  or  sealants  are  applied  to  areas  such  as  joints 

around window and door frames, between sole plates and 

floors, between wall-ceiling joints, between wall panels, at 

penetrations for plumbing, electrical, and gas lines, and at 

other openings.

  If your home meets all of the three criteria above, you must provide 

additional fresh air. See 

“Ventilation Air From Outdoors,”

 page 

10.

Determining if You Have a Confined or Unconfined Space

Use this worksheet to determine if you have a confined or unconfined 

space.   

 

Space:

 Includes the room in which you will install heater plus any 

adjoining  rooms  with  doorless  passageways  or  ventilation  grills 

between the rooms.
1. Determine the volume of the space (length x width x height).

  Length x Width x Height = 

 cu. ft. (volume of 

space)

Example: Space size 16 ft. (length) x 10 ft. (width) x 8 ft. (ceiling 

height) = 1,280 cu. ft. (volume of space)

  If additional ventilation to adjoining room is supplied with grills 

or openings, add the volume of these rooms to the total volume 

of the space.

2.  Divide  the  space  volume  by  50  cubic  feet  to  determine  the 

maximum BTU/Hr the space can support.

 

 (volume of space) ÷ 50 cu. ft. = (maximum 

BTU/Hr the space can support)

Example: 1,280 cu. ft. (volume of space) ÷ 50 cu. ft. = 25.6 or 

25,600 (maximum BTU/Hr the space can support)

PROVISIONS FOR ADEQUATE COMBUSTION & VENTILATION AIR

Summary of Contents for VFD26FM20C-2

Page 1: ...page 8 WARNING If not installed operated and main tained in accordance with the manufacturer s instructions this product could expose you to substances in fuel or from fuel combustion which can cause...

Page 2: ...L 16 OPERATION INSTRUCTIONS FLAME APPEARANCE 16 10 000 BTU MILLIVOLT LIGHTING INSTRUCTIONS 17 MILLIVOLT LIGHTING INSTRUCTIONS 18 HYDRAULIC THERMOSTAT LIGHTING INSTRUCTIONS 19 PILOT FLAME CHARACTERISTI...

Page 3: ...all not be installed in a bedroom or bathroom Due to high temperatures the appliance should be located out of traffic and away from furniture and draperies Children and adults should be alerted to the...

Page 4: ...erform service or make adjustments in an area where the conditions are such that you may not detect the odor if there has been a leak of LP Gas Odor fade due to oxidation by rust or adsorption on wall...

Page 5: ...1 000 feet 305m above sea level Contact the manufacturer or your gas company before changing spud orifice size WARNING Failure to keep the primary air opening s of the burner s clean may result in so...

Page 6: ...own in Figure 2 for corner rough opening Be sure to provide gas line for fireplace and electrical power for optional blower assembly 1 Attach two 2 nailing flanges to firebox sides with two 2 10 x 1 2...

Page 7: ...NE OPENING JUNCTION BOX ASSEMBLY GAS LINE OPENING J I K B C G A D E Figure 4 VFD26 Series Dimensions Index Letter Dimension A 30 1 4 768mm B 30 762mm C 13 1 8 333mm D 18 1 8 460mm E 26 660mm G 25 635m...

Page 8: ...at FREC Electric Remote Control FWS 1 Wall Switch TMV Wall Thermostat Millivolt Reed Switch TRW Wireless Remote Wall Thermostat Water vapor is a by product of gas combustion An unvented room heater pr...

Page 9: ...are confined spaces Furnaces installed in a confined space which supply heated air to areas outside the space must draw return air from outside the space through tightly sealed return air ducts A conf...

Page 10: ...air by using ventilation grills or ducts You must provide two permanent openings one within 12 of the ceiling and one with 12 of the floor Connect these items directly to the outdoors or spaces open...

Page 11: ...l Metal Construction The above connectors may be used if acceptable by the authority having jurisdiction The state of Massachusetts requires that a flex ible appliance connector cannot exceed three fe...

Page 12: ...the top of the fireplace opening to the ceiling should not be less than 36 inches Mantel Clearances for Built in Installation Figure 9 Do not attach combustible material to the mantel of your firepla...

Page 13: ...Remove shrink wrap and logs from fireplace 6 Place back base and fireplace in desired location 7 Connect gas line and electrical wiring at this time in accor dance with local codes 8 Place mantel ass...

Page 14: ...ogs per the Log Placement Instructions See Page 15 14 Install hood See Page 22 9 Attach mantel assembly to studs in the wall through the back brace using two 2 3 drywall screws provided 10 Slide front...

Page 15: ...4 This step is optional for VFD26FP3L10 log sets Place front twig 5 onto 1 log and flat area on 3 log The bottom of the front twig is to be placed behind the grate tang that is second from the left At...

Page 16: ...burner as well as the main flame should be visually checked as the log set is installed In normal operation at full rate after 10 to 15 minutes the flame appearance should be sets of yellow flames NOT...

Page 17: ...m louver assembly if applicable 3 Set REMOTE OFF ON switch to OFF 4 Turn off all electric power to the appliance if applicable 5 Push in gas control knob slightly and turn clockwise to OFF NOTE Knob c...

Page 18: ...pplicable 3 Set REMOTE OFF ON switch to OFF 4 Turn off all electric power to the appliance if applicable 5 Push in gas control knob slightly and turn clockwise to OFF NOTE Knob cannot be turned from P...

Page 19: ...ance 1 Set thermostat gas control knob to lowest setting 2 Turn off all electric power to appliance if service is to be performed if applicable Lighting Instructions 7 Turn gas control knob counterclo...

Page 20: ...Troubleshooting page 25 Cleaning and Maintenance Pilot Oxygen Depletion Sensor Pilot When the pilot has a large yellow tip flame clean the Oxygen Depletion Sensor as follows 1 Clean the ODS pilot by...

Page 21: ...is the OFF position PILOT is the PILOT position VFD26F M P 3 Max 20 000 BTU HR Min 14 000 BTU HR VFD26FP3L10 Max 10 000 Min N A VFD26F M P 2 Main Burner Operation The gas control modulates from a min...

Page 22: ...ireplace Attach top frame to fireplace Use two 2 8 x 1 2 Phillips screws for top frame 5 Replace bottom louver 6 Replace top louver 3 PIECE FRAME KIT SIDE TRIM Figure 21 HOOD INSTRUCTIONS 1 Remove upp...

Page 23: ...urner assembly NOTICE Do not let remote control receiver come in contact with burner assembly On circulating vent free firebox install remote control receiver behind bottom louver Refer to remote cont...

Page 24: ...L ELECTRICAL CODE ANSI NFPA 70 LAT EST EDITION A factory installed junction box is located on the lower right side of the fireplace Wiring must be fed to the junction box and attached to the receptacl...

Page 25: ...setting is not correct Replace gas regula tor 7 ODS pilot lights but flame goes out when control knob is released a Control knob not fully pressed in Press in control knob fully b Control knob not pre...

Page 26: ...R10947 WIRE ASSEMBLY VFD26F M P 3LP PART NUMBERS 10 R3623 PILOT ASSEMBLY 11 21590 PILOT BRACKET 14 R9022 BURNER TUBE 16 P182 ORIFICE 19 23493 TUBING ASSEMBLY 21 R3625 VALVE 23 23496 TUBING ASSEMBLY 30...

Page 27: ...e 27 PARTS VIEW 5 PIECE LOG Y ASSEMBL MILLIVOLT VALVE Y ASSEMBL THERMOSTATIC VALVE Y ASSEMBL 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 19 20 20 21 21 22 23 23 24 25 26 27 28 29 29 30 31 18 32 33...

Page 28: ...ireplace The magnets on the bottom of speed control will sufficiently hold the speed control in place 13 Attach fan control bracket to upper right side of firebox with one 10 x 1 2 hex screw provided...

Page 29: ...r Kit 110 VOLT AC JUNCTION BOX WHITE SPEED CONTROL FAN SWITCH GROUND BLACK FAN WHITE BLACK SWITCH BRACKET FBBX Wiring Diagram FBBX BLOWER KIT EXTENSION INSTALLATION INSTRUCTIONS cont FBB4 OPTIONAL VAR...

Page 30: ...e 1 side panel into firebox 5 Align clearance hole on brick panel bracket with screw hole in the left or right interior top of firebox Use two 2 10 x 1 2 screws to attach brick panel bracket to interi...

Page 31: ...reet Hartford CT 06114 Phone 860 722 2433 Toll Free 800 243 9360 Fax 860 293 0479 Toll Free Fax 800 274 2004 Websites www fwwebb com www victormfg com Parts Heater Hearth and Grills MASTER PARTS DISTR...

Page 32: ...s Empire Comfort Systems Inc 918 Freeburg Ave Belleville IL 62220 If you have a general question about our products please e mail us at info empirecomfort com If you have a service or repair question...

Reviews: