12
RefRIgeRAnT pROCeSSIng
Condenser
Wall Unit
pairing
Line Charge
per foot
factory
Charge
S1Cv9000
WlHv09
.25 oz./ft 23 g/m)
39.5oz (1120g)
S1Cv2000
WlHv12
.25 oz./ft 23 g/m)
39.5oz (1120g)
S1Cv8000
WlHv18
.64 oz./ft 59 g/m)
54.0oz (1531g)
S1Cv4000
WlHv24
.64 oz./ft (59 g/m)
54.0oz (1531g)
S1Cv3000
WlHv30
.64 oz./ft (59 g/m)
90.0oz (2551g)
S1Cv6000
WlHv36
.64 oz./ft (59 g/m)
90.0oz (2551g)
S1Hv9000
WlHv09
.25 oz./ft (23 g/m)
39.5oz (1120g)
S1Hv2000
WlHv12
.25 oz./ft 23 g/m)
39.5oz (1120g)
S1Hv8000
WlHv18
.64 oz./ft (59 g/m)
54.0oz (1531g)
S1Hv4000
WlHv24
.64 oz./ft (59 g/m)
54.0oz (1531g)
S1Hv3000
WlHv30
.64 oz./ft (59 g/m)
90.0oz (2551g)
S1Hv6000
WlHv36
.64 oz./ft (59 g/m)
90.0oz (2551g)
Use following example to find charge adjustment and
system charge for any air handles and tubing length.
line Adjustment = (line Charge/FT) x line length
System Total = Factory line Adjustment
Round to nearest ounce and allow for gauges and hoses.
Table 2 - S1CV / S1HV R410A Refrigerant
Charge Table