58
GB
GB
A
Outdoor Unit
B
B
Maximum difference
in height
Indoor Unit
Indoor unit
Indoor unit
The indoor units are connected to the outdoor unit trough copper pipes.
A maximum of 10 curves is allowed, beyond this number the correct functioning and declared performance of the air conditioner can no longer be guaranteed.
In the case of installing the lower indoor unit of the outdoor unit with a difference in height of more than 5 meters, make an intermediate oil trap.
Warning!
- The siphon must be installed on both pipes.
A
D
E
C
B
1/2
1/2
Outdoor Unit
Indoor Unit
Siphon
A (mm)
B (mm)
C (mm)
D (mm)
E (mm)
> 300
> 600
> 300
> 2000
> 600
5.3 Distance between the units
5.2 Minimum functional distances
Outdoor UNIT
Model
Difference in
level maximum
between
Indoor U. and
Outdoor U. (A)
Difference in
level maximum
between
Indoor U. and
Outdoor U. (B)
Reach
maximum
Indoor U. and
Outdoor U.
Maximum
lenght
total pipe
Total length
standard (m)
Amount of additional
gas over the
total length
standard (g/m)
m
m
m
m
m
g/m
X-REVO-0919E
-
5
15
15
5
20
X-REVO-1219E
-
5
15
15
5
20
X-REVO-1819E
-
5
15
15
5
20
X-REVO-2419E
-
5
15
15
5
30
X-REVO-0919EX
-
10
25
25
5
12
X-REVO-1219EX
-
15
25
25
5
12
X-REVO-1819EX
-
15
30
30
5
12
X-REVO-1419DE
7.5
15
15
30
15
12
X-REVO-1819DE
7.5
15
15
30
15
12
X-REVO-2419TE
7.5
15
20
45
15
12
X-REVO-3619QE
7.5
15
20
60
20
12
5. UNIT POSITIONING