Single-Pump System Installation
CG Drives & Automation 01-5965-01r1
Fig. 14 Relative volume in the pit at pump start
6.3
Adjustment of stop level
The stop level can always be adjusted in the following way:
1. Change the snore margin (window 12) and perform a new Auto set. The
new stop level will be set in relation to the snore margin. See examples in
Fig. 2, page 11 and Fig. 3, page 12.
2. Change the stop level directly in window 11.
6.4
Start conditions and pause time
adjustment
In normal operation there are two starting options:
1. Pump start after remaining pause time (window 01).
2. Pump start at high level switch (window 53 = “1”). This requires connection
of a high-level switch according to Section 6.1.5, page 27.
The pump will also start if a non-latched alarm disappears or the
button is
pressed during pause.
Calculation of pause time is based on previous pumping and pause times and is
controlled by the two parameters, level setting (window 21), and maximum
Pit volume
window 21=1.0
window 21=2.0
window 21=4.8
Time
Pausing
Pumping
[min
Summary of Contents for DCM
Page 1: ...Emotron DCM Control Unit Instruction manual English...
Page 2: ......
Page 6: ...2 Inside the Box CG Drives Automation 01 5965 01r1...
Page 8: ...4 Safety CG Drives Automation 01 5965 01r1...
Page 28: ...24 Installation CG Drives Automation 01 5965 01r1...
Page 36: ...32 Single Pump System Installation CG Drives Automation 01 5965 01r1...
Page 46: ...42 Protection and Alarm CG Drives Automation 01 5965 01r1...
Page 54: ...50 Technical Data CG Drives Automation 01 5965 01r1...
Page 60: ...56 Window Parameters CG Drives Automation 01 5965 01r1...
Page 62: ...58 Service CG Drives Automation 01 5965 01r1...
Page 64: ...60 Appendix CG Drives Automation 01 5965 01r1 Fig 19 Dual pump example Figur 16...
Page 65: ......