5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-4220-A  Rev.9  P. 1 / 8

INSTRUCTION MANUAL

BEFORE USE ....

Thank you for choosing M-System.  Before use, please check 
contents of the package you received as outlined below.
If you have any problems or questions with the product, 
please contact M-System’s Sales Office or representatives.

 

PACKAGE INCLUDES:

Loop Powered Indicator ......................................................(1)
Mounting screws .................................................................(4)
Unit label ...................................................................(1) sheet
Mounting bracket assembly (optional)
  Mounting bracket ..............................................................(1)
  M10 U-bolt .........................................................................(2)
  Nut for M10 .......................................................................(4)
  Spring washer for M10 .....................................................(4)
Cable glands (TIIS explosion-proof approval option) ........(2) 
Stopping plug (TIIS explosion-proof approval option) ......(1)

 

MODEL NO.

Confirm Model No. marking on the product to be exactly 
what you ordered.

 

INSTRUCTION MANUAL

This manual describes necessary points of caution when 
you use this product, including installation, connection and 
basic maintenance procedures.
When using this product in potentially explosive atmos-
phere or hazardous (classified) location, you have to follow 
the safety procedure to install it.  Please refer to “SAFE IN-
STALLATION MANUAL” for each type of certification.

POINTS OF CAUTION

 

CONFORMITY WITH EU DIRECTIVES

• The actual installation environments such as panel con-

figurations, connected devices, connected wires, may af-
fect the protection level of this unit when it is integrated 
in a panel system.  The user may have to review the CE 
requirements in regard to the whole system and employ 
additional protective measures to ensure the CE conform-
ity.

 

GENERAL PRECAUTIONS

• Before you remove the module, turn off the input signal 

for safety.

 

ENVIRONMENT

• Do not install the module where it is subjected to con-

tinuous vibration.  Do not subject the module to physical 
impact.

• Environmental (non-hazardous location) temperature 

must be within -40 to +85°C (-40 to +185°F) with relative 
humidity within 0 to 95% RH in order to ensure adequate 
life span and operation.

• Seal unused electrical wiring conduits.
• For use in a hazardous location, be sure that the envi-

ronmental temperature is within the temperature class 
required for the area.

 

WIRING

• Do not install cables close to noise sources (relay drive 

cable, high frequency line, etc.).

• Do not bind these cables together with those in which 

noises are present.  Do not install them in the same duct.

• When the unit is used in an environment where induc-

tive noise interference is expected, ground the earthing 
terminal.

 

AND ....

• The module is designed to function as soon as input sig-

nal is supplied, however, a warm up for 10 minutes is re-
quired for satisfying complete performance described in 
the data sheet.

4-DIGIT LOOP POWERED INDICATOR

(outdoor enclosure, intrinsically safe/explosion-proof)

MODEL

6DV-B/6DVI-B

Summary of Contents for 6DV-B

Page 1: ...igurations connected devices connected wires may af fect the protection level of this unit when it is integrated in a panel system The user may have to review the CE requirements in regard to the whol...

Page 2: ...op Wiring Conduit Case Internal Earthing Screw Internal Earthing Screw External Earthing Screw Terminal Block Screw Cover Indicator Specifications top Wiring Conduit Case External Earthing Screw Screw...

Page 3: ...or to increase parameter values How to Reset All Parameters to the Factory Setting Turn off the power supply to the module In pressing all the three control buttons at once turn it on When a message a...

Page 4: ...Safe Installation Manual WITHOUT TERMINAL BLOCK 1 Loosen the screws on top of the indicator and separate the indicator module from the case 2 Fasten wires to terminals at the rear side of the indicato...

Page 5: ...EXT UP LED Display Internal Bridge 1 2 4 3 9 10 12 11 9 10 12 11 WITH TERMINAL BLOCK Two wire Transmitter Two wire Transmitter 1 Non Hazardous Location Hazardous Location Safety Barrier Power Source P...

Page 6: ...nstalled for the intrinsic safety The safety barrier must meet the Ex data of this unit and must be approved for the hazardous location In order to use a two wire transmitter etc in the TIIS intrinsic...

Page 7: ...et a four digit number to protect the user s configurations MENU MODE is available only when the code is entered The lockout is canceled when is set ENTR ESC The scaled value for the nth input is set...

Page 8: ...of effective digits in this case is reduced by 1 digit compared from the 3 decimal places Select appropriately for the application Refer to Program ming Procedure for how to choose decimal point posi...