Check all local codes for requirements, especially for the size and 

type of gas supply line required.

Recommended Gas pipe Diameter

Pipe Length

Schedule 40 Pipe

Inside Diameter

Tubing, Type L 

Outside Diameter

Nat.

L.P.

Nat.

L.P.

0-10 feet

0-3 meters

1/2”

12.7mm

3/8”

9.5mm

1/2”

12.7mm

3/8”

9.5mm

10-40 feet

4-12 meters

1/2”

12.7mm

1/2”

12.7mm

5/8”

15.9mm

1/2”

12.7mm

40-100 feet

13-30 meters

1/2”

12.7mm

1/2”

12.7mm

3/4”

19mm

1/2”

12.7mm

100-150 feet

31-46 meters

3/4”

19mm

1/2”

12.7mm

7/8”

22.2mm

3/4”

19mm

NOTICE

Never use plastic pipe. Check to confirm whether your 

local codes allow copper tubing or galvanized.

NOTICE

:

 Since some municipalities have additional local codes, it is 

always best to consult your local authority and installation code.

Installing a New Main Gas Cock 

Each appliance should have its own manual gas cock.

A manual main gas cock should be located in the vicinity of the unit. 

Where none exists, or where its size or location is not adequate, 

contact your local authorized installer for installation or relocation.
Compounds used on threaded joints of gas piping shall be resistant 

to the action of liquefied petroleum gases. The gas lines must be 

checked for leaks by the installer. This should be done with a soap 

solution watching for bubbles on all exposed connections, and if 

unexposed, a pressure test should be made. 

never use an exposed flame to check for leaks. Appliance must 

be disconnected from piping at inlet of control valve and pipe 

capped or plugged for pressure test. Never pressure test with 

appliance connected; control valve will sustain damage!

A gas valve and ground joint union should be installed in the gas 

line upstream of the gas control to aid in servicing. It is required by 

the National Fuel Gas Code that a drip line be installed near the gas 

inlet. This should consist of a vertical length of pipe tee connected 

into the gas line that is capped on the bottom in which condensation 

and foreign particles may collect.
The use of the following gas connectors is recommended:

—  ANS Z21.24 Appliance Connectors of Corrugated Metal Tubing 

and Fittings

—  ANS Z21.45 Assembled Flexible Appliance Connectors of Other 

Than All-Metal Construction

The above connectors may be used if acceptable by the authority 

having jurisdiction. The state of Massachusetts requires that a flex

-

ible appliance connector cannot exceed three feet in length.

pressure Testing of the Gas Supply System

1.   To check the inlet pressure to the gas valve, a 1/8" (3mm) N.P.T. 

plugged tapping, accessible for test gauge connection, must 

be placed immediately upstream of the gas supply connection 

to the appliance.

2.  The  appliance  and  its  individual  shutoff  valve  must  be 

disconnected from the gas supply piping system during any 

pressure testing of that system at test pressures in excess of 

1/2 psig (3.5 kPa).

3.   The  appliance  must  be  isolated  from  the  gas  supply  piping 

system by closing its individual manual shutoff valve during 

any pressure testing of the gas supply piping system at test 

pressures equal to or less than 1/2 psig (3.5 kPa).

Figure 7

Attention!

 If one of the above procedures results in pressures in 

excess of 1/2 psig (14" w.c.) (3.5 kPa) on the appliance gas valve, 

it will result in a hazardous condition.

Checking Manifold pressure

3 Series Millivolt Natural gas

 will have a manifold pressure of 

approximately 3.5" w.c. (.871kPa) for maximum input or 1.7" w.c. 

(.423kPa) for minimum input at the pressure regulator outlet with 

the inlet pressure to the pressure regulator from a minimum of 5.0" 

w.c. (1.120kPa) for the purpose of input adjustment to a maximum 

of 10.5" w.c. (2.614kPa). 

2 Series Hydraulic Thermostat Natural gas

 will have a manifold 

pressure  of  approximately  6.0"  w.c.  (1.49kPa)  at  the  pressure 

regulator outlet with the inlet pressure to the pressure regulator 

from  a  minimum  of  7.0"  w.c.  (1.74kPa)  for  the  purpose  of  input 

adjustment to a maximum of 10.5" w.c. (2.615kPa). 

3  Series  Millivolt  propane  gas

  will  have  a  manifold  pressure 

approximately  10.0"w.c.  (2.49kPa)  for  maximum  input  or 

6.3"w.c.  (1.568kPa)  for  minimum  input  at  the  pressure 

regulator outlet with the inlet pressure to the pressure regulator 

from  a  minimum  of  11.0"w.c.  (2.739kPa)  for  the  purpose  of 

input  adjustment  to  a  maximum  of  13.0"w.c.  (3.237kPa).  

2 Series Hydraulic Thermostat

 

propane gas

 will have a manifold 

pressure approximately 10.0"w.c. (2.49kPa) at the pressure regulator 

outlet with the inlet pressure to the pressure regulator from a minimum 

of 11.0"w.c. (2.739kPa) for the purpose of input adjustment to a 

maximum of 13.0"w.c. (3.237kPa). 

GAS SUPPLY

Summary of Contents for VFD26FM20C-2

Page 1: ...page 8 WARNING If not installed operated and main tained in accordance with the manufacturer s instructions this product could expose you to substances in fuel or from fuel combustion which can cause...

Page 2: ...L 16 OPERATION INSTRUCTIONS FLAME APPEARANCE 16 10 000 BTU MILLIVOLT LIGHTING INSTRUCTIONS 17 MILLIVOLT LIGHTING INSTRUCTIONS 18 HYDRAULIC THERMOSTAT LIGHTING INSTRUCTIONS 19 PILOT FLAME CHARACTERISTI...

Page 3: ...all not be installed in a bedroom or bathroom Due to high temperatures the appliance should be located out of traffic and away from furniture and draperies Children and adults should be alerted to the...

Page 4: ...erform service or make adjustments in an area where the conditions are such that you may not detect the odor if there has been a leak of LP Gas Odor fade due to oxidation by rust or adsorption on wall...

Page 5: ...1 000 feet 305m above sea level Contact the manufacturer or your gas company before changing spud orifice size WARNING Failure to keep the primary air opening s of the burner s clean may result in so...

Page 6: ...own in Figure 2 for corner rough opening Be sure to provide gas line for fireplace and electrical power for optional blower assembly 1 Attach two 2 nailing flanges to firebox sides with two 2 10 x 1 2...

Page 7: ...NE OPENING JUNCTION BOX ASSEMBLY GAS LINE OPENING J I K B C G A D E Figure 4 VFD26 Series Dimensions Index Letter Dimension A 30 1 4 768mm B 30 762mm C 13 1 8 333mm D 18 1 8 460mm E 26 660mm G 25 635m...

Page 8: ...at FREC Electric Remote Control FWS 1 Wall Switch TMV Wall Thermostat Millivolt Reed Switch TRW Wireless Remote Wall Thermostat Water vapor is a by product of gas combustion An unvented room heater pr...

Page 9: ...are confined spaces Furnaces installed in a confined space which supply heated air to areas outside the space must draw return air from outside the space through tightly sealed return air ducts A conf...

Page 10: ...air by using ventilation grills or ducts You must provide two permanent openings one within 12 of the ceiling and one with 12 of the floor Connect these items directly to the outdoors or spaces open...

Page 11: ...l Metal Construction The above connectors may be used if acceptable by the authority having jurisdiction The state of Massachusetts requires that a flex ible appliance connector cannot exceed three fe...

Page 12: ...the top of the fireplace opening to the ceiling should not be less than 36 inches Mantel Clearances for Built in Installation Figure 9 Do not attach combustible material to the mantel of your firepla...

Page 13: ...Remove shrink wrap and logs from fireplace 6 Place back base and fireplace in desired location 7 Connect gas line and electrical wiring at this time in accor dance with local codes 8 Place mantel ass...

Page 14: ...ogs per the Log Placement Instructions See Page 15 14 Install hood See Page 22 9 Attach mantel assembly to studs in the wall through the back brace using two 2 3 drywall screws provided 10 Slide front...

Page 15: ...4 This step is optional for VFD26FP3L10 log sets Place front twig 5 onto 1 log and flat area on 3 log The bottom of the front twig is to be placed behind the grate tang that is second from the left At...

Page 16: ...burner as well as the main flame should be visually checked as the log set is installed In normal operation at full rate after 10 to 15 minutes the flame appearance should be sets of yellow flames NOT...

Page 17: ...m louver assembly if applicable 3 Set REMOTE OFF ON switch to OFF 4 Turn off all electric power to the appliance if applicable 5 Push in gas control knob slightly and turn clockwise to OFF NOTE Knob c...

Page 18: ...pplicable 3 Set REMOTE OFF ON switch to OFF 4 Turn off all electric power to the appliance if applicable 5 Push in gas control knob slightly and turn clockwise to OFF NOTE Knob cannot be turned from P...

Page 19: ...ance 1 Set thermostat gas control knob to lowest setting 2 Turn off all electric power to appliance if service is to be performed if applicable Lighting Instructions 7 Turn gas control knob counterclo...

Page 20: ...Troubleshooting page 25 Cleaning and Maintenance Pilot Oxygen Depletion Sensor Pilot When the pilot has a large yellow tip flame clean the Oxygen Depletion Sensor as follows 1 Clean the ODS pilot by...

Page 21: ...is the OFF position PILOT is the PILOT position VFD26F M P 3 Max 20 000 BTU HR Min 14 000 BTU HR VFD26FP3L10 Max 10 000 Min N A VFD26F M P 2 Main Burner Operation The gas control modulates from a min...

Page 22: ...ireplace Attach top frame to fireplace Use two 2 8 x 1 2 Phillips screws for top frame 5 Replace bottom louver 6 Replace top louver 3 PIECE FRAME KIT SIDE TRIM Figure 21 HOOD INSTRUCTIONS 1 Remove upp...

Page 23: ...urner assembly NOTICE Do not let remote control receiver come in contact with burner assembly On circulating vent free firebox install remote control receiver behind bottom louver Refer to remote cont...

Page 24: ...L ELECTRICAL CODE ANSI NFPA 70 LAT EST EDITION A factory installed junction box is located on the lower right side of the fireplace Wiring must be fed to the junction box and attached to the receptacl...

Page 25: ...setting is not correct Replace gas regula tor 7 ODS pilot lights but flame goes out when control knob is released a Control knob not fully pressed in Press in control knob fully b Control knob not pre...

Page 26: ...R10947 WIRE ASSEMBLY VFD26F M P 3LP PART NUMBERS 10 R3623 PILOT ASSEMBLY 11 21590 PILOT BRACKET 14 R9022 BURNER TUBE 16 P182 ORIFICE 19 23493 TUBING ASSEMBLY 21 R3625 VALVE 23 23496 TUBING ASSEMBLY 30...

Page 27: ...e 27 PARTS VIEW 5 PIECE LOG Y ASSEMBL MILLIVOLT VALVE Y ASSEMBL THERMOSTATIC VALVE Y ASSEMBL 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 19 20 20 21 21 22 23 23 24 25 26 27 28 29 29 30 31 18 32 33...

Page 28: ...ireplace The magnets on the bottom of speed control will sufficiently hold the speed control in place 13 Attach fan control bracket to upper right side of firebox with one 10 x 1 2 hex screw provided...

Page 29: ...r Kit 110 VOLT AC JUNCTION BOX WHITE SPEED CONTROL FAN SWITCH GROUND BLACK FAN WHITE BLACK SWITCH BRACKET FBBX Wiring Diagram FBBX BLOWER KIT EXTENSION INSTALLATION INSTRUCTIONS cont FBB4 OPTIONAL VAR...

Page 30: ...e 1 side panel into firebox 5 Align clearance hole on brick panel bracket with screw hole in the left or right interior top of firebox Use two 2 10 x 1 2 screws to attach brick panel bracket to interi...

Page 31: ...reet Hartford CT 06114 Phone 860 722 2433 Toll Free 800 243 9360 Fax 860 293 0479 Toll Free Fax 800 274 2004 Websites www fwwebb com www victormfg com Parts Heater Hearth and Grills MASTER PARTS DISTR...

Page 32: ...s Empire Comfort Systems Inc 918 Freeburg Ave Belleville IL 62220 If you have a general question about our products please e mail us at info empirecomfort com If you have a service or repair question...

Reviews: