The LCD display will continuously scroll through the selected
parameters.
12. To review the transmitter configuration, navigate using the manual
setup navigation sequences for “AI Block Unit Setup”, “Change
Damping”, and “Set up LCD Display”.
13. Change any values as necessary.
14. Return to the Overview screen.
15. If mode is “Not in Service”, click
Change
, and then select
Return All
to Service
.
Note
If hardware or software write protection is not needed,
can
be skipped.
16. Set switches and software write lock.
a) Check switches (see
Note
The write lock switch can be left in the locked or unlocked
position. The simulate enable/disable switch may be in either
position for normal device operation.
2.5.5
Enable software write lock
Procedure
1. Navigate from the
Overview
screen.
a) Select
Device Information
.
b) Select the
Security and Simulation
tab.
2. Perform Write Lock Setup to enable software write lock.