5.3.5
Device warnings
Device warnings are signaled in the Input Register Device Warnings. Warnings are less serious than errors.
Detailed information about the different warning types can be found in Input registers 1050 - 1070.
Table 5-7. Device warnings
numHiddenErrors
Input register no. 1132.
Number of hidden errors.
Contact Emerson Automation Solutions
/Rosemount TankGauging service department.
numOtherErrors
Input register no. 1134.
Number of other errors.
1.
The register number refers to the internal Input Register of the Rosemount 2230 database.
Note that Input Register data from the Rosemount 2230 display is temporarily stored in the Input Register database of the Rosemount 2410 Tank Hub.
The Input Registers presented in TankMaster WinSetup refer to the internal register area of the Rosemount 2410. Therefore, for tank 1 you will have to add
16000 to the Rosemount 2230 internal register number as given by
in order to find the register presented by WinSetup. For the second and third
Rosemount 2230 display you will have to add 18000 and 20000, respectively.
Message
Description
Action
RAM warning
Input register no. 1050
(1)
.
The application software could
not be started.
Bit 0: Stack low
1.
The register number refers to the internal Input Register of the Rosemount 2230 database. The Input Registers presented in TankMaster WinSetup
refer to the internal register area of the Rosemount 2410 Tank Hub. For tank 1 add 16000 to the Rosemount 2230 internal register number as given
by
in order to find the register presented by WinSetup. For the second and third 2230 display you will have to add 18000 and 20000,
respectively.
Contact Emerson Automation Solutions
/Rosemount TankGauging service department.
FPROM warning
Input register no. 1052
Not used
Hreg warning
Input register no. 1054.
Bit 0: Default Holding register
values used
Contact Emerson Automation Solutions
/Rosemount TankGauging service department.
Other memory warning
Input register no. 1056
Not used
Display warning
Input register no. 1058
Not used
Modem warning
Input register no. 1060
Not used
Other hardware warning
Input register no. 1062
Not used
Measurement warning
Input register no. 1064
Not used
ITEMP warning
Input register no. 1066.
Bit 0: The internal temperature is
out of range
Contact Emerson Automation Solutions
/Rosemount TankGauging service department.
Software warning
Input register no. 1068.
Bit 1: Stack low (less then 10% left
of stack)
Bit 2: Software startup
Configuration warning
Input register no. 1070
Bit 11: Invalid Model Code String
Bit 12: Invalid Model Code
Message (continued)
Description
Action
Summary of Contents for Rosemount 2230
Page 1: ...Reference Manual 00809 0100 2230 Rev CA July 2017 Rosemount 2230 Graphical Field Display ...
Page 2: ......
Page 4: ...ii Reference Manual 00809 0100 2230 Rev CA Title Page July 2017 Title Page ...
Page 16: ...6 Reference Manual 00809 0100 2230 Rev CA Introduction July 2017 Introduction ...
Page 28: ...18 Reference Manual 00809 0100 2230 Rev CA Overview July 2017 Overview ...
Page 44: ...34 Reference Manual 00809 0100 2230 Rev CA Installation July 2017 Installation ...
Page 154: ...144 Reference Manual 00809 0100 2230 Rev CA Index July 2017 Index ...
Page 155: ......