Markings:
HART
™
: Ex ia IIC T5/T4 Ga, T5(–20 °C ≤ T
a
≤ +40 °C), T4(–20 °C
≤ T
a
≤ +70 °C)
PROFIBUS
®
: Ex ia IIC T4 (–20 °C ≤ T
a
≤ +60 °C)
Parameter
PROFIBUS
Voltage U
i
30 V
Current I
i
300 mA
Power P
i
1.3 W
Capacitance C
i
0 µF
Inductance L
i
0 mH
Special Conditions for Safe Use (X):
1. The apparatus is not capable of withstanding the 500 V insulation
test required by clause 6.3.12 of EN60079-11:2012. This must be
taken into account when installing the apparatus.
2. The enclosure may be made of aluminum alloy and given a protective
polyurethane paint finish; however care should be taken to protect it
from impact or abrasion if located in Zone 0.
3.8
Brazil
I2 INMETRO Intrinsic Safety
Certificate:
UL-BR 13.0584X
Standards:
ABNT NBR IEC60079-0:2008 + Errata 1:2011, ABNT NBR
IEC60079-11:2009
Markings:
HART
™
: Ex ia IIC T5/T4 Ga, T5(–20 °C ≤ T
a
≤ +40 °C), T4(–20 °C
≤ Ta ≤ +70 °C) Fieldbus: Ex ia IIC T4 Ga (–20 °C ≤ T
a
≤ +60 °C)
HART
PROFIBUS
®
Voltage U
i
30 V
30 V
Current I
i
200 mA
300 mA
Power P
i
0.9 W
1.3 W
Capacitance C
i
0.012 µF
0 µF
Inductance L
i
0 mH
0 mH
Special Conditions for Safe Use (X):
1. If the equipment is fitted with an optional 90 V transient suppressor,
it is not capable of withstanding the 500 V insulation test required by
June 2020
Quick Start Guide
Quick Start Guide
23