PACMotion VFD Syllabus
Section 5
GFK-3167B
December 2020
PROFINET Controller Demo (Note 2)
16
5.4
Bus Specific Technical Data
Baud rate
10/100 Mbaud in full-duplex mode
Connection technology
2 × RJ45
5.5
Hardware Insertion and Removal
Remove power from the VFD. Using a T9 driver bit, backout the 2 option module screws
approximately 4 or 5 turns each. This should allow the locking tabs to retract to a flat
position. Insert the module into the VFD Fieldbus option module cage and gently press it
into place. Secure the T9 screws until they touch the module. This will engage the locking
tabs to hold it in place. Do not overtighten.
(Note: If the T9 screws are not backed out first the module will not insert or remove
properly.)
To remove the option module remove power from the VFD. Using a T9 driver bit back out
the option module 2 screws approximately 4 or 5 turns each. Gently pull the module out
by pulling on the screws.
5.6
PROFINET Slave Module Settings
1.
With the PROFINET option module installed power up the VFD.
Using the PROFINET DCP tool, which is part of the PAC Machine Edition Utilities, set the
following VFD PROFINET Slave values example:
Device Name
IP Address
vfd-1
192.168.0.2
2.
The QuickPanel Plus Ethernet Settings must be set to the following values:
IP address = 192.168.0.7
Subnet mask = 255.255.255.0
5.7
Starting the system
3.
Connect the VFD PROFINET option module to an available PROFINET port on the
CPE100 (the lower 3 ports) and the QuickPanel to the top ethernet port on the CPE100
and power up the devices.
This is done inside the official PACMotion VFD Demo case.