Application examples
•
Level range monitoring
•
Dry-run prevention
•
Overfill prevention
8.4
Safety certified identification
All Rosemount 5408:SIS Level Transmitters must be identified as safety certified before
installing into SIS systems.
Procedure
1. Verify the transmitter model code starts with “5408F”.
2. Verify the software (SW) is 1.A3 or later.
Figure 8-2: Identification
!
MODEL 5408
FM16US0010X
(
$
%
&
'
SIL 2
A. Model code
B. Serial number
C. SW version
D. Yellow stripe for locating device from distance
E. Yellow tag for locating device from distance
Reference Manual
Safety Instrumented Systems (SIS) requirements
00809-0100-4408
February 2020
Rosemount 5408 and 5408:SIS Level Transmitters
151
Summary of Contents for Rosemount 5408
Page 4: ...4 ...
Page 8: ...Contents Reference Manual February 2020 00809 0100 4408 viii Reference Manual ...
Page 10: ...Introduction Reference Manual February 2020 00809 0100 4408 10 Reference Manual ...
Page 20: ...Transmitter overview Reference Manual February 2020 00809 0100 4408 20 Reference Manual ...
Page 72: ...Mechanical installation Reference Manual February 2020 00809 0100 4408 72 Reference Manual ...
Page 100: ...Operation Reference Manual February 2020 00809 0100 4408 100 Reference Manual ...
Page 240: ...Product certifications Reference Manual February 2020 00809 0100 4408 240 Reference Manual ...
Page 242: ...Product certifications Reference Manual February 2020 00809 0100 4408 242 Reference Manual ...
Page 244: ...Product certifications Reference Manual February 2020 00809 0100 4408 244 Reference Manual ...
Page 246: ...Product certifications Reference Manual February 2020 00809 0100 4408 246 Reference Manual ...
Page 248: ...Product certifications Reference Manual February 2020 00809 0100 4408 248 Reference Manual ...