WARNING
Replacement equipment or spare parts not approved by Emerson for use as
spare parts could reduce the pressure retaining capabilities of the transmitter
and may render the instrument dangerous.
•
Use only bolts supplied or sold by Emerson as spare parts.
•
Refer to page 208 for a complete list of spare parts.
Improper assembly of manifolds to traditional flange can damage sensor
module.
•
For safe assembly of manifold to traditional flange, bolts must break back
plane of flange web (i.e., bolt hole) but must not contact sensor module
housing.
7.3 Product certifications
European Directive Information
A copy of the EC Declaration of Conformity can be found at the end of the
Quick Start Guide. The most recent revision of the EC Declaration of
Conformity can be found at
Ordinary Location Certification
As standard, the transmitter has been examined and tested to determine that
the design meets the basic electrical, mechanical, and fire protection
requirements by a nationally recognized test laboratory (NRTL) as accredited
by the Federal Occupational Safety and Health Administration (OSHA).
7.3.1 North America
E5 USA Explosionproof (XP) and Dust-Ignitionproof (DIP)
Certificate
FM16US0232
Standards
FM Class 3600 – 2011, FM Class 3615 – 2006, FM Class 3616 –
2011, FM Class 3810 – 2005, ANSI/NEMA 250 – 2008. ANSI/IEC
60529 2004
Markings
XP CL I, DIV 1, GP B, C, D; DIP CL II, DIV 1, GP E, F, G; CL III;
T5(-50 °C ≤ T
a
≤ +85 °C); Factory Sealed; Type 4X
I5 USA Intrinsic Safety (IS) and Nonincendive (NI)
Certificate
FM16US0231X
Standards
FM Class 3600 – 2011, FM Class 3610 – 2010, FM Class 3611 –
2004, FM Class 3810 – 2005, ANSI/NEMA 250 – 2008
February 2019
Quick Start Guide
Quick Start Guide
23