8
Display Function Selection Parameter ( Default = 0 )
In main operation screen displayed process value is determined with this
parameter. It can be adjusted from 0 to 2
The measurement process value is shown on the display
The minimum measurement process value is shown
continuously on the display
The maximum measurement process value is shown
continuously on the display
Decimal Point Position Parameter ( Default = 0 )
Decimal point position is determined with this parameter.
It can be adjusted from 0 to 3
No point.
0.0
0.00
0.000
Low Reading Adjustment Value Parameter ( Default = -1999 )
It defines minimum value for dual point reading adjustment
ıt can be adjusted -1999 to (
-1)
Up Reading Adjustment Value Parameter( Default = 9999 )
It defines maximum value for dual point reading adjustment
ıt can be adjusted (
+1) to 9999
Reading Adjustment Selection Parameter ( Default = 0)
It defines which reading adjustment type is active. It can be adjusted from 0 to 1
Selected process input type is read according to the standard
reading adjustment.
Selected process input type is read according to the user reading
adjustment.
User Reading Adjustment Low Limit Analogue Value Parameter
Please refer to section 6.
In this parameter, the equivalent voltage or current for low reading adjustment
value
parameter is determined.(
)
User Reading Adjustment Up Limit Analogue Value Parameter
Please refer to section 6.
In this parameter, the equivalent voltage or current for up reading adjustment
value
parameter is determined. (
)
and
parameters are observed if reading adjustment selection parameter
= 1, otherwise these parameters are can not be observed.
Alarm Hysteresis Parameter ( Default = 0)
Alarm hysteresis value.
It can be adjusted from 0 to (
-
) / 2
Alarm Type Selection Parameter ( Default = 1)
Proses High Alarm
Proses Low Alarm
Alarm On Delay Time Parameter ( Default = 0)
It can be adjusted from 0 to 99 minutes.
5.1 Programming Mode Parameter List
ENGLISH