Quick Installation Guide
00825-0200-4585, Rev AA
January 2009
Flanged Flo-Tap 585 Annubar
14
S
TEP
8
CONTINUED
...
Recommended Installations
Gas Service
Secure the transmitter above the sensor to prevent condensable liquids from collecting in
the impulse piping and the DP cell.
Liquid Service
Secure the transmitter below the sensor to ensure that air will not be introduced into the
impulse piping or the transmitter.
Figure 12. Vertical Line
Figure 13. Horizontal Line
Figure 14. Vertical Line
Figure 15. Horizontal Line
4585_0200_QIG_AA.fm Page 14 Thursday, January 29, 2009 3:05 PM