5 – 22
Section 5 • Maintenance/Service
HPLD Single Screw Compressor • Installation, Operation and Service Manual • Emerson • 35391HP
Figure 5-29. Gaterotor Ball bearing
Gaterotor Ball Bearing Removal
1. Remove bolts (102.4) from the outer retainer
(102.3), see Figure 5-29.
2. Remove ball bearing outer retainer (102.3).
3. Using a press, remove ball bearings (102.2) from
housing (102.1).
Gaterotor Ball Bearing Installation
1. Install three ball bearings (102.2) in the housing
(102.1) so the first two bearings are back to back,
and the second and third bearings are face to face
(the larger sides of the inner races are placed to-
gether, as shown in Figure 5-29). A light applica-
tion of clean compressor lubricating oil should be
used to ease the installation of the bearings into the
housing.
2. Center the bearing outer retainer (102.3) on hous-
ing (102.1), use Loctite® 242-thread locker and
evenly tighten the bolts (102.4) to the recom-
mended torque value (4 lb-ft), see Figure 5-29.
Back to Back
Arrangement of
Bearings
Face to Face
Arrangement
of Bearings
102.1
102.2
102.3
102.4
Summary of Contents for Vilter VSG128
Page 1: ...HPLD Single Screw Bare Shaft Compressor Installation Operation and Service Manual ...
Page 2: ......
Page 32: ...3 8 Blank HPLD Compressor Unit Installation Operation and Maintenance Manual Emerson 35391HPU ...
Page 68: ...6 4 Blank HPLD Compressor Unit Installation Operation and Maintenance Manual Emerson 35391HPU ...
Page 72: ...7 4 Blank HPLD Compressor Unit Installation Operation and Maintenance Manual Emerson 35391HPU ...
Page 78: ...8 6 Blank HPLD Compressor Unit Installation Operation and Maintenance Manual Emerson 35391HPU ...
Page 83: ......