B - 4
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0
Appendix B
•
Vission 20/20 Application Procedures
SETPOINT SELECTION EXAMPLE
The following example is to illustrate the selection of setpoints for the Pulldown feature. The values picked are NOT
representative of actual
fi
eld applications.
Assumptions and Variables:
• Current suction pressure is at 80 psig
• Target suction pressure is 20 psig. (This de
fi
nes a change of 60 psig).
• Time duration allowed to get to setpoint is 10 days (240 hours) of Pulldown time.
• Suction pressure change allowed for each step is 5 psig.
Figure B-1. Pulldown Setpoints
So, for the
fi
rst 20 hours the compressor runs at 75 psig, then for the next 20 hours at 70 psig, then for the next 20
hours at 65 psig, and so forth.
After the 12th step (running at 25 psig), 240 hours will have elapsed, and the new setpoint changes to 20 psig. After
the Pulldown setpoint equals or is less than the control setpoint, the Pulldown feature disables itself.
To calculate the Delay Per Step setpoint:
Number of Pulldown Steps = Delta 60 psig change * 1 step/5 psig = 12 steps
Delay per step = 240 hours / 12 steps = 20 hours/step
Summary of Contents for Vission 20/20
Page 1: ...Vission 20 20 micro controller Operation and service manual Version 2 0 ...
Page 2: ......
Page 4: ......
Page 6: ......
Page 66: ...8 4 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 76: ...10 8 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 86: ...12 6 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 106: ...15 4 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 1 9 ...
Page 108: ...16 2 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 136: ...21 4 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 146: ...24 4 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 154: ...26 4 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 156: ...A 2 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 158: ...B 2 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 162: ...B 6 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 180: ...B 24 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 204: ...B 48 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 220: ...B 64 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 257: ......