CG Drives & Automation 01-5965-01r1
Single-Pump System Installation
31
pause time (window 22). The parameters can be adjusted to achieve desired
magnitudes of pause times, start level and number of starts per hour. See Fig.
11, page 23, and 14, page 30.
The level setting in window 21 is set for shorter or longer pumping and pause
cycles. Higher values increase the calculated pause time and the amount of
accumulated water.
The level setting is best adjusted after a few pumping cycles in order to adjust
the pause time, and hence the start level in the pit. See schematic pump cycle
example in Fig. 11 and 14.
Maximum pause time for the pump is set in window 22. The calculated pause
time will be limited to this value. In some applications the inflow may increase
rapidly during a pause. To prevent overflow in these situations the maximum
pause time can be set in accordance with the circumstances.
6.5
Returning to the default settings
1. To return to the default settings go to window 99.
2. If any value differs from the default values (see Table 8). “Usr” (set by the
user) is displayed in the window.
3. Press
to return to the default settings. “dEF” (default setting) is shown
in the window. Confirm by pressing
.
NOTE: Also, windows 6, 7 and 8 are set to 0.
ENTER
Summary of Contents for DCM
Page 1: ...Emotron DCM Control Unit Instruction manual English...
Page 2: ......
Page 6: ...2 Inside the Box CG Drives Automation 01 5965 01r1...
Page 8: ...4 Safety CG Drives Automation 01 5965 01r1...
Page 28: ...24 Installation CG Drives Automation 01 5965 01r1...
Page 36: ...32 Single Pump System Installation CG Drives Automation 01 5965 01r1...
Page 46: ...42 Protection and Alarm CG Drives Automation 01 5965 01r1...
Page 54: ...50 Technical Data CG Drives Automation 01 5965 01r1...
Page 60: ...56 Window Parameters CG Drives Automation 01 5965 01r1...
Page 62: ...58 Service CG Drives Automation 01 5965 01r1...
Page 64: ...60 Appendix CG Drives Automation 01 5965 01r1 Fig 19 Dual pump example Figur 16...
Page 65: ......