background image

33587-5-0820

Page 9

Empire Comfort Systems Inc. • Belleville, IL

To install the blower kit or access the junction box, remove lower 

louver as illustrated by 

Figure 18.

A factory included junction box is located in the lower compartment 

of the fireplace. Wiring must be fed through the 7/8 inch diameter 

hole provided on the lower side of the fireplace, and secured to the 

outer wrap with the clamp provided. Leave approximately 6 inch of 

wire in the junction box for connection.

Attach black wire to brass screw on the receptacle and attach 

white wire to the silver screw. Attach ground wire (bare) to the 

green (ground) screw. 

Install the receptacle into the junction box as illustrated. 

 

Attach cover plate. 

Place Junction Box so that it is approximately 8 to 12 inches away 

from the outer wrap wall. Secure wiring at outer wrap of fireplace 

with wire clamp provided.

NOTE:

 Depending on the unit, the Junction box may be installed 

on the outer side.

ATTENTION:

 If installed, do not damage gas inlet supply line 

when blower assembly is inserted into fireplace. In some cases, 

removal of the gas inlet supply line may be necessary. 

Figure 17

1.  Insert  blower  assembly  into  interior,  bottom  of  fireplace. 

 

NOTICE:

 On peninsula models, the blower must be installed 

at the end which has the brick panel installed. Position blower 

assembly so that you align the notch on back of blower as-

sembly with the center screw on side/end panel, then push 

the blower assembly against fireplace outer panel. The blower 

wheel must be centered with the side/end wall of the fireplace. 

The magnets on the back and bottom of blower assembly will 

sufficiently hold blower assembly in place. 

See Figure 18.

2.  Once the blower assembly is in position, remove the upper 

louver as shown and locate the switch tab (end of support 

channel) on top of the firebox. Install the fan control switch 

by first removing the two pre-installed screws in the tab, then 

secure the fan control switch to the tab. 

See Figure 19. 

Once 

the fan control has been secured, bend the tab forward so that 

the face of the fan control is pushed down so it contacts the 

firebox top.

3.  Next, find the fan control wire assembly. Feed the wires over 

the top of the firebox. The fan control wires will slide down be

-

tween the firebox and outer wrap near the blower assembly.

 

See Figure 18. Attach the two 3/16 inch wire terminals to 

the fan control switch as shown in Figure 19. Attach the 

wire terminals at the blower as shown by letters “A” and 

“B” in Figure 19.

FAN

CONTROL

SWITCH

WIRE ASSEMBLY

FROM FAN

CONTROL SWITCH

Figure 18

4.  Locate the ground wire attached to the blower base. Secure 

the opposite end with the ring tongue terminal to the outer bot-

tom of the fireplace using using the self drilling screw located 

in the hardware pack.

5.  Route the wires away from moving parts of the blower assem-

bly and retain wires together near the blower motor using the 

plastic purse clip provided.

6.  To complete the installation, plug the power cord into the junc-

tion box receptacle previously installed in the bottom of the 

fireplace. 

See Figures 17 and 18.

7.  Once all connections are made electrically, it is recommended 

that you test the blower fan control operation by turning on 

power to the blower

 (CAUTION

: 110 Volt). 

Turn the fireplace 

on and let run until blower is activated. This should take ap-

proximately 10 to 20 minutes from a cold start. Once blower 

is activated, check for proper operation. Do not place hands 

near blower assembly or other wiring while power is on.

8.  Replace louver(s).

9.  This completes the installation of the optional FBB5 Blower kit 

accessory.

NOTE: 

This blower is equipped with a heat activated fan control 

switch. Blower will operate when the fireplace warms up, and will 

turn off automatically when the fireplace cools down. The time will 

vary for the activation of the fan control switch depending on sev-

eral factors including fireplace type, BTU input variables, and log 

set style. Generally, it may take from 10 to 20 minutes to activate 

blower/fan control from a cold start.

DVP(SP,PP) FIREPLACE BLOWER INSTALLATION

Summary of Contents for FBB5-1

Page 1: ...he grounding prong from this plug For an ungrounded receptacle an adapter which has two prongs and a wire for grounding can be purchased plugged into the ungrounded receptacle and its wire connected t...

Page 2: ...TABLE OF CONTENTS Standard Firebox Blower Installation 3 4 VFP SB PB Firebox Blower Installation 5 6 VFP SP PP Fireplace Blower Installation 7 8 DVP SP PP Fireplace Blower Installation 9 10 Maintenanc...

Page 3: ...s Figure 2 Deluxe Louvered shown Flush Face and Premium Models Figure 3 Deluxe Flush shown Select Firebox Models Figure 4 2 Remove air deflector by removing the four screws securing it to the blower a...

Page 4: ...astic purse clip provided 11 To complete the installation plug the power cord into the junction box receptacle at the right rear corner of the firebox outer wrap See Figure 7 Figure 7 12 If room permi...

Page 5: ...es through the hole at the top of the firebox Feed the wires over the firebox top and down between the firebox side and outer wrap then secure the fan control switch with 2 6 screws provided See Figur...

Page 6: ...CATION Figure 10 HEARTH BLOWER ASSEMBLY CENTER AND INSTALL AGAINST OUTER WRAP AS SHOWN WIRES FROM FAN CONTROL SWITCH OUTER WRAP Figure 11 VFP SB PB FIREBOX BLOWER INSTALLATION USE SCVI VARIABLE SPEED...

Page 7: ...the top corner of the firebox Remove the plug with a standard screwdriver and discard plug 3 Next find the fan control switch and wire assembly Feed the wires through the hole at the top of the firebo...

Page 8: ...elleville IL HEARTH BLOWER ASSEMBLY CENTER AND INSTALL AGAINST OUTER WRAP AS SHOWN WIRES FROM FAN CONTROL SWITCH OUTER WRAP Figure 15 USE OF A STANDARD ON OFF WALL SWITCH TO OPERATE OPTIONAL BLOWER Fi...

Page 9: ...l switch to the tab See Figure 19 Once the fan control has been secured bend the tab forward so that the face of the fan control is pushed down so it contacts the firebox top 3 Next find the fan contr...

Page 10: ...587 5 0820 Page 10 Empire Comfort Systems Inc Belleville IL FAN CONTROL SWITCH Figure 19 USE OF A STANDARD ON OFF WALL SWITCH TO OPERATE OPTIONAL BLOWER Figure 20 DVP PP SP FIREPLACE BLOWER INSTALLATI...

Page 11: ...blower motor Blower Wheels The blower wheels will collect lint and could require periodic clean ing If the air output decreases or the noise level increases it indi cates a dirty blower wheel Remove f...

Page 12: ...el Number and Serial Number from the name plate on your equipment Then determine the Part Number not the Index Number and the Description of each part from the fol lowing illustration and part list Be...

Reviews: