38
Reference Manual
00809-0100-4248, Rev CA
May 2017
5.5
Modbus
®
, EtherNet/IP
™
and OPC mapping
Following is a table of parameters that can be used for Modbus, EtherNet/IP and OPC mapping. These
parameters are used by the Smart Wireless Gateway and can be found in the web interface of the
Gateway. Some of these parameters are analog values and some are discrete, and this is noted in the
description. The Setpoint parameters are used to drive the output channel and for the readback of the
state of the output channel.
Mapping the Rosemount 705 Transmitter parameters
Below is the Gateway screen where the accumulator reset, accumulator state, totalized_volume,
average_flow variables and parameter can be mapped. This is important to understand how to reset the
totalized volume of the device via Modbus, OPC, or EtherNet/IP.
Figure 5-1. Smart Wireless Gateway Modbus Register Map
Table 5-1. Parameters for Modbus, EtherNet/IP, and OPC Mapping
Parameter name
Description
Read/Write
SUPPLY_VOLTAGE
Maps the supply voltage of the device. For
monitoring the health of your power module use
SUPPLY_VOLTAGE_HEALTHY
Read
ELECTRONICS_TEMPERATURE
Maps the electronics temperature
Read
TOTALIZED_VOLUME
Maps the totalized volume the device has measured
Read
AVERAGE_FLOW_RATE
Maps the instantaneous flow rate over that period
of time set by the DD
Read
ACCUMULATOR_RESET
Use this parameter to reset the number of total
counts on the device
Write
ACCUMULATOR_STATE
What is the current totalized value of the device
Read
Summary of Contents for Rosemount 705
Page 2: ......
Page 6: ...vi Reference Manual 00809 0200 4705 Rev AB Contents May 2017 Contents ...
Page 10: ...2 Reference Manual 00809 0200 4705 Rev AB Introduction May 2017 Introduction ...
Page 32: ...28 Reference Manual 00809 0200 4705 Rev AB Commissioning May 2017 Commissioning ...
Page 69: ......