SM-I/O 24V Protected User Guide
33
Issue Number: 2
www.controltechniques.com
How t
e
S
In
In
P
D
Te
P
In
Figure 6-2 Location of the status LED
Any trip can be initiated by writing the relevant trip number to Pr
10.38
. If any trips
shown as user trips are initiated the trip string is "txxx", where xxx is the trip number.
Trips can be reset after 1.0s if the cause of the trip has been rectified.
A full list of drive trips can be found in the
Unidrive SP User Guide / Commander GP20
User Guide.
6.1.2
Commander SK
The drive retains a log of the last 10 trips that have occurred in Pr
10.20
to Pr
10.29
.
Pr
10.20
is the most recent trip, or the current trip if the drive is in a trip condition, and
Pr
10.29
is the oldest trip. Each time a new trip occurs, all the parameters move down
one, such that the current trip (and time) is stored in Pr
10.20
and the oldest trip is lost
from the bottom of the log.
If any parameter between Pr
10.20
and Pr
10.29
inclusive is read by serial
communications, then the trip number in section 6.3
on page 35 is the value transmitted.
Figure 6-3 Commander SK keypad status modes
Any trip can be initiated by writing the relevant trip number to Pr
10.38
. If any trips
shown as user trips are initiated the trip string is "t0xx", where xx is the trip number.
Trips can be reset after 1.0s if the cause of the trip has been rectified.
A full list of drive trips can be found in the
Commander SK Advanced User Guide.
Status LED
Non flashing:
Normal status
Flashing:
Trip status
M
M
M
Alarm Status
Healthy Status
Trip Status
Status Mode
Drive status = tripped
Trip type = UU (undervolts)
Summary of Contents for SM-I/O 24V Protected
Page 41: ......
Page 42: ...0471 0072 02 ...