5 – 7
VSG/VSSG • Installation, Operation and Maintenance Manual •Vilter/Emerson • 35391STG
Section 5 • Maintenance/Service
1. If equipped with dual oil
fi
lters, open inlet shut-off
valve for non-operating oil
fi
lter to put it into opera-
tion, see Figure 5-5.
2. To isolate oil
fi
lter for servicing, close inlet and out-
let shut-off valves for the oil
fi
lter.
NOTE
To reduce unwanted oil splash from a vent or drain
valve, connect a hose to the valve port and direct
the gas and oil into a drain pan.
3. Slowly release pressure in the oil
fi
lter canister by
opening the vent valve. Allow pressures to equalize
to atmosphere.
NOTICE
Dispose of the oil in a appropriate manner following
all Local, State and Federal ordinances regarding the
disposal of used oil.
4. Using an drain pan, open drain valve and allow the
oil to completely drain from the oil
fi
lter canister.
NOTE
Note orientation of components to aid in installation.
5. Remove bolts and nuts securing cover
fl
ange to the
oil
fi
lter canister. Remove cover
fl
ange and spring
plate. Retain spring plate.
6. If equipped with a single oil
fi
lter element, remove
fi
lter element from oil
fi
lter canister.
7. If equipped with dual oil
fi
lter elements, remove
two
fi
lter elements and
fi
lter element centering
piece from oil
fi
lter canister. Retain
fi
lter element
centering piece.
8. Thoroughly clean the oil
fi
lter canister, spring
plate and centering piece. Inspect spring plate and
Figure 5-5. Oil Filter Drain, Vent and Shut-Off Valves
Drain Valve
Inlet Shut-Off Valves
Vent Valve
Drain Valve
Vent Valve
Outlet Shut-Off Valves
centering piece, if damaged, replace as required.
INSTALLATION
NOTE
Ensure oil
fi
lter element on the outlet side is fully
seated on the outlet pipe when installed.
9. If equipped with single oil
fi
lter element, install oil
fi
lter element in canister in orientation noted dur-
ing removal.
10. If equipped with dual oil
fi
lter elements, install two
oil
fi
lter elements and centering piece in orientation
noted during removal.
11. Position spring plate in orientation noted during
removal and install bolts and nuts to secure cover
fl
ange to oil
fi
lter canister.
12. Tighten nuts, see Appendix A.
13. Using dry nitrogen gas, pressurize oil
fi
lter canister
through vent valve and check for leaks.
14. Close the vent valve and drain valve.
15. Open outlet shut-off valve for the oil
fi
lter that is not
in operation.
16. Repeat for second oil
fi
lter, as required.