B - 74
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0
Appendix B
•
Vission 20/20 Application Procedures
17
N51:1
40052
Oil Pump
INT
0 = OFF, 1 = ON Read
18
N51:2
40053
Capacity Increase
ENUM
Read
19
N51:3
40054
Capacity Decrease
ENUM
Read
20
N51:4
40055
Volume Increase
INT
0 = OFF, 1 = ON Read
21
N51:5
40056
Volume Decrease
INT
0 = OFF, 1 = ON
Read
22
N51:6
40057
Oil Separator Heater
INT
0 = OFF, 1 = ON Read
23
N51:7
40058
Trip
INT
0= OFF, 1=ON
(ON when no
Trip)
Read
24
N51:8
40059
Slide Valve Setpoint #1
INT
0 = OFF, 1 = ON
Read
25
N51:9
40060
Slide Valve Setpoint #2
INT
0 = OFF, 1 = ON Read
26
N51:10
40061
Alarm
INT
0 = OFF, 1 = ON
(ON when no
Alarm)
Read
27
N51:11
40062
Spare
INT
0 = OFF, 1 = ON Read
28
N51:12
40063
Liquid Injection Solenoid #1
INT
0 = OFF, 1 = ON Read
29
N51:13
40064
Liquid Injection Solenoid #2
INT
0 = OFF, 1 = ON Read
30
N51:14
40065
Remote Enabled
INT
0 = OFF, 1 = ON Read
31
N51:15
40066
Emergency Output
INT
0 = OFF, 1 = ON Read
32
N51:16
40067
Condenser Step #1
INT
0 = OFF, 1 = ON Read
33
N51:17
40068
Condenser Step #2
INT
0 = OFF, 1 = ON Read
34
N51:18
40069
Condenser Step #3
INT
0 = OFF, 1 = ON Read
35
N51:19
40070
Condenser Step #4
INT
0 = OFF, 1 = ON Read
36
N51:20
40071
Auxiliary Output #1
INT
0 = OFF, 1 = ON Read
37
N51:21
40072
Auxiliary Output #2
INT
0 = OFF, 1 = ON Read
38
N51:22
40073
Auxiliary Output #3
INT
0 = OFF, 1 = ON Read
39
N51:23
40074
Auxiliary Output #4
INT
0 = OFF, 1 = ON Read
Analog Inputs
40
N52:0
40100
Motor Amps
F-INT
Read
41
N52:1
40101
Suction Pressure
F-INT
Read
42
N52:2
40102
Discharge Pressure
F-INT
Read
43
N52:3
40103
Oil Filter Inlet Pressure
F-INT
Read
44
N52:4
40104
Oil Manifold Pressure
F-INT
Read
45
N52:5
40105
Economizer Pressure
F-INT
Read
46
N52:6
40106
Capacity Slide %
F-INT
Read
47
N52:7
40107
Volume Slide %
F-INT
Read
48
N52:8
40108
Suction Temperature
F-INT
Read
49
N52:9
40109
Discharge Temperature
F-INT
Read
50
N52:10
40110
Oil Separator Temperature
F-INT
Read
51
N52:11
40111
Oil Manifold Temperature
F-INT
Read
52
N52:12
40112
Process Temperature
F-INT
Read
53
N52:13
40113
Chiller Inlet Temperature
F-INT
Read
Summary of Contents for Vission 20/20
Page 1: ...Vission 20 20 micro controller Operation and service manual Version 2 0 ...
Page 2: ......
Page 4: ......
Page 6: ......
Page 66: ...8 4 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 76: ...10 8 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 86: ...12 6 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 106: ...15 4 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 1 9 ...
Page 108: ...16 2 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 136: ...21 4 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 146: ...24 4 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 154: ...26 4 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 156: ...A 2 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 158: ...B 2 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 162: ...B 6 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 180: ...B 24 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 204: ...B 48 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 220: ...B 64 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 257: ......