99
Reference Manual
00809-0100-4100, Rev AA
Appendix A: Specifications and Reference Data
June 2012
Specifications and Reference Data
P3
Cleaning for <1 PPM Chlorine/Fluorine
Pressure Calibration
Expanded
P4
Calibrate at Line Pressure
(Specify Q48 on order for corresponding certificate)
High Accuracy
Standard
Standard
P8
(12)
0.04% Accuracy to 5:1 turndown (Range 2-4)
★
Flange Adapters
Standard
Standard
DF
(13)
1
/
2
-14 NPT flange adapter(s)
★
D3
¼–18 NPT Process Connections (No flange adapters)
Vent/Drain Valves
Expanded
D7
Coplanar Flange Without Drain/Vent Ports
RC
1
/
4
RC
1
/
2
Process Connection
Expanded
D9
(14)
RC ¼ Flange with RC ½ Flange Adapter, CS - SST
Max Static Line Pressure
Standard
Standard
P9
4500 psig (310 bar) Static Pressure Limit
(3051CD Ranges 2–5 only)
★
Surface Finish
Standard
Standard
Q16
Surface finish certification for sanitary remote seals
★
Toolkit Total System Performance Reports
Standard
Standard
QZ
Remote Seal System Performance Calculation Report
★
Typical Model Number: 3051CD 2 A 2 2 A 1 A B4$13857 780
(1)Wireless output (code X) available in absolute measurement type (Code A) with only range 1-4, 316L SST isolating diaphragm material
(code 2), silicone fill fluid (code 1), and housing code (code P).
(2)Wireless output (code X) available in draft range 0 with only 316L SST isolating diaphragm (code 2), silicone fill fluid (code 1), housing
code (code P), process flange (code 0), glass-filled o-ring (code A), and bolting option (code L4).
(3)Materials of Construction comply with recommendations per NACE MR0175/ISO 15156 for sour oil field production environments.
Environmental limits apply to certain materials. Consult latest standard for details. Selected materials also conform to NACE MR0103 for
sour refining environments.
(4)Requires 0 code in Materials of Construction for Alternate Process Connection.
(5)Not valid with optional code P9 for 4500 psi Static Pressure.
(6)“Assemble-to” items are specified separately and require a completed model number.
(7)Process Flange limited to Coplanar (codes 2, 3, 5, 7, 8) or Traditional (H2, H3, H7).
(8)Not valid with optional code D9 for RC
1
/
2
Adaptors.
(9)Not valid for optional codes DF and D9 for Adaptors.
(10)Panel mounting bolts are not supplied.
(11)Not available with Alloy C-276 isolator (3 code), tantalum isolator (5 code), all Cast Alloy C-276 flanges, all plated CS flanges, all DIN
flanges, all Level flanges, assemble-to manifolds (S5 and S6 codes), assemble-to seals (S1 and S2 codes), assemble-to primary elements (S3
and S4 codes), surface finish certification (Q16 code), and remote seal system report (QZ code).
(12)Only available with Standard 3051. See specification section for more information.
(13)Not valid with Alternate Process Connection options S3, S4, S5, and S6.
Table 1. 3051C Coplanar Pressure Transmitters Ordering Information
★
The Standard offering represents the most common options. The starred options (
★
) should be selected for best delivery.
__
The Expanded offering is subject to additional delivery lead time.
Summary of Contents for Rosemount 2051 Wireless Series
Page 2: ......
Page 12: ...4 Reference Manual 00809 0100 4102 Rev AA Section 1 Introduction June 2012 Introduction ...
Page 32: ...24 Reference Manual 00809 0100 4102 Rev AA Section 2 Configuration June 2012 Configuration ...
Page 110: ......
Page 113: ......
Page 117: ...iv Reference Manual 00809 0100 4100 Rev AA Title Page June 2012 ...
Page 123: ...x Reference Manual 00809 0100 4100 Rev AA Table of Contents June 2012 Table of Contents ...
Page 167: ...44 Reference Manual 00809 0100 4100 Rev AA Section 3 Installation June 2012 Installation ...
Page 168: ...45 Reference Manual 00809 0100 4100 Rev AA Section 3 Installation June 2012 Installation ...
Page 169: ...46 Reference Manual 00809 0100 4100 Rev AA Section 3 Installation June 2012 Installation ...
Page 249: ......