Problem
Solution
Vission 20/20 does not boot up, no
lights light on any boards.
Check that 120VAC is run to circuit breaker CB1 located on the terminal
strip. The neutral should be brought to any “N” terminal on the terminal
strip.
Check that circuit breaker CB1’s switch is in the ON position.
Use a voltmeter to insure 120VAC is being applied to the power supply,
located on the door. Check that 120 volts is present at the F1 fuse on the
power supply, located on the front of the door. If all of the above are OK,
the power supply may be bad. To test the power supply, check DC voltages
at the power supply output. If proper voltages are not found at these test
points, the power supply may be faulty.
Vission 20/20 appears to be boot-
ed, lights are lit on the boards, but
no touchscreen display is evident:
Remove power COMPLETELY from the Vission 20/20 and restart the
controller.
WARNING
The inverter board creates a high rms voltage to drive
the backlight - it can exceed 1500VAC. Use extreme
caution and insure that voltage has been removed
from the board before physical inspection. Visually
check cable connections located on the LCD inverter
board. This board is located inside the door on the
LCD touch screen back plane next to the single board
computer. Physically inspect board to insure that
all cable connectors are connected tightly to the
board connectors. If these are inserted correctly,
the problem could be a bad LCD inverter board or a
component failure.
Vission 20/20 boots up but all data
temperatures and pressures are ze-
roed and do not update.
Check analog board jumpers to insure proper node addresses are set up
on all boards. Physically inspect power and communication jumper ca-
bles to insure they are inserted properly and completely. Two LEDs on all
boards show the status of the communications for the board. LED1 is on
when a command is received at the board from the single board computer
(SBC), and LED2 is on when a response is sent from the board to the SBC.
Vission 20/20 Troubleshooting Guide
In the event of a problem with the Vilter Vission 20/20, the help screen, along with your electrical drawings will help
determine the cause.
NOTICE
Before applying power to the Vission 20/20 control
panel, all wiring to the panel should be per the
National Electrical Code (NEC). Speci
fi
cally check for
proper voltage and that the neutral is grounded at
the source. An equipment ground should also be run
to the panel.
Summary of Contents for Vission 20/20
Page 1: ...Vission 20 20 micro controller Operation and service manual Version 2 0 ...
Page 2: ......
Page 4: ......
Page 6: ......
Page 66: ...8 4 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 76: ...10 8 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 86: ...12 6 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 106: ...15 4 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 1 9 ...
Page 108: ...16 2 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 136: ...21 4 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 146: ...24 4 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 154: ...26 4 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 156: ...A 2 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 158: ...B 2 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 162: ...B 6 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 180: ...B 24 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 204: ...B 48 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 220: ...B 64 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 257: ......