42724-0-1120

Page 2

Empire Comfort Systems Inc. • Belleville, IL

CAUTION

Due to sharp edges and the weight of the assembly, 

please use proper eye protection and gloves to reduce 

the potential for injuries.

TOOLS NEEDED:

•  Phillips 

•  Flathead 

•  5/16", 3/8"  •  Metal Snips

  Screwdriver    Screwdriver    Nut Drivers  •  Utility Knife

Other miscellaneous tools commonly used for framing 

and wiring.

INTRODUCTION

The Forced Air Heat Management system (HMFA) is designed 

to  be  installed  in  conjunction  with  specific  Empire  Comfort 

Systems  Fireplaces, to reduce the amount of heat produced 

during operation of the fireplace. This system includes a variable 

speed controlled blower that will deliver a desired percentage of 

the heat produced by the fireplace to the exterior of the building.

CONTENTS:

1.  Blower w/Base Assembly (1 ea.)

2.  Outer Termination Assembly (1 ea.)

3. 

6" Diameter Collar w/Flange (2 ea.)

4. 

6" X 6" X 6" “Y” Duct Connector (1 ea.)

5. 

6" Diameter Adapter (“Y” to Flex Connection) (1 ea.)

6. 

Band Clamp (4 ea.)

7. 

Rheostat (Variable Speed Control) w/Knob (1 ea.)

8. 

Junction Box w/Cover (1 ea.)

9.  Hardware Pack (1 ea.)

NOTE:

  Flex  venting  is  not  included  with  HMFA  kit.  Please 

order  the  SD6DFA25  Flex  Vent  kit  which  includes  25'  foot 

of  Flex 

Vent and (2) Band clamps to complete the system 

MAKE-UP AIR REQUIREMENT

When in operation, the HMFA Forced Air Heat Management 

System will deliver a percentage of heated air from the 

fireplace  to  the  exterior  of  the  building.  Because  a  certain 

amount of air will be removed from the building, it must be 

replaced with fresh make-up air, to prevent negative pressure 

from building up inside the structure.
Some central furnaces include make-up air dampers. If 

a make-up air damper is included with the furnace, check 

the damper for proper function and operation. There are 

variations in central furnace make-up dampers, therefore,  

you must check to see if the existing system is compatible. 

Some systems are designed to operate if a negative pressure 

is detected inside the building. 

Other systems are designed to operate only while the central 

furnace blower is operating, and would therefore require an 

additional make-up air damper system be installed. 

Make-up Air  Dampers  are  available  at  local  HVAC  supply 

stores or contractors. The Make-up Air Damper shall be sized 

based on the potential amount of cubic air to be expelled. 

The HMFA system has the potential of expelling 150 CFM.

If installing a Make-up Air Damper, it is recommended that it 

be installed at the opposite end of the building. In addition, 

installation of the damper at a high level of a vaulted ceiling 

will help dilute the incoming cold air with the warmer air 

normally found near the ceiling. 

LOCATING THE HEAT MANAGEMENT SYSTEM

1.  Determine the location of the HMFA in relationship to the 

fireplace. Placement of the HMFA blower system in 

relationship to the fireplace is indicated with minimum framed 

opening dimensions and vent length requirements as shown 

in 

Figure 1-3. 

Figure 1

HMFA Framed Opening Framing Locations

FRAMED OPENING

WHEN BELOW TOP

OF FIREPLACE

FRAMED OPENING

WHEN ABOVE THE

TOP OF FIREPLACE

6” FLEX VENT

4’ FOOT

MINIMUM

4” INCHES

MINIMUM

6" FLEX 

VENT

FRAMED 

OPENING 

WHEN ABOVE  

THE TOP OF 

FIREPLACE

FRAMED OPENING

WHEN BELOW

TOP

OF FIREPLACE

FRAMED OPENING

WHEN ABOVE

THE

TOP OF FIREPLACE

6” FLEX VENT

4’ FOOT

MINIMUM

4” INCHES

MINIMUM

4' FOOT 

MINIMUM

4" INCHES 

MINIMUM

FRAMED OPENING 

WHEN BELOW THE 

TOP OF FIREPLACE

Summary of Contents for HMFA-1

Page 1: ...ARD Failure to follow safety warnings exactly could result in serious injury death or property damage Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any...

Page 2: ...central furnaces include make up air dampers If a make up air damper is included with the furnace check the damper for proper function and operation There are variations in central furnace make up dam...

Page 3: ...LENGTH REQUIRED ALL APPLICATIONS REQUIRE A MINIMUM 7 LENGTH OF FLEX VENT FROM THE Y CONNECTOR TO THE BLOWER NO MINIMUM LENGTH REQUIRED NOTE Flex venting from kit SD6DFA25 CAUTION Due to sharp edges an...

Page 4: ...VENT DUCT WORK VERTICAL ALL APPLICATIONS REQUIRE A MINIMUM 7 LENGTH OF FLEX VENT FROM Y CONNECTOR TO THE BLOWER ALL APPLICATIONS REQUIRE A MINIMUM 7 LENGTH OF FLEX VENT FROM THE Y CONNECTOR TO THE BLO...

Page 5: ...or the junction box field wiring and internal placement of the rheostat to control the HMFA should be made Refer to electrical connections on page 10 4 The framed opening for installation of the HMFA...

Page 6: ...4 1 2 OFFSET FLANGE TO BE FLUSH WITH INSIDE WALL AND SECURED BACK EDGE OF BLOWER BASE BRACKET TO BE MOUNTED FLUSH TO THE INSIDE WALL VENT CONNECTION RIGHT SIDE Figure 5a Figure 5b LEFT SIDE VENT CONNE...

Page 7: ...ns based on the particular fireplace model you have NOTE Collar Flange Hand bend tabs to be bent down on DVLL72 only 4 DVCT SERIES 1 DVLL 36 48 60 2 DVLL72 3 8 DVL 36 46 4 DVCT SERIES 1 DVLL 36 48 60...

Page 8: ...making sure the bottom of the collars are touching the inner heat shield then install 4 10 X screws to secure each collar assembly See figure 10 INSTALLATION OF THE FLEX VENTING 11 Plan out the locati...

Page 9: ...adapter installed in step 10 Secure each flex vent section to the collars on top of the fireplace with a 7 diameter gear clamp See Figure 12 15 Attach and secure the Y adapter to the two flex section...

Page 10: ...ied electrician 2 Flexible Conduit Wire Harness 120 VAC Power In From Rheostat Wall Switch To Fireplace Connections Figure 14 18 The electrician is responsible for performing all wiring from the blowe...

Page 11: ...Figure 18 Figure 18 23 Install the cut end of the Air Duct over the Blower outlet See Figure 19 24 Check to see if the flanges of the Air Duct are flush with the bottom inside flange of the Outer Ter...

Page 12: ...e Outer Cover then place the Outer Cover into the Outer Termination frame Using 4 10 X screws secure the Outer Cover to complete the installation See Figure 22 BACK PLATE OUTER TERMINATION ASSEMBLY SC...

Page 13: ...42724 0 1120 Page 13 Empire Comfort Systems Inc Belleville IL This page intentionally left blank...

Page 14: ...1 9 R10856 Spacer Vibration 4 10 42715 Base Blower 1 N S R13145 Wire Harness 2 Feet 1 N S R13221 Diverter Connector 6 X 6 X 6 Y Branch 1 N S R13222 Adapter 6 Inch Flex 1 N S R13223 Clamp 7 Inch Diame...

Page 15: ...42724 0 1120 Page 15 Empire Comfort Systems Inc Belleville IL Figure 23 Exploded View 1 2 3 4 5 6 7 8 9 10...

Page 16: ...ww empirecomfort com Empire Comfort Systems Inc Belleville IL If you have a general question about our products please e mail us at info empirecomfort com If you have a service or repair question plea...

Page 17: ...ison voisine Suivre les instructions du fournisseur de gaz S il est impossible de joindre votre fournisseur de gaz appeler le service d incendie L installation et l entretien doivent tre ex cut s par...

Page 18: ...MED OPENING WHEN BELOW TOP OF FIREPLACE FRAMED OPENING WHEN ABOVE THE TOP OF FIREPLACE 6 FLEX VENT 4 FOOT MINIMUM 4 INCHES MINIMUM CONDUIT D VACUATION FLEXIBLE DE 6 po 152 4 mm OUVERTURE LORSQU ELLE S...

Page 19: ...GUEUR MINIMALE DE CONDUIT D VACUATION FLEXIBLE DE 7 pi 2 13 m DU RACCORD EN Y JUSQU LA SOUFFLANTE PAS DE LONGUEUR MINIMALE REQUISE REMARQUE Conduit d vacuation flexible de la trousse SD6DFA25 ATTENTIO...

Page 20: ...M Y CONNECTOR TO THE BLOWER VERTICAL VENTED FIREPLACE ATTENTION En raison du poids de l appareil et du fait qu il pr sente des bords tranchants porter une protection oculaire appropri e et des gants p...

Page 21: ...rh ostat pour commander le syst me HMFA Se reporter aux raccordements lectriques la page 10 4 L ouverture pour l installation du syst me HMFA est de 14 1 2 po x 14 1 2 po 368 3 mm x 368 3 mm dans tout...

Page 22: ...GE TO BE FLUSH WITH INSIDE WALL AND SECURED BACK EDGE OF BLOWER BASE BRACKET TO BE MOUNTED FLUSH TO THE INSIDE WALL VENT CONNECTION RIGHT SIDE Figure 5a Figure 5b LEFT SIDE VENT CONNECTION Figure 5c B...

Page 23: ...QUE Bride de collier languettes plier vers le bas manuellement sur le mod le DVLL72 seulement 4 DVCT SERIES 1 DVLL 36 48 60 2 DVLL72 3 8 DVL 36 46 4 DVCT SERIES 1 DVLL 36 48 60 2 DVLL72 3 8 DVL 36 46...

Page 24: ...rmique interne puis visser 4 vis n 10 x 1 2 po pour fixer chaque collier Voir Figure 10 INSTALLATION DU CONDUIT D VACUATION FLEXIBLE 11 Pr parer l emplacement de l adaptateur Y Le placement de cet ada...

Page 25: ...r l aide d un collier de serrage vis sans fin de 7 po 177 8 mm de diam tre Voir Figure 12 15 Fixer solidement l adaptateur en Y aux deux sections de conduit d vacuation flexible provenant du foyer au...

Page 26: ...tat Wall Switch To Fireplace Connections Figure 14 18 L lectricien est responsable de la r alisation de l ensemble du c blage partir de la soufflante jusqu au rh ostat mont sur le mur Le rh ostat doit...

Page 27: ...nduit d air sur la sortie de la soufflante Voir Figure 19 24 V rifier si les rebords du conduit d air sont align s avec le rebord interne inf rieur de l assemblage d extr mit ext rieure comme illustr...

Page 28: ...ercle ext rieur puis placer le couvercle ext rieur dans l assemblage d extr mit ext rieure l aide de 4 vis n 10 x 1 2 po fixer le couvercle ext rieur pour terminer l installation Voir Figure 22 BACK P...

Page 29: ...42724 0 1120 Page 13 Empire Comfort Systems Inc Belleville IL Page laiss e vierge intentionnellement...

Page 30: ...145 Faisceau de c bles 2 pi 610 mm 1 N M R13221 Raccord en Y 6 po x 6 po x 6 po 152 4 mm x 152 4 mm x 152 4 mm 1 N M R13222 Adaptateur flexible 6 po 152 4 mm 1 N M R13223 Collier de serrage vis sans f...

Page 31: ...42724 0 1120 Page 15 Empire Comfort Systems Inc Belleville IL Figure 23 Vue clat e 1 2 3 4 5 6 7 8 9 10...

Page 32: ...irecomfort com Empire Comfort Systems Inc Belleville IL Pour toute question g n rale concernant nos produits veuillez nous envoyer un courriel info empirecomfort com Pour toute question d entretien ou...

Reviews: