Standards
CSA Std. C22.2 No. 142 - M1987, CSA Std. C22.2 No. 213 -
M1987, CSA Std. C22.2 No. 157 - 92, CSA Std. C22.2 No. 213 -
M1987, ANSI/ISA 12.27.01 – 2003, CAN/CSA-E60079-0:07,
CAN/CSA-E60079-11:02
Markings
Intrinsically safe for Class I, Division 1, Groups A, B, C, and D
when connected in accordance with Rosemount drawing
02051-1008. Ex ia IIC T3C. Single Seal. Enclosure Type 4X
IF Canada FISCO
Certificate
2041384
Standards
CSA Std. C22.2 No. 142 - M1987, CSA Std. C22.2 No. 213 -
M1987, CSA Std. C22.2 No. 157 - 92, CSA Std. C22.2 No. 213 -
M1987, ANSI/ISA 12.27.01 – 2003, CAN/CSA-E60079-0:07,
CAN/CSA-E60079-11:02
Markings
Intrinsically safe for Class I, Division 1, Groups A, B, C, and D
when connected in accordance with Rosemount drawing
02051-1008. Ex ia IIC T3C. Single Seal. Enclosure Type 4X
7.3.2 Europe
E1 ATEX Flameproof
Certificate
KEMA 08ATEX0090X
Standards
EN 60079-0:2012 + A11:2013, EN 60079-1:2014, EN
60079-26:2015
Markings
II 1/2 G Ex db IIC Ga/Gb T6(–60 °C ≤ T
a
≤ +70 °C), T4/T5 (–60
°C ≤ T
a
≤ +80 °C)
Table 7-1: Process Connection Temperature
Temperature class
Process temperature
Ambient temperature
T6
-60 °C to +70 °C
-60 °C to +70 °C
T5
-60 °C to +80 °C
-60 °C to +80 °C
T4
-60 °C to +120 °C
-60 °C to +80 °C
Special Conditions for Safe Use (X):
1. Appropriate cable, glands and plugs need to be suitable for a
temperature of 5°C greater than maximum specified temperature for
location where installed.
2. Non- standard paint options may cause risk from electrostatic
discharge. Avoid installations that could cause electrostatic build-up
on painted surfaces, and only clean the painted surfaces with a damp
February 2019
Quick Start Guide
Quick Start Guide
25