Reference Manual
00809-0100-4248, Rev CA
May 2017
Note
Use Rosemount Wireless LCD display part number: 00753-9004-0002.
Diagnostic button screen 7.2
: Terminal voltage is below the
recommended operating range - if this is a self-operated device,
the power module should be replaced - for line powered devices,
the supply voltage should be increased
Diagnostic button screen 8
: device cannot retrieve information
from the radio in the device - the device may still be operational
and publishing HART data
Diagnostic button screen 9
: Configuration of the transmitter is
invalid such that critical operation of the device may be affected
- check the extended configuration status to identify which
configuration item(s) need to be corrected
Diagnostic button screen 10
: Switch attached to the
transmitter has failed, and valid readings from that switch are no
longer possible - check the switch and switch wiring
connections - check additional status for more detailed
information of the failure source
Diagnostic button screen 11
: Device has not yet received all of
the requested wireless bandwidth needed to operate as
configured
s u p l y
l o w
r a d i o
f a i l u r
c o n f g
f a i l u r
s n s r
f a i l u r
b d W T h
l i m i t d