LED CODES
Steady ON
Normal operation, power ON to control
2 Flashes
3 unsuccessful ignition trials
3 Flashes
Main burner flame failed 4 times during a single heating cycle
4 Flashes
Interrupt power for 5 seconds to reset control
Steady Flash
Flame detected out of sequence
OPTIONAL REMOTE CONTROL
Electric (120 volt) Operated Remote Control (FREC)
1. Disconnect 3-prong power cord from receptacle.
2. Remove wire from 120 VAC hot terminal on control module.
3. Connect female terminal from receiver onto 120 VAC hot
terminal on control module.
4. Connect remaining wire from remote control (male
terminal) to (female terminal) on power cord removed from
control module (step 2).
Figure 71
5. Insert electric remote control power cord plug into the
junction box on the right side of fireplace.
6. Connect 3-prong plug into receptacle.
DIRECT IGNITION WIRING DIAGRAM