EMKO ESM-7311-H Instruction Manual Download Page 23

°C

SV

PR

Main Operation

Screen

3 secs.

23

Buzzer is Active During This Time

This parameter can be observed if buzzer function selection

is 1.

It can be adjusted from 1 to 99 minutes. When this parameter is 1, if decrement button
is pressed,

is observed. Then buzzer becomes active till buzzer silence button

³

( Default =

)

Button Protection Parameter ( Default = 0 )

There is no protection

Cooking time(Timer) can not be changed. Cooking ON/OFF operation is
not performed.
SET value can not be changed

Cooking time (Timer) and set value can not be changed. Cooking ON/OFF
operation is not performed.

Programming Mode Accessing Password

Password for entering to the programming mode is defined with this parameter.
It can be adjusted from 0 to 999. If it is 0, programming mode accessed without
entering password.

( Default = 0 )

Cooking time (Timer) and set value can not be changed. Cooking ON/OFF
operation is performed when

button is pressed.

7

8

DIGITAL INPUT

K

When K switch that is connected to the cooking time
start/stop input, getting closed condition, cooking
time (Timer) is started and cooking time active led
becomes active. While cooking time (Timer)
continues if K switch getting open condition, cooking
time (Timer) is finished and cooking time active led
lights off.

4.5.2 Cooking Time (Timer) ON/OFF Operation with Cooking Time Start/Stop Input

4.5 Cooking Time (Timer) ON/OFF Operation

4.5.1 Cooking Time (Timer) ON/OFF Operation with Cooking Button

In main operation screen, If cooking button is
pressed for 3 seconds, then cooking time (Timer) is
started and cooking time active led becomes active.
While cooking time (Timer) continues if cooking
button is pressed for 3 seconds, cooking time (Timer)
is finished and cooking time active led lights off.
If button protection parameter

= 4 cooking time

(Timer) ON/OFF operation is performed when

button is pressed.

Summary of Contents for ESM-7311-H

Page 1: ...ture control Adjustable temperature offset Set value low limit and set value high limit boundaries Relay or SSR driver output Adjustable cooking time from front panel Temperature control with manual heating function Alarm parameters Adjustable internal buzzer according to cooking time probe defect and alarm status Button protection Password protection for programming section Digital Input Cooking ...

Page 2: ... are explained Also in these sections there are warnings to prevent serious injury while doing the physical and electrical mounting or using the device Explanation of the symbols which are used in these sections are given below CONTENTS Installation Operation and Parameters In this section user interface of the device accessing to the parameters description of the parameters are explained a c i Th...

Page 3: ...LAY OUTPUT CONNECTION 3 7 2 SSR DRIVER OUTPUT CONNECTION 4 2 CHANGING AND SAVING SET VALUE 4 3 CHANGING AND SAVING COOKING TIME TÝMER PARAMETER 4 4 PROGRAMMING MODE PARAMETER LIST 4 5 4 5 1 4 5 2 4 6 OPERATION GRAPHICS OF ESM 7311 H HEATING CONTROLLER 4 7 EASY ACCESS DIAGRAM OF PROGRAMMING SECTION PARAMETERS 4 8 ENTERING TO THE PROGRAMMING MODE CHANGING AND SAVING PARAMETERS 2 INSTALLATION 3 ELECT...

Page 4: ...ssued Authorized Signature 2006 95 EC The Low Voltage Directive 2004 108 EC The Electromagnetic Compatibility Directive has been designed and manufactured to the following specifications EN 61000 6 4 2007 EMC Generic Emission Standard for Industrial Environments EN 61000 6 2 2005 EMC Generic Immunity Standard for Industrial Environments EN 61010 1 2001 Safety Requirements for electrical equipment ...

Page 5: ...g Ovens Incubators Storages Etc Petro Chemistry Textile Automative Machine Production Industries etc Air Conditioning ESM 7311 H Standard Control Output Alarm Output Output 1 Relay Output Control Output Alarm Output Heating Function ON OFF Operation Temperature Sensor Input Power Supply Input Cooking Time Timer Start Stop Input Digital Input Standart 230 V 15 50 60Hz V Optional Supply Input 115 V ...

Page 6: ...loth dampened in ethyl alcohol or water to clean the external plastic case A BC D E FG HI U V W Z 0 00 1 0 0 1 Relay Output resistive load 10 A 250 V 1 NO 1NC V Output 1 E Supply Voltage A Input Type BC Scale C ESM 7311H 35x77 DIN Size 24V 15 50 60Hz V 3 115V 15 50 60Hz V 4 230V 15 50 60Hz V 5 12V 15 50 60Hz W 6 9 Customer 2 SSR Driver Output Maximum 15 mA 5 V Z 00 12 05 09 J Fe CuNi IEC584 1 ITS9...

Page 7: ...power off until all of the wiring is completed so that electric shock and trouble with the unit can be prevented Never attempt to disassemble modify or repair this unit Tampering with the unit may results in malfunction electric shock or fire Do not use the unit in combustible or explosive gaseous atmospheres During the equipment is putted in hole on the metal panel while mechanical installation s...

Page 8: ... ESM 7311 H Heating Controller 77 mm 3 03 inch 35 mm 1 38 inch Heating Controller ESM 7311 H C SV PR Maximum 15 0 59 inch mm 58 5 mm 2 30 inch 4 mm 0 16 inch 8 Mounting Clamp Front Panel IP65 protection NEMA 4X Panel surface maximum thickness 15 mm 0 59 inch ...

Page 9: ...2 3 Panel Cut Out 98 mm 3 82 inch min 56 mm 3 82 inch min 29 mm 1 14 inch 71 mm 2 79 inch 9 ...

Page 10: ...ng Up to 2000 m Operating Conditions Forbidden Conditions Corrosive atmosphere Explosive atmosphere Home applications The unit is only for industrial applications 2 4 Environmental Ratings 2 5 Panel Mounting c c During installation into a metal panel care should be taken to avoid injury from metal burrs which might be present The equipment can loosen from vibration and become dislodged if installa...

Page 11: ...holes that located left and right sides of the device and make the unit completely immobile within the panel 2 6 Installation Fixing Clamp 2 7 Removing from the Panel c c Before starting to remove the unit from panel power off the unit and the related system Montage of the unit to a system must be done with it s own fixing clamps Do not do the montage of the device with inappropriate fixing clamps...

Page 12: ... set according to the system s needs Only qualified personnel and technicians should work on this equipment This equipment contains internal circuits with voltage dangerous to human life There is severe danger for human life in the case of unauthorized intervention Be sure to use the rated power supply voltage to protect the unit against damage and to prevent failure Keep the power off until all o...

Page 13: ...PTC PT 100 or PT 1000 Relay or SSR Driver Output a Supply Voltage Input It must be determined in order 12 V 15 50 60 Hz 1 5 W VA CAT II P N 7311 H ESM Y c OUTPUT NO NC C 10 A 250 V V TC PTC PT 100 PT 1000 1 2 3 4 5 6 7 8 9 10 11 12 For SSr Output L N L N DIGITAL INPUT Cooking Time Timer Start Stop Input Supply Voltage Input It must be determined in order 230 VA 115 VA VA V 15 50 60 Hz 1 5 V 15 50 ...

Page 14: ...ce input Supply Voltage Input and Relay Output 12V W 2 P N ESM 7311 H 5 05 0 1 00 00 1 0 0 0 Y ca L N OUTPUT 230 V 15 50 60Hz 1 5VA V 3 4 1 5 NO NC C 10A 250V V 6 7 8 9 10 11 12 CAT II J Type TC 0 to 800 C Scale DIGITAL INPUT 2 P N ESM 7311 H 6 05 0 1 00 00 1 0 0 0 ca OUTPUT 12 V 15 50 60Hz 1 5VA W 3 4 1 5 NO NC C 10A 250V V 6 7 8 9 10 11 12 CAT II L N J Type TC 0 to 800 C Scale DIGITAL INPUT ...

Page 15: ...Supply voltage range must be determined in order While installing the unit supply voltage range must be controlled and appropriate supply voltage must be applied to the unit Controlling prevents damages in unit and system and possible accidents as a result of incorrect supply voltage There is no power supply switch or fuse on the device So a power supply switch and a fuse must be added to the supp...

Page 16: ...thermocouple used If present the shield must be connected to a proper ground i Input resistance is greater than 10M W i 10 3 5 2 PTC and NTC Connection PTC 12 11 10 WHITE RED 3 5 3 PT 100 and PT 1000 Connection PT 100 i 12 11 10 PT 1000 12 11 10 Input resistance is greater than 10M W i Input resistance is greater than 10M W i Pay attention the cable colours of PTC probe while doing the PTC probe c...

Page 17: ... Output 2000V V 2000V V 2000V V 2000V V 2000 ESM V For 7311 H 5 500V For ESM 7311 H 3 V V 1 2 3 1 2 11 Supply Voltage Input 9 10 Ground 12 Output 1 Relay Output 1 2 3 1 2 Analog Inputs 11 Optional SSR Driver Output 2000V V 2000V V 1 2 3 1 2 11 Galvanic Isolation Test Values for the devices with 12 V Supply voltage input W 7 8 7 8 Digital Inputs 7 2000 V V 7 8 8 Digital nputs I ...

Page 18: ...Control Element SSR 2 Device L N 1 Fuses must be selected according to the application c c 5 V Max 15mA Z 3 7 Output Connections Fuses must be selected according to the application c Device 1 L N 2 Max A T Fuse 10 V NC C NO 3 7 1 Relay Output Connection 3 c Load ...

Page 19: ...become 10 if increment or decrement button is pressed for 10 seconds continuously increment and decrement number become 100 Heating Controller ESM 7311 H C SV PR 19 Led indication of Output is active Cooking Time Active and Temperature Control Delay Active Led It is used to decrease the value and silence the buzzer Note 1 It is used to increase the value and access to the parameter in programming ...

Page 20: ...e led starts to blink Change the cooking time with increment and decrement buttons Press Set button for saving the cooking time Cooking time is saved cooking time active led lights off main operation screen is shown If no operation is performed in cooking time enter mode and set value enter mode for 20 seconds device turns to main operation screen automatically i 20 SET value changes according to ...

Page 21: ...lue is tried to keep equal to set value by opening or closing the last control element ON OFF controlled system temperature value oscillates continuously Temperature value s oscillation period or amplitude around set value changes according to controlled system For reducing oscillation period of temperature value a threshold zone is formed below or around set value and this zone is named hysteresi...

Page 22: ...s Temperature Controlling Continuity Selection Parameter Temperature controlling can be continues or stopped according to the selection This parameter can be observed if cooking time Timer is 1 Default 0 Continuous Operation Temperature control starts after the temperature control starting delay at power on is expired and continues If buzzer function selection parameter Is 1 or 4 at the end of the...

Page 23: ...Timer and set value can not be changed Cooking ON OFF operation is performed when button is pressed 7 8 DIGITAL INPUT K When K switch that is connected to the cooking time start stop input getting closed condition cooking time Timer is started and cooking time active led becomes active While cooking time Timer continues if K switch getting open condition cooking time Timer is finished and cooking ...

Page 24: ...e Time Time Time Buzzer is Active Cooking Button starts time 2 When cooking time parameter 1 if selection of temperature control and starting the cooking time parameter 1 Temperature control starts at power on Cooking time Timer can be started by pressing cooking ON OFF button or when is selected cooking time start stop input is getting closed condition Continuous Operation Interrupted Operation P...

Page 25: ... Active Temperature Control is Active Temperature Control is Active Time Time Time Buzzer is Active Cooking Button starts time Cooking Button starts time Buzzer is Active Cooking Button starts time Cooking Button starts time Time Time Time Time Temperature control starts with cooking ON OFF button or when cooking time start stop input is getting closed condition Power Process Set C Process Output ...

Page 26: ...lection of Temperature Control and Starting the Cooking Time Cooking Time Starting Conditions Parameter Temperature Controlling Continuity Selection Temperature Alarm Function Selection C SV PR C SV PR C SV PR C SV PR C SV PR C SV PR C SV PR Maximum Alarm Alarm Delay Alarm Delay at Power On Buzzer Function Selection Buzzer is Active During this time Button Protection Programming Mode Accessing Pas...

Page 27: ...ing to the password entering screen Enter programming mode accessing password with increment and decrement buttons Note 2 Parameters can be observed by pressing SET OK button in password entering screen without entering the programming mode entering password But parameters can not be changed Password Entering Screen Press SET OK button for accessing to the parameters C SV PR C SV PR C SV PR Hyster...

Page 28: ... the parameter Press set button for accessing to the next parameter Minimum Set Value Parameter 28 Other Programming mode parameters can be accessed with the same method explained above observed and changed i If no operation is performed in programming mode for 20 seconds device turns to main operation screen automatically i Minimum Set Value Minimum Set Value Minimum Set Value Parameter Programmi...

Page 29: ...rature is above 50 C value on the screen starts to blink Also buzzer function selection parameter is 2 or 4 then internal buzzer is on Example 1 If alarm function selection parameter In programming section is 1 Absolute alarm and minimum alarm parameter is 20 When temperature is less than 20 then internal buzzer is on C value on the screen starts to blink Also if buzzer function selection paramete...

Page 30: ... 29 mm Ip65 at front IP20 at rear Approximately 0 20 Kg Standard indoor at an altitude of less than 2000 meters with none condensing humidity 40 C to 85 C 0 C to 50 C 90 max None condensing Fixed installation II II office or workplace none conductive pollution Continuous V 15 50 60 Hz 1 5 V 15 50 60 Hz 1 5 24 V 15 50 60 Hz 1 5 V 15 10 50 60 Hz 1 5 V 15 50 60 Hz 1 5 NTC PTC TC RTD NTC 10 k 25 C PTC...

Reviews: