
32
SM-I/O 24V Protected User Guide
www.controltechniques.com
Issue Number: 2
6
Diagnostics
If the drive trips, the output is disabled so that the drive stops controlling the motor. The
display indicates that a trip has occurred as shown in Figure 6-1 and Figure 6-3.
Trips are listed in section 6.2
Unidrive SP / Commander GP20 trip descriptions
Commander SK trip descriptions
on page 35 based on the trip
indication shown on the drive display. Refer to Figure 6-1 for Unidrive SP / Commander
GP20 and Figure 6-3 for Commander SK.
If a display is not used on the Unidrive SP / Commander GP20, the drive LED Status
indicator will flash if the drive has tripped. Refer to Figure 6-2.
The trip indication can be read in Pr
10.20
providing a trip number.
6.1
Displaying the trip history
6.1.1
Unidrive SP / Commander GP20
The drive retains a log of the last 10 trips that have occurred in Pr
10.20
to Pr
10.29
and
the corresponding time for each trip in Pr
10.43
to Pr
10.51
. The time of the trip is recorded
from the powered-up clock (if Pr
6.28
= 0) or from the run time clock (if Pr
6.28
= 1).
Pr
10.20
is the most recent trip, or the current trip if the drive is in a trip condition (with
the time of the trip stored in Pr
10.43
). Pr
10.29
is the oldest trip (with the time of the trip
stored in Pr
10.51
). Each time a new trip occurs, all the parameters move down one,
such that the current trip (and time) is stored in Pr
10.20
(and Pr
10.43
) and the oldest
trip (and time) is lost from the bottom of the log.
If any parameter between Pr
10.20
and Pr
10.29
inclusive is read by serial
communications, then the trip number in section 6.2
on page 34 is the value transmitted.
Figure 6-1 Unidrive SP / Commander GP20 keypad status modes
Trip type (UU
= undervolts)
Drive status
= tripped
Trip Status
Alarm Status
Healthy Status
Status Mode
Summary of Contents for SM-I/O 24V Protected
Page 41: ......
Page 42: ...0471 0072 02 ...