3. Operation and Display
EM-GU User’s Manual
8
3.2 Description of Function Parameters
F00
Soft Starter Rated Current
Description:
The default value of the parameter depends on the model, this parameter is read only and
can not be modified.
F01
Soft Starter Rated Voltage
Description: The default value of the parameter depends on the model, this parameter is read only and
can not be modified.
F02
Motor Rated Current
Description: The default value of the parameter depends on the model.
Match the starter to the rated current of the connected motor. Set the rated current is depend on the
motor nameplate
F03
Control Mode
Range: 0~7 (Default: 3)
Option: 0: Disable
1: Keypad
2: Terminal
3: Key+Term (Both keypad control and terminal control are valid)
4: Communication
5: Key+Comm (Both keypad control and communication control are valid)
6: Term+Comm (Both terminal control and communication control are valid)
7: Key+Term+Comm (Keypad control, terminal control, communication control all valid)
F04
Start Mode
Range: 0~2 (Default: 0)
Option: 0: Voltage Ramp
1: Current Limit
2: Torque Start
Select soft starter start mode.
F05
CLS Current Limited
Range: 50%~600% (Default: 300%)
Description: Set the current limit value for current-limited starting, as a percentage of motor rated
current.
F06
Initial Start Voltage
Range: 30%~80% (Default: 35%)
Description: Set initial start voltage for Voltage ramp starting.
F07
VRS Start Time
Range: 1s~120s (Default: 15s)
Description: Set start time for voltage ramp starting(Invalid for current limit starting)
F08
Stay Voltage
Range: 60%~85% (Default: 65%)
Description: Set stay voltage, valid for torque starting.
F09
Initial Ramp Time
Range: 1s~10s (Default: 5s)
Description: Set initial acceleration time, valid for torque starting.
F10
Stay Time
Range: 1s~120s (Default: 10s)