![background image](http://html1.mh-extra.com/html/m-system/6dv-b/6dv-b_instruction-manual_3135228004.webp)
6DV-B / 6DVI-B
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-4220-A Rev.9 P. 4 / 8
INSTALLATION
■
MOUNTING THE ENCLOSURE ON A PIPE
■
MOUNTING THE ENCLOSURE ON A WALL
■
MOUNTING DIRECTION
The LED indicator can be mounted in two different direc-
tions in relation to the position of the external earthing
screw.
A
B
TERMINAL CONNECTION
Warning!
For use in a hazardous location, refer to “Installation Diagram”
in the “Safe Installation Manual.”
■
WITHOUT TERMINAL BLOCK
1) Loosen the screws on top of the indicator and separate
the indicator module from the case.
2) Fasten wires to terminals at the rear side of the indicator.
Applicable wire size: 0.14 to 1.5mm
2
(AWG26 to 16)
Stripped length: 6 mm (0.27”)
Recommended pin terminal: Phoenix Contact AI0,25-6BU
3) Put the indicator module back inside the case and tighten
with the screws. (torque: 0.8 N·m)
■
WITH TERMINAL BLOCK
1) Loosen the screw on the left side of the indicator and
extract the indicator module from the case.
2) Fasten wires to terminal block. (torque: 0.5 N·m)
3) Put the indicator module back inside the case and tighten
with the screw. (torque: 0.8 N·m)