CG Drives & Automation 01-5965-01r1
Protection and Alarm
39
8
Protection and Alarm
When an error occurs, the triangular alarm sign starts to flash and the alarm
relay is activated.
Window 00 becomes active and gives the information about the alarm
according to the alarm list, see Table 6, page 41.
Alarm in a dual-pump application
The fault code is shown in window 00 of the respective DCM, the alarm relay is
only set on terminal 6 of the DCM SLAVE when an error occurs. If a latched
alarm occurs it must be reset on the respective DCM by pressing the
button or, if specified as digital input, by an external reset.
8.1
Phase sequence (F1)
When the DCM is first switched on, phases L1, L2 and L3 are checked for
correct phase sequence.
If the wrong phase sequence is detected, an F1 alarm is generated and the
ALARM relay on terminal 6 is activated. The pump will not start. Switch the
power off and shift phase L2 and L3.
8.2
Phase asymmetry (F2)
The permitted phase asymmetry is set in window 41, see Table 8, page 53. Any
failure shorter than 5 seconds is ignored. When phase asymmetry is detected an
F2 alarm is generated and the ALARM relay on terminal 6 is activated. The
pump will be stopped.
If window 42 is set to
on,
the alarm can be reset by pressing the
button or
by using the external reset signal.
NOTE: Do not shift L1, only shift phase L2 and L3.
Summary of Contents for DCM
Page 1: ...Emotron DCM Control Unit Instruction manual English...
Page 2: ......
Page 6: ...2 Inside the Box CG Drives Automation 01 5965 01r1...
Page 8: ...4 Safety CG Drives Automation 01 5965 01r1...
Page 28: ...24 Installation CG Drives Automation 01 5965 01r1...
Page 36: ...32 Single Pump System Installation CG Drives Automation 01 5965 01r1...
Page 46: ...42 Protection and Alarm CG Drives Automation 01 5965 01r1...
Page 54: ...50 Technical Data CG Drives Automation 01 5965 01r1...
Page 60: ...56 Window Parameters CG Drives Automation 01 5965 01r1...
Page 62: ...58 Service CG Drives Automation 01 5965 01r1...
Page 64: ...60 Appendix CG Drives Automation 01 5965 01r1 Fig 19 Dual pump example Figur 16...
Page 65: ......