Five-valve Natural Gas configurations shown:
Note
Do not open the low side equalize valve before the high side equalize valve. Doing so will
overpressure the transmitter.
Test
(Plugged)
Test
(Plugged)
Equalize
(closed)
Process
Isolate
(open)
Isolate
(open)
H
L
In normal operation, the two block
valves between the process and
instrument ports will be open, and the
equalizing valves will be closed.
Process
Equalize
(closed)
Drain
Vent
Test
(Plugged)
Test
(Plugged)
Equalize
(closed)
Process
Isolate
(closed)
Isolate
(open)
H
L
1.
To zero the 3051, first close
the block valve on the low
pressure (downstream) side
of the transmitter.
Process
Equalize
(closed)
Drain
Vent
Test
(Plugged)
Test
(Plugged)
Equalize
(closed)
Process
Isolate
(closed)
Isolate
(open)
H
L
2.
Open the equalize valve on
the high pressure (upstream)
side of the transmitter.
Process
Equalize
(open)
Drain Vent
(closed)
Summary of Contents for Rosemount 2051 Wireless Series
Page 2: ......
Page 12: ...4 Reference Manual 00809 0100 4102 Rev AA Section 1 Introduction June 2012 Introduction ...
Page 32: ...24 Reference Manual 00809 0100 4102 Rev AA Section 2 Configuration June 2012 Configuration ...
Page 110: ......
Page 113: ......
Page 117: ...iv Reference Manual 00809 0100 4100 Rev AA Title Page June 2012 ...
Page 123: ...x Reference Manual 00809 0100 4100 Rev AA Table of Contents June 2012 Table of Contents ...
Page 167: ...44 Reference Manual 00809 0100 4100 Rev AA Section 3 Installation June 2012 Installation ...
Page 168: ...45 Reference Manual 00809 0100 4100 Rev AA Section 3 Installation June 2012 Installation ...
Page 169: ...46 Reference Manual 00809 0100 4100 Rev AA Section 3 Installation June 2012 Installation ...
Page 249: ......