background image

29209-0-0911

Page 21

With proper installation and maintenance, your new Direct Vent Gas Fireplace will provide years of trouble-free 

service. If you do experience a problem, refer to the Trouble Shooting Guide below. This guide will assist a qualified 

service person in the diagnosis of problems and the corrective action to be taken.

1.  Spark ignitor will not light pilot after repeated triggering 

of piezo ignitor button.

a.  Defective ignitor (no spark electrode) 

 

— Check for spark at electrode and pilot; if no spark and 

electrode wire is properly connected, replace ignitor.

b.  No gas or low gas pressure.

 

— Check remote shut off valves from fireplace. Usually 

there is a valve near the main. There can be more than 

one (1) valve between the fireplace and main.

 

— Low pressure can be caused by a variety of situations 

such as a bent line, too narrow diameter of pipe, or low 

line pressure. Consult with plumber or gas supplier.

c.  No LP in tank. 

  — Check LP (propane) tank. Refill tank.

2.  Pilot  will  not  stay  lit  after  carefully  following  lighting 

instructions.

a.  Defective thermocouple.

 

— Check that pilot flame impinges on thermocouple. Clean 

and/or adjust pilot for maximum flame impingement.

 

— Ensure the thermocouple connection at the gas valve 

is fully inserted and tight (hand tight plus 1/4 turn). Faulty 

thermocouple if reading is below specified minimum of 15 

millivolts.

 

— Disconnect the thermocouple from the valve, place one 

millivolt meter lead wire on the end of the thermocouple 

and the other millivolt meter lead wire on the thermocouple 

copper wire. Start the pilot and hold the valve knob in. If 

the millivolt reading is less than 15 millivolt, replace the 

thermocouple.

b.  Defective valve.

 

— If thermocouple is producing more than 15 millivolts, 

replace faulty valve.

3.  Pilot burning, no gas to burner, valve knob “ON”, REMOTE/

OFF/ON switch “ON.”

a.  REMOTE/OFF/ON switch, wall switch, remote control or 

wires defective.

 

— Check REMOTE/OFF/ON switch and wires for proper 

connections. Place jumper wires across terminal at switch. 

If burner comes on, replace defective switch. If OK, place 

jumper wires across switch wires at gas valve-if burner 

comes on, wires are faulty or connections are bad.

b.  Thermopile may not be generating sufficient millivolts.

 

— If the pilot flame is not close enough physically to the 

thermopile, adjust the pilot flame.

 

— Be sure the wire connections from the thermopile at 

the gas valve terminals are tight and the thermopile is fully 

inserted into the pilot bracket.

 

— Check the thermopile with a millivolt meter. Take the 

reading at TH-TP & TP terminals of the gas valve. The 

meter should read 350 millivolts minimum, while holding the 

valve knob depressed in the PILOT position, with the pilot 

lit, and the REMOTE/OFF/ON switch in the OFF position. 

Replace the faulty thermopile if the reading is below the 

specified minimum.

 

— With the pilot in the ON position, disconnect the thermopile 

leads from the valve. Take a reading at the thermopile leads. 

The reading should be 350 millivolts minimum. Replace 

the thermopile if the reading is below the minimum.

c.  Defective valve.

 

— Turn valve knob to ON. Place REMOTE/OFF/ON switch 

to ON. Check with millivolt meter at thermopile terminals. 

Millivolt meter should read greater than 200 millivolts. If 

the reading is okay and the main burner does not ignite, 

replace the gas valve.

d.  Plugged main burner orifice.

 

— Check main burner orifice for blockage and remove.

4.  Frequent pilot outage problem.

a.  Pilot flame may be too high or too low, or blowing (high), 

causing pilot safety to drop out.

 

— Clean and adjust flame for maximum flame impingement 

on the thermocouple. Follow lighting instructions 

carefully.

5.  The pilot and main burner extinguish while in operation.

a.  No LP (Propane) in tank. 

 

Check LP (Propane) tank. Refill fuel tank.

b.  Inner vent pipe leaking exhaust gases back into system.

 

— Check for leaks.

c.  Glass too loose, gasket leaks in corners after usage.

 

— Be certain glass assembly is installed correctly.

d.  Horizontal vent improperly pitched.

 

— The horizontal vent cap should slope down only enough 

to prevent any water from entering the unit. The maximum 

downwards slope is 1/4 inch.

e.  Bad thermopile or thermocouple.

 

— Replace if necessary.

f.  Improper vent cap installation.

 

— Check for proper installation and freedom from debris 

or blockage.

6.  Glass soots, and/or soot deposits collected internally.

a.  Flame impingement on decorative glass.

 

— Check and adjust glass positioning. See Page 15. 

Contact Empire Comfort Systems, Inc.

b.  Debris around throat of main burner.

 

— Inspect the opening at the base of the main burner. It 

is imperative that NO material be placed in this opening.

7.  Flame burns blue and lifts off main burner.

a.  Insufficient oxygen being supplied.

 

— Check to make sure vent cap is installed properly and 

free of debris. Make sure that vent system joints are tight 

and have no leaks.

 

— Check to make sure that no material has been placed 

at the main burner base.

b.  On taller vent heights (20-35 feet) it may help to open the 

small flue baffle vent located directly above the pilot. This 

will help maintain a positive vent draft and balance the 

required combustion air flow.

STANDING PILOT TROUBLESHOOTING

Summary of Contents for DVL25IN33N-1

Page 1: ...NG If the information in these instruc tions are not followed exactly a fire or explo sion may result causing property damage personal injury or loss of life WARNING HOT GLASS DO NOT TOUCH NEVER WILL...

Page 2: ...y Information 16 Glass Placement 17 Operating Instructions 18 Standing Pilot Lighting Instructions 19 Standing Pilot Wiring 20 Standing Pilot Troubleshooting 21 IPI Electronic System Operating Instruc...

Page 3: ...ass front or any part removed for servicing the appliance must be replaced prior to operating the appliance Work should be done by a qualified service person Keep burner and control compartment clean...

Page 4: ...erform service or make adjustments in an area where the conditions are such that you may not detect the odor if there has been a leak of LP Gas Odor fade due to oxidation by rust or adsorption on wall...

Page 5: ...West 42nd St New York N Y 10036 NOTICE Prior to operating this unit be sure to clean the interior porcelain coated liner panels and glass door with a soft clean cloth Due to normal manufacturing proc...

Page 6: ...s and clamps Recommended when installing to a square or rectangular clay flue DVK35 Vent Extension Kit 35 flex vent extension section with 2 connectors and 4 clamps NOTICE When installing vent caps sp...

Page 7: ...EPLACE INSERT DIMENSIONS all dimensions in inches MODEL A B C D E F G H I J K L M N O DVL25IN 28 16 1 2 15 10 1 2 25 1 4 12 3 4 17 18 5 16 27 6 7 8 9 1 4 20 22 1 4 40 22 1 2 DVL33IN 31 19 1 2 16 1 2 1...

Page 8: ...ation of any type should be placed on or attached to the fireplace The flow of heat can ignite combustibles Figure 4 8 MINIMUM CLEARANCE TO PERPENDICULAR COMBUSTIBLE SIDE WALL FROM EDGE OF DOOR FRAME...

Page 9: ...ne of the procedures results in pressures in excess of 1 2 psig 14 w c 3 5 kPa on the fireplace gas valve it will result in a hazardous condition Checking Manifold Pressures Both Propane and Natural g...

Page 10: ...urround panel kits have been tested and approved to cover existing air circulation vents or grills NOTICE Cutting of sheet metal parts of a fireplace in order to install the fireplace insert is prohib...

Page 11: ...y chimney may need to be removed to allow installation of the flexible vent pipe When installing into a zero clearance factory built wood burning fireplace the use of the DVKI Round Vertical Terminati...

Page 12: ...CESS COVER PLATE BLOWER POWER CORD OPTIONAL ON OFF SWITCH LOCATION VENT CLAMPS RECTANGULAR TERMINATION CAP DVVK3FV KIT ROUND TERMINATION CAP DVKI KIT ROUND CO LINEAR TO CO AXIAL ADAPTOR 10 MINIMUM 35...

Page 13: ...stem exposed to cold weather 4 Inspect joints to verify that no pipe sections or fittings have been disturbed and consequently loosened Also check mechanical supports such as wall straps or plumbers t...

Page 14: ...d white wires as shown in Figure 13b Note This bypasses the On Off switch located on the unit s left hand side flange 3 Run the low voltage alternate switch wires over to the right or left surround pa...

Page 15: ...THE FIREPLACE INSERT NEVER OB STRUCT OR MODIFY THE AIR INLET OUTLET LOUVERS ON THE FIREPLACE INSERT IN ANY MANNER SURROUND ASSEMBLY ENGAGE SIDE PANEL MAGNETS TO SIDE FLANGES ON INSERT BACK SIDE NOTE...

Page 16: ...oval of the blower system must be performed by a qualified service person If the blower assembly must be replaced the following steps are recommended for removal 1 Turn off gas and disconnect the elec...

Page 17: ...Glass should only be performed after the DVL Fireplace Insert has been fully installed secured and tested for leaks If operating the burner with a Remote Control make sure all batteries are installed...

Page 18: ...ilot The pilot remains ON even when the main burner is OFF Whenyouignitethepilot thethermopileproducesmillivolts electrical current which energizes the magnet in the gas valve After 30 seconds to 1 mi...

Page 19: ...applicable 13 Set REMOTE OFF ON switch to desired setting FOR YOUR SAFETY READ BEFORE LIGHTING WARNING If you do not follow these instructions exactly a fire or explosion may result causing property...

Page 20: ...PERATION AFTER SERVICING For Standing Pilot Ignition Wiring Appliance Requirements WARNING DO NOT CONNECT 110 120 VAC TO THE GAS CONTROL VALVE OR THE APPLIANCE WILL MALFUNCTION AND THE VALVE WILL BE D...

Page 21: ...t bracket Check the thermopile with a millivolt meter Take the reading at TH TP TP terminals of the gas valve The metershouldread350millivoltsminimum whileholdingthe valve knob depressed in the PILOT...

Page 22: ...and LIGHTING INSTRUCTIONS for In termittent Pilot controls found in this manual and on labels found in the control compartment located in the lower cavity of the appliance 2 During the operating seaso...

Page 23: ...t is used CAUTION Do not operate the appliance with panel s removed cracked or broken Replacement of the panel s should be done by a licensed or qualified service person WARNING Improper installation...

Page 24: ...structions for detailed operation information FOR YOUR SAFETY READ BEFORE LIGHTING WARNING If you do not follow these instructions exactly a fire or explosion may result causing property damage person...

Page 25: ...ions on page 24 and Wiring Diagram on page 23 Troubleshooting Before proceeding with the procedures in the following trouble shooting table verify that the power supply AC DC adapter is present and th...

Page 26: ...ire harness 4 Replace the DFC board 1 Verify the electrical connections integrity and make sure they are in accordance with the relevant system wiring diagram If necessary replace the wire harness 2 I...

Page 27: ...and verify voltage at ignition between the EV1 terminal and the ground connection on the valve body 5 1 If the voltage is greater than 0 then Replace Valve 5 2 Or Replace DFC 6 Check the pressure at...

Page 28: ...g Glass Door Frequency After the first 3 to 4 hours of use As necessary after initial cleaning By Home owner Task Remove and clean glass after the first 3 to 4 hours of use After the initial cleaning...

Page 29: ...L25IN 43 DVL33IN 22 1 4 DVL25IN 25 1 4 DVL33IN 6 2 1 4 6 28 DVL25IN 31 DVL33IN 14 DVL25IN 17 DVL33IN Black Used to raise insert and surround panels when installed in a fireplace without a flush hearth...

Page 30: ...3 N P 1 22950 22950 22950 22950 FLUE CONNECTOR GUIDE 2 23309 23211 23309 23211 SLIDE PLATE ASSEMBLY 3 R9188 R9188 R9188 R9188 GASKET TOP 4 16223 27718 16223 27718 SPRING RETAINER ASSEMBLY 5 27666 2769...

Page 31: ...5 28063 28063 28683 28683 VALVE BRACKET 26a R7577 R7577 R11125 R11125 VALVE SIT NAT 26b R7578 R7578 R11126 R11126 VALVE SIT LP 27 R6207 R6207 R6207 R6207 ELBOW 5 16 X 3 8 NPT 90 28 27147 27672 28791 2...

Page 32: ...reet Hartford CT 06114 Phone 860 722 2433 Toll Free 800 243 9360 Fax 860 293 0479 Toll Free Fax 800 274 2004 Websites www fwwebb com www victormfg com Parts Heater Hearth and Grills MASTER PARTS DISTR...

Page 33: ...29209 0 0911 Page 33 APPLIANCE SERVICE HISTORY Date Dealer Name Service Technician Name Service Performed Notes...

Page 34: ...29209 0 0911 Page 34 APPLIANCE SERVICE HISTORY Date Dealer Name Service Technician Name Service Performed Notes...

Page 35: ...29209 0 0911 Page 35 APPLIANCE SERVICE HISTORY Date Dealer Name Service Technician Name Service Performed Notes...

Page 36: ...s Empire Comfort Systems Inc 918 Freeburg Ave Belleville IL 62220 If you have a general question about our products please e mail us at info empirecomfort com If you have a service or repair question...

Reviews: