Configuration
2.1 LCD display configuration
The 20-segment bar graph is factory calibrated and represents 4–20 mA
directly, but the end points of the LCD display are user-definable. The meter
requires a current between 4 and 20 mA in order to be scaled, but the actual
value of the current is not significant.
2.1.1 Remove the cover
WARNING
Explosions could result in death or serious injury.Do not remove the
transmitter cover in explosive atmospheres when the circuit is live.
Procedure
Unscrew and remove the transparent housing cover from the LCD display
body.
2.1.2 Position the decimal point and select the meter function
Procedure
1. Press the left and right configuration buttons simultaneously and
release them immediately.
2. To move the decimal point to the desired location, press the left
configuration button.
Note
The decimal point wraps around.
3. To scroll through the mode options, press the right configuration
button repeatedly until the meter displays the desired mode (See
Note
The LCD display time-out is approximately 16 seconds. If you do not
press the configuration buttons within 16 seconds, the indicator will
revert to reading the current signal.
Table 2-1: LCD Display Mode Options
Options
Relationship between Input Signal
and Digital Display
L in
Linear
LinF
Linear with five-second filter
February 2019
Quick Start Guide
Quick Start Guide
9
Summary of Contents for Rosemount 751
Page 1: ...Quick Start Guide 00825 0100 4378 Rev AE February 2019 Rosemount 751 Field Signal Indicator ...
Page 18: ...4 Declaration of Conformity Quick Start Guide February 2019 18 Rosemount 751 ...
Page 19: ...February 2019 Quick Start Guide Quick Start Guide 19 ...
Page 20: ...Quick Start Guide February 2019 20 Rosemount 751 ...
Page 22: ...Quick Start Guide February 2019 22 Rosemount 751 ...
Page 23: ...February 2019 Quick Start Guide Quick Start Guide 23 ...