32261-5-0414
Page 30
Figure 60
VENT TERMINAL CLEARANCES
Canadian Installations1
US Installations2
Canadian Installations1
US Installations2
A= Clearance above grade,
veranda, porch, deck, or
balcony
12 in (30 cm)
12 in (30cm)
I= Clearance to service
regulator vent outlet
3 ft (91 cm)
*
B= Clearance to window or
door that may be open
6 in (15 cm) for appli-
ances ≤ 10,000 Btuh
(3 kW), 12 in (30 cm)
for appliances > 10,000
Btuh (3 kW) and ≤
1000,000 Btuh (30 kW),
36 in (91 cm) for appli-
ances > 100,000 Btuh
(30 kW)
6 in (15 cm) for appli-
ances ≤ 10,000 Btuh (3
kW), 9 in (23 cm) for ap-
pliances > 10,000 Btuh
(3 kW) and ≤ 50,000
Btuh (15 kW), 12 in
(30 cm) for appliances >
50,000 Btuh (15 kW)
J= Clearance to nonme-
chanical air supply
inlet to building or the
combustion air inlet to
any other appliance
6 in (15 cm) for appli-
ances ≤ 10,000 Btuh (3
kW), 12 in (30 cm) for
appliances > 10,000
Btuh (3 kW) and ≤
1000,000 Btuh (30 kW),
36 in (91 cm) for appli-
ances > 100,000 Btuh
(30 kW)
6 in (15 cm) for appli-
ances ≤ 10,000 Btuh
(3 kW), 9 in (23 cm) for
appliances > 10,000 Btuh
(3 kW) and ≤ 50,000 Btuh
(15 kW), 12 in (30 cm) for
appliances > 50,000 Btuh
(15 kW)
C= Clearance to perma-
nently closed window
*
*
K= Clearance to a mechani-
cal air supply inlet
6 ft (1.83 m)
3 ft (91 cm) above if
within 10 ft (3 m) hori-
zontally
D= Vertical clearance
ventilated soffit located
above the terminal within
a horizontal distance of 2
feet (61 cm) from the cen-
ter line of the terminal
*
*
L= Clearance above paved
sidewalk or paved drive-
way located on public
property
7 ft (2.13 m) †
*
E= Clearance to unventi-
lated soffit
*
*
M= Clearance under
veranda, porch deck, or
balcony
12 in (30 cm) ‡
*
F= Clearance to outside
corner
*
*
1
In accordance with the current CSA B149.1, Natural Gas and Propane Instal-
lation Code
G= Clearance inside corner
*
*
2
In Accordance with the current ANZI Z223.1/NFPA 54, National Fuel Gas
Code
H= Clearance to each side
of center line extended
above meter/regulator
assembly
3 ft (91 cm) within a
height 15 ft (4.5 m)
above the meter/regula-
tor assembly
*
†
A vent shall not terminate directly above a sidewalk or paved driveway that is
located between two single family dwellings and serves both dwellings
‡
Permitted only if veranda,, porch, deck, or balcony is fully open on a minimum
of two sides beneath the floor.
*
For clearances not specified in ANZI Z223.1/NFPA 54 or CSA B149.1, one of
the following shall be indicated:
a)
A minimum clearance value determined by testing in accordance with section
2.23.5, or;
b)
A reference to the following footnote: “Clearance in accordance with local
installation codes and the requirements of the gas supplier.”
Summary of Contents for DVCC32LP
Page 39: ...32261 5 0414 Page 39 Figure 77 MILLIVOLT STANDING PILOT WIRING DIAGRAM BP3 SERIES ...
Page 46: ...32261 5 0414 Page 46 INTERMITTENT PILOT CONTROL SYSTEM TROUBLESHOOTING BP7 SERIES ...
Page 47: ...32261 5 0414 Page 47 INTERMITTENT PILOT CONTROL SYSTEM TROUBLESHOOTING BP7 SERIES ...
Page 51: ...32261 5 0414 Page 51 MILLIVOLT PARTS VIEW DVCP 32 36 42 BP3 ...
Page 53: ...32261 5 0414 Page 53 IP PARTS VIEW DVCP 32 36 42 BP7 ...