background image

35

electric Heat Applications

Units with electric heat utilize control relay located on the 

air handlers control board in the control box.

Auto-reset limit switch located on heater end plate or 

on heater assembly interrupts power to heater should 

overheat condition occur. 

Each electric heat assembly is also equipped with one-time 

fuse link. Should electric heat temperatures rise above auto 

resetting limit switch, non-resetting, one-time fuse link 

opens and heater remains off. To restart, new fuse link is 

required. 

 

 

 

 

 

 

             5 kw = 22.3 Amps 

          

 

             3 kw = 13.5 Amps 

 

 

 

        

     

Units With Condensate pumps

EMI air handlers are available with optional condensate 

pump. Condensate pumps are recommended when it is not 

possible to gravity drain condensate from indoor unit. 

Maximum lift for pumps will vary. Consult pump 

instructions for maximum lift.

Condensate generated by air handlers will collect in pump’s 

reservoir.

• When water level is high enough, pump motor 

energizes clearing water from the reservoir. 

• If water exceeds either drain pan upper limit or 

condensate pump reservoir's upper limit, compressor 

shuts down, preventing generation of additional 

condensate.

Interconnect Wiring

See “Electrical Wiring” on page 13 for interconnect wiring 

diagrams, both unit mounted and optional wired wall 

thermostat. 

 

 

 

Checking Voltage

 can be accomplished at either indoor or 

outdoor unit.   

 

 

 

 

24v transformer located in indoor air handler unit provides 

low volt control power to both indoor air handler and 

outdoor condenser between SC and 24vDC(-) terminals. 

This is DC voltage use proper scale on meter.   

 

    

Cooling

EMI heat pump systems utilize Reversing valve energized 

in Cooling mode and de-energized in Heating mode.  When 

24 volts 

AC

 exists between Rv and Rv (either indoors or 

outdoors) system is in cooling mode.  As long as system 

is in Cooling mode, 24 volt power exists between Rv and 

Rv terminals.  When zero (0) volts AC exists between Rv 

and Rv, system is either in Heating mode or there is open 

circuit to reversing valve in Cooling mode. 

• EMI heat pump systems utilize a reversing valve is 

that is energized in the cooling mode. 

• It should remain energized constantly as long as the 

indoor unit or thermostat remains in cooling mode. 

Heating

Heat pump systems accommodate two-stage heating when 

optional electric heater is present in combination with heat 

pump condenser. First stage consists of heat pump alone 

and second stage consists of heat pump and electric heat 

both operating simultaneously. 

To verify heating operation, place Amp meter on indoor 

incoming power line.  Mode should be heating, with 

temperature set 1° above current room temperature.     

      

•  Compressor starts and delivers heat to conditioned 

space, Amp meter registers fraction of Amp (blower 

motor only).

• Set temperature 2° continues to run delivering heat to 

conditioned space, and electric heat energizes.

Amp meter reads 7 to  twenty 23 Amps at 230 volts 

AC 

depending on electric heater capacity and line voltage 

supplied to air handler.   

 

TROUbLeSHOOTIng

Summary of Contents for E Verter WLHV09

Page 1: ...ominal Capacities WLHV09 WLHV12 WLHV18 WLHV24 WLHV30 WLHV36 Units 9 000 12 000 18 000 24 000 29 800 33 400 Btuh COOL 2 6 3 5 5 3 7 0 8 7 9 8 kW 8 800 10 000 18 000 21 000 26 000 26 400 Btuh HEAT 2 6 2...

Page 2: ...ontrol Operation 30 Controller Features 31 Controller Fault Conditions 32 Maintenance 33 Troubleshooting 34 Frequently Asked Questions 36 Specifications And Dimensions 37 Wlhv System Options 38 Test U...

Page 3: ...to verify unit has been installed correctly Run unit for one complete cycle to verify proper function To obtain technical service or warranty assistance during or after installation contact your loca...

Page 4: ...grounded electrical supply Do not fail to properly ground this unit Check the rating plate on the unit before installation to verify voltage shown is same as electric supply to the unit Rating plate...

Page 5: ...4mm 7 5 16 Model A B C D E Shipping weight Depth in mm Height in mm Length in mm Mounting bracket clearance in mm Tubing access clearance in mm Pounds kg WLHV09 WLHV12 9 7 8 251 15 387 38 978 24 610 2...

Page 6: ...air handlers freeze up Test operation Allows testing after installation Runs at rate condition speeds for set ups and charging Non volatile back up memory maintains control settings for indefinite per...

Page 7: ...truction See Figure 2 Site Preparation Mount unit plumb and level to vertical surface to prevent unit vibration and noise Mount unit directly to smooth surface such as wallboard or similar material Mo...

Page 8: ...Figure 3 Page 7 2 Determine appropriate hole size Cut through the wall 3 Use supplied wall bracket See Figure 4 4 Secure bracket to wall with wood screws or masonry anchors Insure bracket is mounted...

Page 9: ...contact with sharp edges Wrap refrigeration valves with wet rag heat sink to protect valves while brazing See Figure 9 Page 10 DO NOT use suction line size larger than condenser service valve connecti...

Page 10: ...d can be made from scrap metal 4 Braze tubing into fittings 5 Install all panels removed to this point Panels are required for proper air flow 6 Both lines of line set must be insulated entire length...

Page 11: ...systems require field charge adjustments Refer to Refrigerant Charge Tables for proper weight charge Charge with dial a charge or weighed in with scale NOTICE It is illegal to discharge refrigerant in...

Page 12: ...V9000 WLHV09 25 oz ft 23 g m 39 5oz 1120g S1HV2000 WLHV12 25 oz ft 23 g m 39 5oz 1120g S1HV8000 WLHV18 64 oz ft 59 g m 54 0oz 1531g S1HV4000 WLHV24 64 oz ft 59 g m 54 0oz 1531g S1HV3000 WLHV30 64 oz f...

Page 13: ...to expose control box Locate wiring diagram on inside of end cap See Figure 17 Units rated 208 230V primary side of transformer is factory wired for 230V For 208V power supply transformer tap must be...

Page 14: ...voltage interconnecting wires between indoor and outdoor units Each wire COM1 COM2 SC 24 VDC RV and RV should connect to same named terminal indoor and outdoor See Figure 19 and Figure 20 RV signal is...

Page 15: ...f 2 cables or 30 feet of interconnect cable Do not slice cables together on site Hand held remote is required to enter Test Mode Wired wall thermostat has limited control capabilities for technician t...

Page 16: ...16 Electrical Wiring Figure 22 Wall Mounted Thermostat Configuration Cooling Only Figure 23 Wall Mounted Thermostat Configuration Heat Pump...

Page 17: ...en right end cap using Phillip head screw 3 Replace and tighten remaining screws across bottom panel 4 Replace left end cap See Figure 25 5 Tighten screw on right when end cap is properly seated 6 Tig...

Page 18: ...enser mounted Electronic Expansion Valve EXV continuously adjusts refrigerant flow to maintain 15 F 8 3 C superheat at compressor Expanded refrigerant froth travels through small diameter tube of line...

Page 19: ...inimum compressor run times and outdoor coil defrost are in place whenever compressor runs in Heating Mode Condenser mounted Electronic Expansion Valve EXV continuously adjusts refrigerant flow to mai...

Page 20: ...n on page 29 for setup and operation when using wall thermostat Unit Operation is dependent on room temperature It may be necessary to warm room before testing unit s cooling abilities Before Starting...

Page 21: ...ing mode press to decrease setting FAN Press to toggle between fan modes High Med Low or Auto PROGRAM Normal operation Press to toggle between manual operation and Pre programmed 7 day run mode Config...

Page 22: ...g mode press to decrease the setting LEFT ARROW Press for previous item selection RIGHT ARROW Press for next item selection FAN Press to toggle between fan modes High Med Low or Auto PROGRAM Normal op...

Page 23: ...7 Day Programming See Table 4 Page 25 to record settings Day of week Mon Tue Wed Thu Fri Sat Sun Louver is closed when fan is off Period of day Morning Day Evening Night Periods provide four time sett...

Page 24: ...h room temperature at or above 71 F heating is on with room temperature at or below 65 F Check filter time 05 F Lt 2 5 7 10 12 250 hours 500 hours 750 hours 1000 hours 1250 hours 10 Set this time for...

Page 25: ...Temp Time Temp Time Temp Time Temp Monday Tuesday Wednes day Thursday Friday Saturday Sunday To copy the settings from any day to the entire week 1 Select the day to be copied 2 Simultaneously press...

Page 26: ...remote while in hibernate mode Remote returns to mode it was in prior to entering hibernate mode Power Pressing POWER button momentarily switches unit either on or off 1 OFF mode LCD displays time of...

Page 27: ...ut Electric Heat Heat Pump Unit Outdoors EMI heat pumps are intended to operate with indoor air handler with optional electric heat If indoor air handler without electric heat is matched with heat pum...

Page 28: ...inues to boost room temperature back up to setpoint temperature If room temperature rises above setpoint temperature by 2 degrees heating stops and cooling continues to bring room temperature back dow...

Page 29: ...ry or Fan modes 3 Pressing PROGRAM button momentarily enters or exits Pre Programmed Run mode 4 The word PROGRAM appears in LCD display 5 The setpoint changes to programmed setting at selected time To...

Page 30: ...es not start for at least 3 minutes short cycle protection Electric heat Operation Optional wired wall controller operation with electric heat control must be configured properly Remote Thermostat ON...

Page 31: ...eat pump mode Minimum Run Time Minimum on time prevents compressor or heat source from cycling off prematurely Minimum ON time for both compressor and electric heat is 2 minutes Drain Pan Sensor Drain...

Page 32: ...On 10 Condenser coil temperature too high or low Check system air flow and sensor On 11 Suction temperature too high or low Check system air flow and module On 12 Outdoors ambient temperature too high...

Page 33: ...g 3 Replace filters clips and front grille before operating unit See Figure 33 WARNING DO NOT operate unit without filter and front grille in place 4 Vacuum dust from return air grille and coil surfac...

Page 34: ...low volt interconnecting wires between indoor unit outdoor and optional thermostat Air handlers with unit mounted controls require contacts wired to same name indoors and outdoors COM1 COM2 SC and 24...

Page 35: ...r handler unit provides low volt control power to both indoor air handler and outdoor condenser between SC and 24VDC terminals This is DC voltage use proper scale on meter Cooling EMI heat pump system...

Page 36: ...eeze up does occur check the following Check freeze sensor is located in lowest part of coil Generally this is where freeze up begins Check freeze sensor is inserted fully and snug in coil fin If not...

Page 37: ...nit Specifications and Dimensions Table 7 WLHV Interconnecting Line Sizes MODEL VOLTS HZ PH FAN RLA HP HEATER K W AMPS TOTAL AMPS MIN VOLT M C A HACR BRKR WLHV 09 12 208 230 60 1 0 34 0 02 0 34 197 0...

Page 38: ...0 67 9 0 R410A Table 9 Heat Pump System With Wall Units Condenser Wall Units Cooling Btuh Heating Btuh SEER HSPF SHR EER COP Ref S1HV9000 WLHV09 9 000 8 800 16 7 8 2 0 75 13 5 3 2 R410A S1HV2000 WLHV1...

Page 39: ...Air handlers Entering Air DB Air handlers Entering Air WB Air handlers Leaving Air DB Air handlers Leaving Air WB Outdoor Section Entering Air Leaving Air Temperature Split Operating Pressures Compres...

Page 40: ...Phone 1 800 228 9364 Fax 1 800 232 9364 2201 Dwyer Avenue Utica NY 13501...

Reviews: