Quick Start Guide

00825-0400-4101, Rev BD

February 2019

Rosemount

 2051 Pressure Transmitter

and Rosemount 2051CF Series
Flowmeter

with PROFIBUS

®

 PA Protocol

Summary of Contents for Rosemount 2051CF series

Page 1: ...Quick Start Guide 00825 0400 4101 Rev BD February 2019 Rosemount 2051 Pressure Transmitter and Rosemount 2051CF Series Flowmeter with PROFIBUS PA Protocol ...

Page 2: ...rs and switches 11 Connect wiring and power up 12 Basic configuration 16 Trim the transmitter 19 Rosemount 2051 Product Certifications 20 Quick Start Guide February 2019 2 Rosemount 2051 Pressure Transmitter and Rosemount 2051CF Series Flowmeter Quick Start Guide ...

Page 3: ... side of the line 2 Mount beside or below the taps 3 Mount the transmitter so the drain vent valves are oriented upward 1 2 Gas applications Procedure 1 Place taps in the top or side of the line 2 Mount beside or above the taps February 2019 Quick Start Guide Quick Start Guide 3 ...

Page 4: ...ide or below the taps 3 Fill impulse lines with water Example Figure 1 1 Panel and Pipe Mounting Panel mount 1 Pipe mount Coplanar flange Traditional flange Quick Start Guide February 2019 4 Rosemount 2051 Pressure Transmitter and Rosemount 2051CF Series Flowmeter Quick Start Guide ...

Page 5: ...nge adapters follow the assembly guidelines to ensure a tight seal for optimal performance characteristics of the transmitters Use only bolts supplied with the transmitter or sold by Emerson as spare parts Figure 1 2 illustrates common transmitter assemblies with the bolt length required for proper transmitter assembly February 2019 Quick Start Guide Quick Start Guide 5 ...

Page 6: ... Process Management representative for more information Carbon steel bolts do not require lubrication and the stainless steel bolts are coated with a lubricant to ease installation However no additional lubricant should be applied when installing either type of bolt Use the following bolt installation procedure Procedure 1 Finger tighten the bolts 2 Torque the bolts to the initial torque value usi...

Page 7: ... 2024 3095 each require a unique O ring see Figure 1 3 Use only the O ring designed for the corresponding flange adapter WARNING Failure to install proper flange adapter O rings may cause process leaks which can result in death or serious injury The two flange adapters are distinguished by unique O ring grooves Only use the O ring that is designed for its specific flange adapter as shown below Whe...

Page 8: ...ctory if other Ingress Protection ratings are required For M20 threads install conduit plugs to full thread engagement or until mechanical resistance is met 1 7 In line gage transmitter orientation The low side pressure port atmospheric reference on the in line gage transmitter is located in the neck of the transmitter behind the housing The vent path is 360 around the transmitter between the hous...

Page 9: ...tion including but not limited to paint dust and lubrication by mounting the transmitter so fluids can drain away Figure 1 4 In line Gage Low Side Pressure Port A A Pressure port location February 2019 Quick Start Guide Quick Start Guide 9 ...

Page 10: ...nch 2 Rotate the housing clockwise to the desired location 3 If the desired location cannot be achieved due to thread limit rotate the housing counterclockwise to the desired location up to 360 from thread limit 4 Re tighten the housing rotation set screw to no more than 7 in lbs when desired location is reached Quick Start Guide February 2019 10 Rosemount 2051 Pressure Transmitter and Rosemount 2...

Page 11: ... jumper also prevents changes made using the Local Operator Interface 3 2 Simulate The simulate jumper is used in conjunction with the analog input AI block This jumper is used to simulate the pressure measurement and is used as a lock out feature for the AI block To enable the simulate feature the jumper must be moved to the ON position after power is applied This feature prevents the transmitter...

Page 12: ...nal is not recommended as the connection may be more susceptible to loosening over time or under vibration 5 Ensure proper grounding It is important that the instrument cable shield 6 Be trimmed close and insulated from touching the transmitter housing 7 Be connected to the next shield if cable is routed through a junction box 8 Be connected to a good earth ground at the power supply end 9 Plug an...

Page 13: ...Example Figure 4 1 Terminals A B A Power terminals B Ground terminal February 2019 Quick Start Guide Quick Start Guide 13 ...

Page 14: ...in conduit or open trays with power wiring or near heavy electrical equipment Grounding terminations are provided on the outside of the electronics housing and inside the terminal compartment These grounds are used when transient protect terminal blocks are installed or to fulfill local regulations See step 2 below for more information on how the cable shield should be grounded Quick Start Guide F...

Page 15: ...ed until there is no gap between the cover and the housing 7 Plug and seal unused conduit connections 4 1 1 Power supply The dc power supply should provide power with less than two percent ripple The transmitter requires between 9 and 32 Vdc at the terminals to operate and provide complete functionality 4 1 2 Power conditioner The DP PA coupler link often includes an integrated power conditioner 4...

Page 16: ...ure Transmitter is shipped with a temporary address of 126 This must be changed to a unique value between 0 and 125 in order to establish communication with the host Usually addresses 0 2 are reserved for masters or couplers therefore transmitter addresses between 3 and 125 are recommended Address can be set via either LOI see Table 5 1 and Figure 5 1 Class 2 master see Class 2 Master Manual for s...

Page 17: ... 1 Changes between Save and Cancel Enter Selects menu category Enters character and advances Saves 1 Characters blink when they can be changed Figure 5 1 LOI Menu 1 ADDRESS 6 IDENTIFICATION 7 EXIT 4 DAMPING 5 DISPLAY 3 UNITS 2 CALIBRATION PRESSURE FLOW LEVEL TEMPERATURE 0 126 ZERO LOWER SENSOR UPPER SENSOR RESET FACTORY 5 3 Class 2 Master The Rosemount 2051 PROFIBUS DD and DTM files are available ...

Page 18: ...ode Put Analog Input Block into Auto mode 5 4 Host integration 5 4 1 Control host Class 1 The Rosemount 2051 device utilizes condensed status as recommended by the Profile 3 02 specification and NE 107 See manual for condensed status bit assignment information The appropriate GSD file must be loaded on the control host Rosemount 2051 specific rmt3333 gsd or Profile 3 02 Generic pa139700 gsd These ...

Page 19: ...o trim via LOI see Table 5 1 and Figure 5 1 Class 2 master see Zero trim via Class 2 Master for parameter settings 6 1 Zero trim via Class 2 Master Procedure 1 Place the transducer block into Out of Service OOS mode 2 Apply zero pressure to device and allow to stabilize 3 Go to Basic Setup Calibration and set the lower calibration point to 0 0 4 Place the transducer block to AUTO mode February 201...

Page 20: ...ents by a nationally recognized test laboratory NRTL as accredited by the Federal Occupational Safety and Health Administration OSHA Hazardous location certifications Note Device ambient temperature ratings and electrical parameters may be limited to the levels dictated by the hazardous location certificate parameters 7 1 Overview This Appendix contains information on approved manufacturing locati...

Page 21: ...ST Asia Pacific 65 777 8211Europe Middle East Africa 49 8153 9390 North American Response Center Equipment service needs 1 800 654 7768 24 hours includes Canada Outside of these areas contact your local Emerson representative CAUTION The products described in this document are NOT designed for nuclear qualified applications Using non nuclear qualified products in applications that require nuclear ...

Page 22: ...nstall and tighten process connectors before applying pressure Do not attempt to loosen or remove flange bolts while the transmitter is in service Electrical shock can result in death or serious injury Avoid contact with the leads and terminals High voltage that may be present on leads can cause electrical shock 7 2 1 WARNING Before connecting a HART communicator in an explosive atmosphere ensure ...

Page 23: ...Declaration of Conformity can be found at www Emerson com Ordinary Location Certification As standard the transmitter has been examined and tested to determine that the design meets the basic electrical mechanical and fire protection requirements by a nationally recognized test laboratory NRTL as accredited by the Federal Occupational Safety and Health Administration OSHA 7 3 1 North America E5 US...

Page 24: ...potential risk of ignition by impact or friction Care must be taken into account during installation and use to prevent impact and friction E6 Canada Explosion Proof Dust Ignition Proof Certificate 2041384 Standards CAN CSA C22 2 No 0 10 CSA Std C22 2 No 25 1966 CSA Std C22 2 No 30 M1986 CAN CSA C22 2 No 94 M91 CSA Std C22 2 No 142 M1987 CAN CSA C22 2 No 157 92 CSA Std C22 2 No 213 M1987 CAN CSA E...

Page 25: ...rawing 02051 1008 Ex ia IIC T3C Single Seal Enclosure Type 4X 7 3 2 Europe E1 ATEX Flameproof Certificate KEMA 08ATEX0090X Standards EN 60079 0 2012 A11 2013 EN 60079 1 2014 EN 60079 26 2015 Markings II 1 2 G Ex db IIC Ga Gb T6 60 C Ta 70 C T4 T5 60 C Ta 80 C Table 7 1 Process Connection Temperature Temperature class Process temperature Ambient temperature T6 60 C to 70 C 60 C to 70 C T5 60 C to 8...

Page 26: ...079 0 2012 A11 2013 EN60079 11 2012 Markings II 1 G Ex ia IIC T4 Ga 60 C Ta 70 C Table 7 2 Input Parameters Input parameter HART Fieldbus PROFIBUS Voltage Ui 30 V 30 V Current Ii 200 mA 300 mA Power Pi 1 W 1 3 W Capacitance Ci 0 012 μF 0 μF Inductance Li 0 mH 0 mH Special Conditions for Safe Use X 1 If the equipment is fitted with an optional 90V transient suppressor it is incapable of withstandin...

Page 27: ... Standards EN60079 0 2012 A11 2013 EN60079 15 2010 Markings II 3G Ex nA IIC T4 Gc 40 C Ta 70 C Special Condition for Safe Use X 1 If the equipment is fitted with an optional 90V transient suppressor it is incapable of withstanding the 500V electrical strength test as defined in clause 6 5 1 of by EN 60079 15 2010 This must be taken into account during installation ND ATEX Dust Certificate Baseefa0...

Page 28: ...nditions to which the diaphragm shall be subjected The manufacturer s instructions for installation and maintenance shall be followed in detail to assure safety during its expected lifetime 2 Appropriate cable glands and plugs need to be suitable for a temperature of 5 C greater than maximum specified temperature for location where installed 3 Flameproof joints are not intended for repair 4 Non st...

Page 29: ...are should be taken to protect it from impact or abrasion if located in Zone 0 3 The equipment contains thin wall diaphragms The installation maintenance and use shall take into account the environmental conditions to which the diaphragms will be subjected The manufacturer s instructions for installation and maintenance shall be followed in detail to assure safety during its expected lifetime IG I...

Page 30: ...ecial Condition for Safe Use X 1 If fitted with a 90V transient suppressor the equipment is not capable of withstanding the 500V electrical strength test as defined in clause 6 5 1 of IEC60079 15 2010 This must be taken into account during installation 7 3 4 Brazil E2 INMETRO Flameproof Certificate UL BR 14 0375X Standards ABNT NBR IEC60079 0 2008 Errata 1 2011 ABNT NBR IEC 60079 1 2009 Errata 1 2...

Page 31: ... C Table 7 7 Input Parameters Parameter HART Fieldbus PROFIBUS Voltage Ui 30 V 30 V Current Ii 200 mA 300 mA Power Pi 1 W 1 3 W Capacitance Ci 12 nF 0 Inductance Li 0 0 Special Conditions for Safe Use X 1 If the equipment is fitted with an optional 90 V transient suppressor it is incapable of withstanding the 500 V insulation from earth test and this must be taken into account during installation ...

Page 32: ...to protect it from impact and abrasion when located in atmospheres that require EPL Ga 7 3 6 Japan E4 Japan Flameproof Certificate TC20598 TC20599 TC20602 TC20603 HART TC20600 TC20601 TC20604 TC20605 Fieldbus Markings Ex d IIC T5 7 3 7 Technical Regulations Customs Union EAC EM EAC Flameproof Certificate TC RU C US AA87 B 00588 Markings Ga Gb Ex d IIC X T5 50 C Ta 80 C T6 50 C Ta 65 C Special Cond...

Page 33: ... V transient suppressor it is incapable of withstanding a 500V isolation from earth test and this must be taken into account during installation KA Combination of E1 I1 and K6 KB Combination of K5 and K6 KC Combination of E1 I1 and K5 KD Combination of K1 K5 and K6 KP Combination of EP and IP KM Combination of EM and IM 7 4 Additional Certifications SBS American Bureau of Shipping ABS Type Approva...

Page 34: ...ske Veritas DNV Type Approval Certificate TAA000004F Intended Use DNV GL Rules for Classification Ships and offshore units Application Location classes Type Rosemount 2051 Temperature D Humidity B Vibration A EMC B Enclosure D SLL Lloyds Register LR Type Approval Certificate 11 60002 Application Environmental categories ENV1 ENV2 ENV3 and ENV5 Quick Start Guide February 2019 34 Rosemount 2051 Pres...

Page 35: ...ssen MN 55317 9685 USA to which this declaration relates is in conformity with the provisions of the European Union Directives including the latest amendments as shown in the attached schedule Assumption of conformity is based on the application of the harmonized standards and when applicable or required a European Union notified body certification as shown in the attached schedule signature Vice ...

Page 36: ... Certificate of Assessment Certificate No 12698 2018 CE ACCREDIA Module H Conformity Assessment Other Standards Used ANSI ISA 61010 1 2004 EN 60770 1 1999 Note previous PED Certificate No 59552 2009 CE HOU DNV All other Rosemount 2051 3051 Wireless Pressure Transmitters Sound Engineering Practice Transmitter Attachments Diaphragm Seal Process Flange or Manifold Sound Engineering Practice Rosemount...

Page 37: ...mercate MB Italy Note equipment manufactured prior to 20 October 2018 may be marked with the previous PED Notified Body number previous PED Notified Body information was as follows Det Norske Veritas DNV Notified Body Number 0575 Veritasveien 1 N 1322 Hovik Norway ATEX Notified Body SGS FIMCO OY Notified Body Number 0598 P O Box 30 Särkiniementie 3 00211 HELSINKI Finland ATEX Notified Body for Qua...

Page 38: ...ᦞ SJ T11364Ⲵ㿴ᇊ㘼ࡦ This table is proposed in accordance with the provision of SJ T11364 O Ѫ䈕䜘ԦⲴᡰᴹ 䍘ᶀᯉѝ䈕ᴹᇣ 䍘Ⲵਜ਼䟿 վҾGB T 26572ᡰ㿴ᇊⲴ䲀䟿㾱 O Indicate that said hazardous substance in all of the homogeneous materials for this part is below the limit requirement of GB T 26572 X Ѫ 䈕䜘Ԧᡰ Ⲵᡰᴹ 䍘ᶀᯉ䟼ˈ㠣ቁᴹа 䍘ᶀᯉѝ䈕ᴹᇣ 䍘Ⲵਜ਼䟿儈ҾGB T 26572ᡰ㿴ᇊⲴ䲀䟿㾱 X Indicate that said hazardous substance contained in at least one of the homoge...

Page 39: ...February 2019 Quick Start Guide Quick Start Guide 39 ...

Page 40: ... Baar Switzerland 41 0 41 768 6111 41 0 41 768 6300 RFQ RMD RCC Emerson com Asia Pacific Regional Office Emerson Automation Solutions 1 Pandan Crescent Singapore 128461 65 6777 8211 65 6777 0947 Enquiries AP Emerson com Middle East and Africa Regional Office Emerson Automation Solutions Emerson FZE P O Box 17033 Jebel Ali Free Zone South 2 Dubai United Arab Emirates 971 4 8118100 971 4 8865465 RFQ...