2.5.6
AI block configuration parameters
Use the pressure example for a guide.
Parameters Enter data
Channel
1 = Pressure, 2 = Sensor temp, 12 = SPM mean, 13 = SPM standard
deviation
L_Type
Direct, indirect, or square root
XD_Scale
Scale and engineering units
Pa
bar
torr at 0 °C
ft H
2
O at 4 °C
m H
2
O at 4 °C
kPa
mbar
kg/cm
2
ft H
2
O at 60 °F
mm Hg at 0 °C
mPa psf
kg/cm
2
ft H
2
O at 68 °F
cm Hg at 0 °C
hPa
Atm
in H
2
O at 4 °C
mm H
2
O at 4 °C
in Hg at 0 °C
°C
psi
in H
2
O at 60 °F
mm H
2
O at 68 °C in Hg at 0 °C
°F
g/cm2
2
in H
2
O at 68 °F
cm H
2
O at 4 °C
Out_Scale
Scale and engineering units
(1)
Select only the units that are supported by the device.
Table 2-1: Pressure example
Parameters
Enter data
Channel
1
L_Type
Direct
XD_Scale
See list of supported engineering
units
.
Out_Scale
Set values outside operating range.
(1)
Select only the units that are supported by the device.
2.5.7
Display pressure on the LCD display
Select the Pressure check box on the Display Configuration screen.
2.6
Zero trim the transmitter
Procedure to zero trim the transmitter, which is a single-point adjustment
used for compensating mounting position and line pressure effects.
Prerequisites
When performing a zero trim, ensure that the equalizing valve is open and
all wet legs are filled to the correct level.
June 2020
Quick Start Guide
Quick Start Guide