Table 7-5: Input Parameters
Parameter
HART
Fieldbus/PROFIBUS
Voltage U
i
30 V
30 V
Current I
i
200 mA
300 mA
Power P
i
1 W
1.3 W
Capacitance C
i
12 nF
0 μF
Inductance L
i
0 mH
0 mH
Special Conditions for Safe Use (X):
1. If the equipment is fitted with an optional 90V transient suppressor, it
is incapable of withstanding the 500V isolation from earth test and this
must be taken into account during installation.
2. The enclosure may be made of aluminum alloy and given a protective
polyurethane paint finish; however, care should be taken to protect it
from impact or abrasion if located in Zone 0.
3. The equipment contains thin wall diaphragms. The installation,
maintenance and use shall take into account the environmental
conditions to which the diaphragms will be subjected. The
manufacturer’s instructions for installation and maintenance shall be
followed in detail to assure safety during its expected lifetime.
IG IECEx FISCO
Certificate
IECEx BAS 08.0045X
Standards
IEC60079-0:2011, IEC60079-11:2011
Markings
Ex ia IIC T4 Ga (–60 °C ≤ T
a
≤ +60 °C)
Table 7-6: Input Parameters
Parameter
FISCO
Voltage U
i
17.5 V
Current I
i
380 mA
Power P
i
5.32 W
Capacitance C
i
0 nF
Inductance L
i
0 μH
February 2019
Quick Start Guide
Quick Start Guide
29